Step 2: Refrigerant leak detection through Electronic halogen leak detector and/or ultrasonic leak detector:
1. Use any one of below detector to check leaking.
Electronic halogen leak detector.
o
Switch on the unit.
Cover the test area from direct draft.
Pass the detection probe near test area and wait for audible and visible signals.
Ultrasonic Leak Detector
o
Make sure the area is quiet.
Switch on the ultrasonic leak detector.
Move the probe along your air conditioning system to test for leaks, and mark for repair.
2. Any leak detected at this level shall be repaired and retested, starting from "Step 1: Pressure test".
NOTE:
Always recover the refrigerant and Nitrogen gas into recovery cylinder after completion of a test.
You must use the detection equipment with Detectable Leak Rate of 10
Do not use refrigerant as test medium for system with total refrigerant charge more than 5kg.
Test shall be performed with dry Nitrogen or another non-flammable, non-reactive, dried gas. Oxygen, air or
mixtures containing them shall not be used.
Step 3: Evacuation of the equipment:
Do not purge the air with refrigerants but use a vacuum pump to vacuum the installation.
There is no extra refrigerant in the outdoor unit for air purging.
1. Connect a charging hose with a push pin to
the Low and High side of a charging set and
the service port of the 3-way valve.
Be sure to connect the end of the
o
charging hose with the push pin to the
service port.
2. Connect the center hose of the charging set to
a vacuum pump with check valve, or vacuum
pump adaptor.
3. Turn on the power switch of the vacuum pump
and make sure that the needle in the gauge
moves from 0 cmHg (0 MPa) to -76 cmHg
(-0.1 MPa). Then evacuate the air
approximately 10 minutes.
4. Close the Low and High side valves of the
charging set and turn off the vacuum pump.
Make sure that the needle in the gauge does
not move after approximately 5 minutes.
Note: BE SURE TO FOLLOW THIS
PROCEDURE IN ORDER TO AVOID
REFRIGERANT GAS LEAKAGE.
5. Disconnect the charging hose from the
vacuum pump and from the service port of the
3-way valves.
If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa), in step  above take the following measure:
-
If the leak stops when the piping connections are tightened further, continue working from step .
-
If the leak does not stop when the connections are retightened, repair location of leak.
-
Do not release refrigerant during piping work for installation and reinstallation.
-
Take care of the liquid refrigerant, it may cause frostbite.
-6
Pa.m
6. Tighten the service port caps of the 3-way
valve at a torque of 18 N•m with a torque
wrench.
7. Remove the valve caps of the both 3-way
valves. Position both of the valves to "OPEN"
using a hexagonal wrench (4 mm).
8. Mount valve caps onto the both 3-way valves.
Be sure to check for gas leakage.
o
Indoor Unit
Indoor Unit
Vacuum pump
adaptor
Vacuum
pump
CAUTION
27
3
/s or better.
3-way valve
Outdoor Unit
Close
Liquid side
3-way valve
Close
Gas side
3-way valve
Close
Liquid side
3-way valve
Close
Gas side
OPEN
OPEN