Page 1
LT−ISOG26−1 Issue 1 Print 2 INSTALLATION INSTRUCTIONS 3.6 KVA IsoG2t & OWNER’S MANUAL SHORELINE ISOLATION TRANSFORMER Model 93-ISOG2/6-A E Charles Industries, Ltd. All rights reserved. Printed in the United States of America.
Do not store equipment on or next to transformer. This unit is designed to operate hot and must have free air flow to prevent over heating or charring of adjacent material. E Charles Industries, Ltd. All rights reserved. Printed in the United States of America.
Application Precaution These units are intended for hard-wired, permanent, on-board applications. Use of attachments not recom- mended or sold by Charles Marine Products may result in risk of fire, electrical shock or personal injury. Damaged Unit Precaution Do not operate the IsoG2 if it has received a sharp blow, been dropped, immersed in water or otherwise dam- aged.
Method 1 is most commonly used. Note: This diagram does not illustrate a complete system. Refer to the appropriate ABYC text. E Charles Industries, Ltd. All rights reserved. Printed in the United States of America.
Page 6
To Engine Negative Terminal or its Bus Transformer Shield (Insulated from Case and Core) Figure 2. Electrical Diagram − Method 1 (see Figure 4 for Wiring Connections) E Charles Industries, Ltd. All rights reserved. Printed in the United States of America.
Page 7
Type Plugs & Receptacles To Engine Negative Terminal or its Bus Transformer Shield Figure 3. Electrical Diagram − Method 2 (see Figure 5 for Wiring Connections) E Charles Industries, Ltd. All rights reserved. Printed in the United States of America.
Realign the IsoG2’s mounting holes with the drilled holes and fasten the unit to the bulkhead with the appropriate mounting hardware Firmly secure all mounting hardware. E Charles Industries, Ltd. All rights reserved. Printed in the United States of America.
5263 .660−.780 6/3 Cordset Various other cord grip connectors may be suitable for use with the IsoG2. Contact Charles Marine Products cus- tomer service for information. Overcurrent Protection Overcurrent protection must be provided at the time of installation by a circuit breaker on the primary (shore) sup- ply circuit.
Page 10
H1 H2 Wire is fed through the cord grip connector in 2 places Figure 4. Terminal Placement − Method 1 (See Figure 2 for Electrical Diagram) E Charles Industries, Ltd. All rights reserved. Printed in the United States of America.
No adjustment or maintenance is required for the IsoG2 other than periodic cleaning of the outside cabinet with a dry cloth and inspecting all connections for tightness and corrosion by a qualified service person. E Charles Industries, Ltd. All rights reserved. Printed in the United States of America.
WARRANTY & CUSTOMER SERVICE Warranty Charles Industries, Ltd., Marine Group warrants the IsoG2 will be free from defects in materials and workmanship which cause mechanical failure for one (1) year, as set forth in the Limited Warranty. Review this warranty care- fully for information on what is covered by its terms.
Page 13
60 pounds/27 kilograms Height 8.25 inches/21.0 centimeters Width 11.25 inches/28.6 centimeters Width (excluding the mounting flange) 8.25 inches/21.0 centimeters Depth 9.25 inches/23.6 centimeters g g g E Charles Industries, Ltd. All rights reserved. Printed in the United States of America.