Assign I/O modules to the ET 200SP and set parameters
1. Change to the device view of an IM 155-6 PN HF.
2. In the properties of the interface module in the "General" area, assign "Section1" as the
name for tunnel section 1.
3. Select the following modules in succession from the hardware catalog. Assign the
modules to the interface module from slot 1 to 6:
– DQ 4x24VDC/2A ST (for traffic lights)
– DQ 4x24VDC/2A ST (for barrier)
– AI 4xU/I 2-wire ST (for outdoor light, indoor light and air-quality sensors)
– DQ 4x24VDC/2A ST (for fans)
– DQ 4x24..230VAC/2A HF (for tunnel lighting)
– 1 server module (as termination of the configuration)
Figure 2-8
Assigning ET 200SP I/O modules
4. Double-click on the 3rd module DQ 4x24VDC/2A ST in the configuration (for fan).
5. In the module properties "General" > "Potential group", select "Enable new potential
group (light-colored BaseUnit)".
6. Double-click on the module DQ 4x24..230VAC/2A HF (for tunnel lighting).
7. In the module properties "General" > "Potential group", select "Enable new potential
group (light-colored BaseUnit)".
8. Double-click on the module AI 4xU/I 2-wire ST.
S7-1500R/H redundant system
Getting Started, 10/2018, A5E44910930-AA
Configuration
2.3 Configuring ET 200SP
27