Connection Hints

Auxiliary Voltage and Signal Output
Direct Cable Connection: Solid or stranded conductor with connector sleeve for conductor
cross-sections from 0.5 mm
of the connecting cables (auxiliary voltage and signal output) must be at least 300 V AC.
Tightening Torque: min 0.5 Nm
The maximum rated current of the device is 0.5 A. To ensure proper selectivity in the fusing
sequence, the power supply line is to be equipped with a minimum 2 A circuit breaker (the
maximum value depends on the wiring of the cabinet). The circuit breaker must be installed
close to the device. The circuit breaker must be marked as a switch for the device.
Fiber Optic
Warning
Do not look directly into the fibre-optic elements or cables!
You have to comply with the permissible bending radii of the fiber optic cable. In other cases,
you may destroy the optical fibers.
30
2
2
to 2.5 mm
, corresponding to AWG 12 to 22. The rated voltage
Sync-Transceiver
E50417-K1074-C294-A1