Fluidwell F126-P-EG-IA-TP Manual

Flow computer for corrected gas volume

Advertisement

Quick Links

F126-P-EG-IA-TP
FLOW COMPUTER FOR CORRECTED GAS VOLUME
Signal input flowmeter - type P: pulse, Namur and coil
Signal input pressure - type IA: (0)4-20mA
Signal input temperature - type TP: PT100 2- or 3 wire
Signal output: 0/4-20mA / 0-10V ref. corrected flowrate
Options: Intrinsically Safe, Modbus communication
F-Series - Field mounted indicators for safe and hazardous areas. More info: www.fluidwell.com/fseries

Advertisement

Table of Contents
loading

Summary of Contents for Fluidwell F126-P-EG-IA-TP

  • Page 1 Signal input pressure - type IA: (0)4-20mA Signal input temperature - type TP: PT100 2- or 3 wire Signal output: 0/4-20mA / 0-10V ref. corrected flowrate Options: Intrinsically Safe, Modbus communication F-Series - Field mounted indicators for safe and hazardous areas. More info: www.fluidwell.com/fseries...
  • Page 2: Safety Instructions

     Intrinsically Safe applications: follow the instructions as mentioned in Chapter 5 and consult “Fluidwell F1..-..-XI - Documentation for Intrinsic Safety”. DISPOSAL At the end of its life this product should be disposed of according to local regulations regarding waste electronic equipment.
  • Page 3: About The Operation Manual

    Manual HF126PEN_EG_IA_TP_v0501_04 © Copyright 2003-2011 : Fluidwell bv - The Netherlands. Information in this manual is subject to change without prior notice. The manufacturer is not responsible for mistakes in this material or for incidental damage caused as a direct or indirect result of the delivery, performance or use of this material.
  • Page 4: Table Of Contents

    Page 4 CONTENTS MANUAL Safety instructions ............................2 Disposal ..............................2 Safety rules and precautionary measures ....................... 2 About the operation manual ..........................3 Introduction ..........................5 1.1. System description of the F126-P-EG ................... 5 Operational ..........................7 2.1. General ..........................7 2.2.
  • Page 5: Introduction

    SYSTEM DESCRIPTION OF THE F126-P-EG Functions and features The flowrate / totalizer model F126-P-EG-IA-TP is a microprocessor driven instrument designed for the calculation of corrected gas volume using flow equations. The unit displays compensated flowrate / total, line temperature and pressure.
  • Page 6 Page 6 Configuration of the unit The F126-P-EG was designed to be implemented in many types of applications. For that reason, a SETUP-level is available to configure your F126-P-EG according to your specific requirements. SETUP includes several important features, such as Span, measurement units, signal selection etc. All setting as are stored in EEPROM memory and will not get lost in case of power break-down or empty battery.
  • Page 7: Operational

    Page 7 OPERATIONAL 2.1. GENERAL  The F126-P-EG may only be operated by personnel who are authorized and trained by the operator of the facility. All instructions in this manual are to be observed.  Take careful notice of the " Safety rules, instructions and precautionary measures " in the front of this manual.
  • Page 8: Operator Information And Functions

    Page 8 2.3. OPERATOR INFORMATION AND FUNCTIONS In general, the F126-P-EG will always act function at Operator level. The information displayed is dependant up on the SETUP-settings. The signal generated by the connected flowmeter are measured by the F126-P-EG in the background, whichever screen refresh rate setting is chosen. After pressing a key, the display will be updated very quickly during a 30 second period, after which it will slow-down again.
  • Page 9: Configuration

    Page 9 CONFIGURATION 3.1. INTRODUCTION This and the following chapters are exclusively meant for electricians and non-operators. In these, an extensive description of all software settings and hardware connections are provided.  Mounting, electrical installation, start-up and maintenance of the instrument may only be carried out by trained personnel authorized by the operator of the facility.
  • Page 10 Page 10 Matrix structure SETUP-level: SCROLLING THROUGH SETUP-LEVEL Selection function-group and function: SETUP is divided into several function groups and functions. Each function has a unique number, which is displayed below the word "SETUP" at the bottom of the display. The number is a combination of two figures. The first figure indicates the function-group and the second figure the function.
  • Page 11 Page 11 To change or a select a value or value: To change a value, use  to select the digits and  to increase that value. To select a setting, both  and  can be used. When the new value is not valid, the increase sign or decrease-sign will be displayed while you are programming.
  • Page 12: Overview Functions Setup Level

    Page 12 3.2.2. OVERVIEW FUNCTIONS SETUP LEVEL SETUP FUNCTIONS AND VARIABLES TOTAL UNIT L - m3 - kg - lb - GAL - USGAL - bbl - no unit DECIMALS 0 - 1 - 2 - 3 (Ref: displayed value) K-FACTOR: 0.000010 - 9,999,999 DECIMALS K-FACTOR...
  • Page 13: Explanation Setup-Functions

    Page 13 3.2.3. EXPLANATION SETUP-FUNCTIONS 1 - TOTAL SETUP - 11 determines the measurement unit for total and accumulated MEASUREMENT UNIT total. The following units can be selected: L - m3 - kg - lb. - GAL - USGAL - bbl - _ (no unit). Alteration of the measurement unit will have consequences for operator and SETUP-level values.
  • Page 14: Flowrate

    Page 14 2 - FLOWRATE The settings for total and flowrate are entirely separate. In this way, different units of measurement can be used for each e.g. cubic meters for total and liters for flowrate. The display update time for flowrate is one second or more. Note: these settings also influence the analog output.
  • Page 15: Power Management

    Page 15 3 - POWER MANAGEMENT When used with the internal battery option, the user may hold the concern of reliable measurement over a long period of time. The F126-P-EG has several smart power management functions to extend the battery life time significantly. Two of these functions can be set: The calculation of the display-information influences the power LCD NEW consumption significantly.
  • Page 16: Temperature

    Page 16 5 - TEMPERATURE Conversion formula’s temperature units: xK = (x-273,15)°C = (9/5x-459,67)°F x°C = (x+273,15)K = 9/5x+32°F x°F = 5/9(x-32)°C = 5/9(x+459,67)K SETUP - 51 determines the displayed unit for the Operator DISPLAY UNIT The following units can be selected: °C - °F - K Do select here the number of wires of the two PT100 elements - two or NO.
  • Page 17: Pressure

    Page 17 6 - PRESSURE SETUP - 61 determines the measurement unit for pressure. MEASURING UNIT The following units can be selected: mbar - bar - psi - no unit With this setting, the measurement range of the (0)4-20mA pressure SPAN sensor is determined according the selected measurement unit (setting 61).
  • Page 18: Formula

    Page 18 With this setting it is possible to calibrate the input value for 20mA as the CALIBRATE HIGH signal from the sensor might not be exact 20.0 mA at maximum signal. This function will measure the real output value at maximum signal. ...
  • Page 19: Analog Output

    Page 19 8 - ANALOG OUTPUT A linear analog (0)4-20mA or 0-10V signal is generated according to the flowrate with a 10 bits resolution. The settings for flowrate (SETUP - 2) influence the analog output directly. The relationship between rate and analog output is set with the following functions: The analog output can be disabled.
  • Page 20: Communication

    Page 20 8 - ANALOG OUTPUT (CONTINUED) This function is used to stabilize the analog output signal. FILTER The output value is updated every 0.1 second. With the help of this digital filter a more stable but less precise reading can be obtained. The filter principal is based on three input values: the filter level (01-99), the last analog output value and the last average value.
  • Page 21: Installation

    Page 21 INSTALLATION 4.1. GENERAL DIRECTIONS  Mounting, electrical installation, start-up and maintenance of this instrument may only be carried out by trained personnel authorized by the operator of the facility. Personnel must read and understand this Operating Manual before carrying out its instructions. ...
  • Page 22: Dimensions- Enclosure

    Page 22 4.3. DIMENSIONS- ENCLOSURE Aluminum enclosures: 75 mm (2.95") 112 mm (4.40") 130 mm (5.12") 12mm 12mm 30mm 30mm 24mm 24mm M20 x 1,5 6 x M12 36mm 36mm 30mm 30mm M16 x 1,5 M16 x 1,5 1/2"NPT M20 x 1,5 0.12"...
  • Page 23 Page 23 GRP enclosures: 75 mm (2.95") 112 mm (4.40") 130 mm (5.12") HK back box: (flat bottom) 75 mm (2.95") 118 mm (4.65”) 25mm 25mm D=20mm D=20mm 12mm 12mm 30mm 30mm 24mm 24mm D=12mm D=16mm D=16mm D=20mm 36mm 36mm 0.12”...
  • Page 24: Installing The Hardware

    Page 24 4.4. INSTALLING THE HARDWARE 4.4.1. INTRODUCTION  Electro static discharge does inflict irreparable damage to electronics! Before installing or opening the unit, the installer has to discharge himself by touching a well-grounded object.  This unit must be installed in accordance with the EMC guidelines (Electro Magnetic Compatibility).
  • Page 25: Voltage Selection Sensor Supply

    Page 25 4.4.2. VOLTAGE SELECTION SENSOR SUPPLY For Intrinsically Safe applications: read chapter 5. Type PB / PC / PX (AP) - battery powered and output loop-powered applications: Terminal 11 provides a limited supply voltage of 3.2 V DC (coil signals 1.2V) for the signal output of the flowmeter.
  • Page 26: Terminal Connectors

    SIGNAL PT100 INPUT - 2 WIRE PT100 INPUT - 3 WIRE Fig. 9 Overview terminal connectors F126-P-EG-IA-TP and most options. REMARKS TERMINAL CONNECTORS: Terminal GND- 01- 02: Power Supply - only available with type PD / PF or PM: erminal...
  • Page 27 Page 27 Terminal 07-08; basic POWER SUPPLY - type PX - output loop powered: Connect an external power supply of 8-30VDC to these terminals or a 4-20mA loop. Do connect the "-" to terminal 7 and the "+" to terminal 8. When power is applied to these terminals, the (optional) internal battery will be disabled / enabled automatically to extend the battery life time.
  • Page 28 Page 28 Type AI: An isolated 4-20mA signal proportional to the flowrate is available with this option. When the output is disabled, a 3.5mA signal will be generated on these terminals. Max. driving capacity 1000 Ohm @ 30VDC. This option can be used with a battery powered unit but the life time of the battery is about 2 -3 years.
  • Page 29 Page 29 Terminal 09-11; Flowmeter input: Three basic types of flowmeter signals can be connected to the unit: pulse, active pulse or sine- wave (coil). The screen of the signal wire must be connected to the common ground terminal 09 (unless earthed at the sensor itself).
  • Page 30 Page 30 Pulse-signal PNP / PNP-LP: The F126-P is suitable for use with flowmeters which have a PNP output signal. 3.2V is offered on terminal 11 which has to be switched by the sensor to terminal 10 (SIGNAL). For a reliable pulse detection, the pulse amplitude has to go above 1.2V.
  • Page 31 Namur SIGNAL 820 Ohm shielding Common ground unit Terminal 12-13; Pressure input (0)4-20mA: The F126-P-EG-IA-TP requires a (0)4-20mA signal for pressure which will be processed 4 times a second with a 14 bits accuracy. The input is not isolated. HF126PEN_EG_IA_TP_v0501_04...
  • Page 32 Page 32 Terminal 20-22; Temperature input TP - PT100: Two types of PT100 elements can be connected to the F126-P-EG-IA-TP: 2 or 3-wire. PT100 INPUT - 2 WIRE PT100 INPUT - 3 WIRE Terminal 26-31: type CB / CH / CI / CT - communication RS232 / RS485 / TTL (option) ...
  • Page 33: Intrinsically Safe Applications

    Please Note  Certificates, safety values and declaration of compliance can be found in the document named: “Fluidwell F1..-..-XI - Documentation for Intrinsic Safety”.  Special conditions for safe use mentioned in both the certificate and the installation instructions must be observed for the connection of power to both input and / or output circuits.
  • Page 34: Terminal Connectors Intrinsically Safe Applications

    Indicated labels on the back cover (below) and on the inside cover (right) show the type labels for intrinsically safe certified units. For details on usage see the separate “Fluidwell F1..-..-XI Documentation for Intrinsic Safety”. Serial number and year of production This information can be looked-up on the display: See setup function (par.
  • Page 35 Page 35 Explanation Intrinsically Safe options: Type AF - Intrinsically Safe floating 4-20mA analog output - Terminal 7-8: A floating 4-20mA signal proportional to the flowrate is available with this option. When the output is disabled, a 3.5mA signal will be generated. Max. driving capacity 1000 Ohm @ 30V DC. Note! It is required to link the minus from the analog output - terminal 7 - with a ground terminal of the unit;...
  • Page 36: Configuration Examples

    Page 36 CONFIGURATION EXAMPLES Configuration example IIB /IIIC F126-P-AP-CT-IA-(PD)-TP-XI HAZARDOUS AREA SAFE AREA TERMINAL CONNECTORS F100-series Modbus communication type CT: TTL I.S. Certified  Isolator TTL to: = max. 30 V e.g. PC RS232 = max. 250 mA RS422 = max. 0.85 W +12V For example: Common ground...
  • Page 37 Page 37 Configuration example IIB/IIIC and IIC - F126-P-AP-IA-(CT)-PD-TP-XI HAZARDOUS AREA SAFE AREA TERMINAL CONNECTORS F100-series Modbus communication type CT: TTL Please note: communciation type CT is allowed in IIC applications. I.S. Certified  Isolator TTL to: = max. 30 V e.g.
  • Page 38: Battery Replacement Instructions

    Batteries for use in safe areas have no Ex label. DO NOT EXCHANGE: Using the wrong type of battery can pose a SERIOUS RISK.  For use in hazardous areas Fluidwell recommends FW-LiBAT batteries (manufactured by Fluidwell bv) only. Battery replacement procedure Depending on the production batch, one of two visualized Intrinsically Safe certified battery types may have been installed in the unit.
  • Page 39: General Directions

    Page 39 Maintenance 6.1. GENERAL DIRECTIONS  Mounting, electrical installation, start-up and maintenance of the instrument may only be carried out by trained personnel authorized by the operator of the facility. Personnel must read and understand this Operating Manual before carrying out its instructions. ...
  • Page 40: Appendix A: Technical Specification

    Page 40 APPENDIX A: TECHNICAL SPECIFICATION GENERAL Display Type High intensity reflective numeric and alphanumeric LCD, UV-resistant. Digits Seven 17mm (0.67") and eleven 8mm (0.31"). Various symbols and measuring units. Refresh rate User definable: 8 times/sec - 30 secs. Option ZB Transflective LCD with green LED backlight.
  • Page 41 Page 41 Sensor excitation Type PB / PC / PX 3.2V DC for pulse signals and 1.2V DC for coil pick-up. Note: This is not a real sensor supply. Only suitable for pulse sensors with a very low power consumption like coils (sine wave) and reed-switches. Type PD 1.2 - 3.2 - 8.2 - 12 and 24V DC - max.
  • Page 42 Page 42 Temperature Type TP 2 or 3 wire PT100. Standard range: -100°C to +200°C (-148°F to 392°F) - accuracy 0.1 °C (0.18°F). Update time four times a second. Note The linearity is internally compensated. Type ZV range: -200°C to +800°C (-328°F to 1832°F) - accuracy 0.5 °C (0.9°F). Type TA (0)4-20mA - with signal calibration feature at any current within the range.
  • Page 43 Page 43 OPERATIONAL Operator functions Displayed functions • compensated total and/or compensated flowrate. • compensated total and compensated accumulated total. • line pressure. • line temperature. • compensated total can be reset to zero by pressing the CLEAR-key twice. Total Digits 7 digits.
  • Page 44: Appendix B: Problem Solving

    Page 44 APPENDIX B: PROBLEM SOLVING In this appendix, several problems are included that can occur when the F126-P-EG is going to be installed or while it is in operation. Analog output does not function properly: Check:  SETUP 81 - is the function enabled? ...
  • Page 45: Appendix C: Communication Variables

    Page 45 APPENDIX C: COMMUNICATION VARIABLES Remarks:  Below, an overview of the F126-P-EG specific variables; other common variables are described in the standard table.  All numbers are decimal numbers, unless otherwise noted.  Following variables of the standard table (var00-var30) are not valid for this product and will be responded with value 1: var00, 03-05, 07,08, 16-22, 24, 26-29.
  • Page 46 Page 46 DESCRIPTION BYTES VALUE REMARKS DISPLAY display function 0=total (40h) 1=flowrate set flowrate monitor 0=operator level (44h) 1=SETUP level POWERMANAGEMENT LCD update time 0=fast (50h) 1=1sec 2=3sec 3=15sec 4=30sec 5=off power-mode battery 1 0=operational (51h) 1=shelf FLOWMETER flowmeter signal 0=npn (60h) 1=npn-lp...
  • Page 47 Page 47 DESCRIPTION BYTES VALUE REMARKS PRESSURE unit 0=mbar (220h) 1=bar 2=psi 3=no unit span 1..9,999,999 (222h) decimals span 0…6 (225h) offset 0.000..9,999.999 unit as var544 (226h) step 0.001 calibration low 0=default (5Ah) (4mA) 1=calibrate 2=cal set calibration high 0=default (5Bh) (20mA) 1=calibrate...
  • Page 48 Page 48 OTHER F126-P-EG VARIABLES FOR COMMUNICATION TOTAL - variable number 566 (236h) – 6 bytes Read total: The value of total read using communication might differ from the value that appears on the display. This is due to the fact that the display can only display up to seven digits ( for example when two decimals are selected for total and total has a value of 123456,78 the display will show 23456,78 while communication will read a “total”...
  • Page 49: Index Of This Manual

    Fig. 7: Grounding aluminum enclosure with type PM 115-230V AC..........24 Fig. 8: Switch setting sensor supply voltage..................25 Fig. 9 Overview terminal connectors F126-P-EG-IA-TP and most options........26 Fig. 10: Overview terminal connectors communication option............32 Fig.
  • Page 50: Notes

    Page 50 NOTES HF126PEN_EG_IA_TP_v0501_04...
  • Page 51 Page 51 LIST OF CONFIGURATION SETTINGS SETTING DEFAULT DATE : DATE : 1 - TOTAL Enter your settings here 11 unit 12 decimals 0000000 13 K-factor 0000001 14 decimals K-factor 2 - FLOWRATE 21 unit 22 time unit /min 23 decimals 0000000 24 K-factor 0000001...
  • Page 52 A - OTHERS A4 password 0000 A5 tagnumber 0000000 Fluidwell bv HF126PEN_EG_IA_TP_v0501_04 PO box 6 Voltaweg 23 Website: www.fluidwell.com 5460 AA Veghel 5466 AZ Veghel Find your nearest representative: www.fluidwell.com/representatives The Netherlands The Netherlands Copyright Fluidwell bv - 2012 - HF110AEN_v0501_03...