Panasonic CU-2TZ41TBE Service Manual page 41

Outdoor unit
Table of Contents

Advertisement

Diagnosis
Abnormality or
display
protection control
Indoor standby units
F17
freezing abnormality
Power factor correction
F90
(PFC) circuit protection
Refrigerant cycle
F91
abnormality
Compressor abnormal
F93
revolution
Compressor discharge
F94
pressure overshoot
protection
Outdoor cooling high
F95
pressure protection
Power transistor module
F96
overheating protection
Compressor overheating
F97
protection
Total running current
F98
protection
Outdoor direct current
F99
(DC) peak detection
Abnormality judgment
Protection operation
3 times happen within
40 minutes
4 times happen within
20 minutes
4 times happen within
60 minutes
4 times happen within
20 minutes
4 times happen within
20 minutes
4 occurrences within
20 minutes
4 times happen within
30 minutes
3 times happen within
30 minutes
3 times happen within
20 minutes
Continuous happen for
7 times
Problem
Wrong wiring and
connecting pipe,
-
expansion valve
leakage
Power factor
-
correction circuit
abnormal
Refrigeration cycle
-
abnormal
Compressor abnormal
-
evolution
Compressor discharge
-
pressure overshoot
Cooling high pressure
-
protection
Power transistor
-
module overheat
-
Compressor overheat 
Total current
-
protection
Power transistor
-
module current
protection
41
Check location
Check indoor/outdoor
connection wire and pipe
Indoor heat exchanger
sensor lead wire and
connector
Expansion valve lead
wire and connector
Outdoor PCB faulty
Insufficient refrigerant or
valve close
Power transistor module
faulty or compressor lock
Check refrigeration
system
Check refrigeration
system
Outdoor air circuit
PCB faulty
Outdoor air circuit (fan
motor)
Insufficient refrigerant
Check refrigeration
system
Power source or
compressor lock
Power transistor module
faulty or compressor lock