Position Of Electrodes-Baffle - Ferroli SUN Series Installation, Use And Maintenance Instructions

Heating oil burner
Table of Contents

Advertisement

Available languages

Available languages

COMBUSTION HEAD AND AIR
DAMPER ADJUSTMENT (Fig. 8)
The combustion head is adjusted accord-
ing to burner flow rate. To adjust, rotate
the adjustment screw (B) clockwise or
anticlockwise until the notch on the rod
"A" coincides with the indicator.
This modifies the position of the deflec-
tor in relation to the draught tube and con-
sequently the passage of air.
The air flow rate is adjusted via screw "C".
When the burner shuts down, the air
damper closes automatically.
EXAMPLE OF COMBUSTION REGU-
LATION
The injector, pump pressure, combustion
head adjustment and air flow rate regula-
tion must be established according to the
flow rate required by the boiler, as indi-
cated in the following chart check com-
bustion.
Delivered heat
MODEL
output
BOILER
kW
kcal/h
GN1.02
23,3
20.000
GN1.03
34,9
30.000
GN1.04
46,5
40.000
* Regulations for without preheater burner version
POSITION OF ELECTRODES - BAFFLE (Fig. 9)
After having mounted the injector, check
that the electrodes and baffle are correctly
positioned according to the above listed
measurements.
Always check the measurements
whenever operations are carried out on
the head.
Fig. 9
Fig. 8
Heat rate
Burner
flow rate
kW
kcal/h
Kg/h
25,8
22.200
2,176
38,7
33.200
3,25
51,6
44.400
4,35
L
S.p.A.
A
B
Injector
US
Gall/h
Angle
Code
0,6
60°
3560154/0
0,85
60°
3560134/0
1,1
60°
3560128/0
*
*
*
1,0
60°
3560127/0
3
1
SUN
C
Pump
Head
pressure
adjustment
Bar
Tacca
L
12
6
18
12
10
22
12
15
27
*
*
*
12
18
31
Air
regulation
Tacca
5
10
15
*
15
9

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sun g.6 rSun g.6

Table of Contents