Timers
Timers in the base units of the MELSEC FX family
Device
Device identifier
Device type (for setting and polling)
Possible values (timer output)
Device address format
Timer setpoint value entry
Number of devices
and addresses
These timers are only available when special relay M8028 is set ("1"). The total number of 100 ms timers is then
reduced to 32 (T0–T31).
When special relay M8028 is set ("1"), the timers T32 to T62 operate as 10 ms timers.
4 – 8
100 ms
(Range 0.1 to 3276.7 s)
10 ms
FX
1S
(Range 0.01 to 327.67 s)
1 ms
(Bereich 0.001 to 32.767 s)
100 ms
(Range 0.1 to 3276.7 s)
10 ms
FX
1N
(Range 0.01 to 327.67 s)
1 ms
(Range 0.001 to 32.767 s)
100 ms
(Range 0.1 to 3276.7 s)
FX
2N
10 ms
(Range 0.01 to 327.67 s)
FX
2NC
1 ms
(Range 0.001 to 32.767 s)
100 ms
(Range 0.1 to 3276.7 s)
FX
3G
10 ms
FX
3GC
(Range 0.01 to 327.67 s)
FX
3GE
1 ms
(Range 0.001 to 32.767 s)
100 ms
(Range 0.1 to 3276.7 s)
100 ms/10 ms
FX
(Range 0.1 to 3276.7 s/
3S
0.01 to 327.67 s)
1 ms
(Range 0.001 to 32.767 s)
100 ms
(Range 0.1 to 3276.7 s)
FX
3U
10 ms
(Range 0.01 to 327.67 s)
FX
3UC
1 ms
(Range 0.001 to 32.767 s)
Devices in Detail
Timer types
Normal Timers
Retentive Timers
T
Bit device
0 or 1
Decimal
As a decimal integer constant. The setpoint can
be set either directly in the instruction or indi-
rectly in a data register.
63 (T0–T62)
31 (T32–T62)
1 (T63)
200 (T0–T199)
6 (T250–T255)
46 (T200–T245)
4 (T246–T249)
200 (T0–T199)
6 (T250–T255)
46 (T200–T245)
4 (T246–T249)
200 (T0–T199)
6 (T250–T255)
46 (T200–T245)
64 (T256–T319)
4 (T246–T249)
32 (T0–T31)
6 (T131–T137)
31 (T32–T62)
65 (T63–T127)
4 (T128–T131)
200 (T0–T199)
6 (T250–T255)
46 (T200–T245)
256 (T256–T511)
4 (T246–T249)