SINGLE CHANNEL LOOP DETECTORS
I.
General
Please verify source voltage before applying power. The model designation indicates the input power required, output
configuration, sensitivity boost configuration, and Fail-Safe / Fail-Secure configuration for the detector as follows.
Model B-xx-xx-x
NOTE: Models B-3, B-4 and B-8 are fitted with a rear mounted, 11 pin, and Amphenol style connector. Models
B-1, B-5, and B-35 are fitted with a rear mounted, 10-pin, MS style connector.
The detector is factory configured for either Fail-Safe or Fail-Secure operation (see unit side label). The output state of
each output relay in either Fail-Safe or Fail-Secure mode is listed in the table below.
Relay
A
B
II.
Indicators and Controls
i.
Power / Detect / Fail LEDs
The detector has one green and two red LED indicators that are used to provide an indication of the detector's
power status, output state, and/or loop failure conditions. The table below lists the various indications and their
meanings.
Status
Off
On
Flash
NOTE: If the supply voltage drops below 75% of the nominal level, the PWR LED will turn off, providing a
visual indication of low supply voltage. Model B detectors will operate with supply voltage as low as 70% of
nominal supply voltage.
ii.
Frequency LEDs:
The four red LED indicators provide an indication of the current detector operating frequency.
iii.
Front Panel Pushbutton Switches:
Two momentary contact pushbutton switches are used to control the following.
RESET - Push the front panel mounted pushbutton labeled RESET to reset the detector.
Model B Series Rev. 03-14-2019
MODEL B SERIES
INSTALLATION AND OPERATING INSTRUCTIONS
Blank = Fail-Safe, S = Fail-Secure
Blank = Internal DIP switches set to True Presence
DP = Internal DIP switches set to True Presence
SB = Internal DIP switch set to enable Sensitivity Boost
3 or 1 = 120 VAC
4 or 5 = 12 VDC / 24 VDC / 24 VAC
8 or 35 = 240 VAC
Fail-Safe
Power Failure
Call
No Call
PWR (Power) LED
No power or low power
Normal power to detector
N/A
Loop Failure
Call
No Call
DET (Detect) LED
Output(s) Off
Output(s) On
4 Hz (50% duty cycle)
Two second timing
delay activated
1
Eberle Design, Inc.
3510 E Atlanta Avenue
Phoenix, AZ 85040,
Tel: (480) 968-6407
Fax: (602) 437-1996
www.renoae.com
TM
/ Pulse-on-Entry
TM
/ True Presence
Fail-Secure
Power Failure
No Call
No Call
FAIL LED
Loop OK
Open Loop
1 Hz (50% duty cycle)
Shorted Loop
1 Hz (5% duty cycle)
Waiting for release of FREQ push-
button to enter diagnostics mode
(See Failed Loop Diagnostics)
TM
Loop Failure
No Call
No Call
P/N 551-0202-02