3. Warnings and Safety Precautions

IMPORTANT NOTICE
Carefully read the installation
instruction for the burner before
installation and putting into service.
Non-compliance or improper
installation renders the warranty nil
and void.
When installing accessory
components, follow the
corresponding instructions.
DANGER
WARNING!
due to electric current.
Before undertaking any work on the
burner and heating equipment, cut
off all electric power, e.g. by means
of the heater emergency OFF switch
outside the furnace room. Switching
off the regulating device is not
sufficient!
EQUIPMENT DAMAGE
CAUTION!
due to improper installation. Please
comply with engineering standards
as well as building and other legal
regulations regarding construction
and operation of the equipment!
EQUIPMENT DAMAGE
CAUTION!
This burner is equipped for use with
biological fuels with special
components.
Use only original spare parts.
EQUIPMENT DAMAGE
CAUTION!
due to improper cleaning and
maintenance. Perform cleaning and
maintenance steps as instructed,
whereby the entire system must be
tested for faultless functioning!
Eliminate any defects immediately to
avoid damaging the equipment!
IMPORTANT NOTICE
CONCERNING OIL STORAGE
For vegetable oils, storage
temperatures higher than 20° C and
lower than 8° C must be avoided.
Avoid exposure to light. Oil must be
removed from storage via a floating
device to guarantee sediment-free
oil quality. Oil storage, including
laying of the oil lines, must be
realized in such a manner that the
oil temperature upstream from the
burner is at least + 8° C .
IMPORTANT NOTICE
CONCERNING OIL TANK FILLING
The oil burner must be switched off
before filling the tank. To allow
floating particles to settle, it is
necessary to wait approx. 3 h after
filling before switching on the oil
burner again.
In case of leaky oil lines or an empty
tank, deflagrations may occur due to
air bubble formation.
Shutting down of burner for a given
period
If the heating system is being run on
vegetable oil, the burner must be
flushed with the fuels EL (extra light)
heating oil or automotive diesel for at
least 10 minutes before shutting
down the system for periods longer
than 14 days.
We reserve the right to make technical
changes!
Illustrations, functional steps and technical data
may deviate slightly due to ongoing
developments.
- 5 -