Testing of
high-set stage
Testing of the self-
supervision system
(IRF)
The switches of switchgroup SGR should be set
as follows:
Switch
1
2
3
4
5
6
7
8
Then the following signals are linked to the
output relays:
Output
Function
(terminals)
A (65-66) Tripping of stage I>
B (68-69)
(Tripping of stage I>>)
C (80-81) Signal on tripping of stage I>
(LED L3)
D (77-78) Start of stage I>> (LED L2)
E (71-72)
Signal on internal relay fault
(LED L1)
The self-supervision system and its operation
indicator IRF and output relay E can be tested
in the Trip-Test mode described in section
The high-set stage is tested in the same way as
the low-set stage. The clock measuring the
operate time is stopped by contact 68-69 when
output relay B operates.
Position
N.B. High test currents are permitted for short
1
durations only, because the wires, terminals and
1
the matching transformers of the relay have a
0
limited current-carrying capability. The test leads
0
should have an area of 4 mm
1
100 A can be connected to a 1 A energizing
0
input for 1 s and to a 5 A energizing input for
0
10 s.
0
"General characteristics of C-type relay mod-
ules" of this manual. The operation of output
relay E is indicated by the LED indicator L1.
2
. Then a current of
21