Summary of Contents for Schweitzer Engineering Laboratories SEL-2100
Page 1
SEL-2100 PROTECTION LOGIC PROCESSOR INSTRUCTION MANUAL SCHWEITZER ENGINEERING LABORATORIES 2350 NE HOPKINS COURT PULLMAN, WA USA 99163-5603 TEL: (509) 332-1890 FAX: (509) 332-7990...
Page 2
All brand or product names appearing in this document are the trademark or registered trademark of their respective holders. Schweitzer Engineering Laboratories, SEL , Connectorized, Job Done, SEL-PROFILE, and are registered trademarks of Schweitzer Engineering Laboratories. OGIC The English language manual is the only approved SEL manual.
− Updated Firmware information. Appendix E: − Made changes to A5CO block to include fast message (unsolicited SER messaging). − Added A5CE Fast Operate Configuration Message subsection. − Added SNS Message subsection. Date Code 20011017 Manual Change Information SEL-2100 Instruction Manual...
Section 2: − Updated Figure 2.1 and Figure 2.4. Section 3: − Updated Figure 3.9. Section 4: − Updated cable information in SEL-2100 to SEL-351 or SEL-311C. − Updated password information. Section 9: − Added battery Caution statement. Appendix E: −...
Page 5
− Corrected information in the DNP V3.00 Subset Definitions document. Appendix H: − Corrected cycle information in the SEL Control Equation Variable OGIC Timers section (Settings Sheet 1 and 2). 20000120 Reissued Entire Manual. 991221 New Manual Release. Date Code 20011017 Manual Change Information SEL-2100 Instruction Manual...
Page 7
SEL-2100 INSTRUCTION MANUAL TABLE OF CONTENTS SECTION 1: INTRODUCTION SECTION 2: INSTALLATION SECTION 3: APPLICATIONS EXAMPLES SECTION 4: SERIAL PORT COMMUNICATIONS AND COMMANDS ® SECTION 5: CONTROL EQUATIONS AND THE RELAY WORD OGIC SECTION 6: INPUTS, OUTPUTS, TIMERS, AND OTHER CONTROL LOGIC...
SEL-2100 Relay Relay DWG: M2100_033 IRRORED Line Links Relays )LJXUH %XV DQG %UHDNHU )DLOXUH 3URWHFWLRQ SEL-2100 Transmits PT to a Relay if it Receives PT from Both of the Other Two Relays Relay Relay SEL-2100 Relay IRRORED DWG: M2100_034...
Page 12
'LJLWDO PLFURZDYH vÁ 0XOWLSOH[HG GLJLWDO UDGLR vÁ 6SUHDG VSHFWUXP UDGLR vÁ DV ZHOO DV PDQ\ RWKHU W\SHV RI FKDQQHOV 6HH 6HFWLRQ 0 &RPPXQLFDWLRQV IRU PRUH LQIRUPDWLRQ DERXW 0 ,5525(' ,5525(' FRPPXQLFDWLRQV Introduction Date Code 20010305 SEL-2100 Instruction Manual...
Page 50
Begins to and Trips Time-Qualify (3.0 Cycles) Trip Decision (1.5 Cycles) Time Line For SEL-2100 SEL-2100 Receives SEL-2100 Qualifies Trip Message From Decision for 12 ms Relay and Begins Transmission (1.25 Cycles) of Trip Commands (2.25 Cycles) 9XB)ÃÃH! f!' )LJXUH /RRSHG )HHGHU %XV 3URWHFWLRQ 7LPH /LQH...
Page 128
Port n to Port n IRRORED Relay OGIC Integrity Word Processor Checks R1P n - T1P n - Encoder R8P n T8P n Default Receive Values DWG: M2100_038 )LJXUH 0 3URFHVVLQJ ,5525(' Communications Date Code 20010305 IRRORED SEL-2100 Instruction Manual...
APPENDIX A: FIRMWARE VERSIONS To find the firmware revision number in the SEL-2100 Protection Logic Processor, view the status report using the serial port STATUS command. The status report displays the Firmware Identification (FID) label: FID=SEL-2100-Rxxx-Vx-Z000000-Dxxxxxxxx The firmware revision number is after the “R” and the release date is after the “D”.
If you do not wish to perform the installation yourself, SEL can assist you. Simply return the SEL-2100 and ICs to SEL. We will install the new ICs and return the unit to you within a few days. If you perform the upgrade, please follow these step-by-step instructions.
Page 148
SEL-2100. Energizing the SEL-2100 with an IC reversed irrecoverably damages the IC. If you mistakenly reenergize the relay with an IC reversed, do not place the SEL-2100 in service using that IC, even if you correct the orientation.
Page 149
Figure B.1: SEL-2100 Main Board Date Code 20010529 Firmware Upgrade Instructions SEL-2100 Instruction Manual...
DCD indication. This allows RTS to be looped back to CTS in cases where the external transceiver does not support DCD. When the SEL-2100 transmits a DNP message, it delays transmitting after asserting RTS by at least the time in the PREDLY setting. After transmitting the last byte of the message, the SEL-2100 delays for at least PSTDLY milliseconds before deasserting RTS.
Page 152
When the SEL-2100 decides to transmit on the DNP link, it has to wait if the physical connection is in use. The SEL-2100 monitors physical connections by using CTS input (treated as a Data Carrier Detect) and monitoring character receipt.
Page 153
Object Group Request Function Codes Response Function Codes Object Variation Request Qualifiers Response Qualifiers Object Name (optional) Vendor Name: Schweitzer Engineering Laboratories, Inc. Device Name: SEL-2100 Highest DNP Level Supported: Device Function: ¨ Master þ Slave For Requests Level 2...
Page 154
þ Default object þ 16 Bits ❏ Default variation ❏ 32 Bits ❏ Point-by-point list attached ❏ Other Value ❏ Point-by-point list attached ❏ Yes þ No Sends Multi-Fragment Responses: Distributed Network Protocol 3.00 Date Code 20010529 SEL-2100 Instruction Manual...
Page 155
When an item in the device profile is configurable, it is controlled by SEL-2100 settings. BJECT ABLE The following object table shows the supported object, function, and qualifier code combinations. Table C.2: SEL-2100 DNP Object Table REQUEST RESPONSE OBJECT (supported)
Page 156
32-Bit Delta Counter Change Event with Time 16-Bit Delta Counter Change Event with Time Frozen Counter Event–All Variations 32-Bit Frozen Counter Event without Time 16-Bit Frozen Counter Event without Time Distributed Network Protocol 3.00 Date Code 20010529 SEL-2100 Instruction Manual...
Page 157
16-Bit Analog Change Event without Time 32-Bit Analog Change Event with Time 16-Bit Analog Change Event with Time Frozen Analog Event–All Variations 32-Bit Frozen Analog Event without Time 16-Bit Frozen Analog Event without Time Date Code 20010529 Distributed Network Protocol 3.00 SEL-2100 Instruction Manual...
Page 158
Class 0 Data Class 1 Data 1,20,21 6,7,8 Class 2 Data 1,20,21 6,7,8 Class 3 Data 1,20,21 6,7,8 File Identifier Internal Indications index=7 Storage Object Device Profile Private Registration Object Distributed Network Protocol 3.00 Date Code 20010529 SEL-2100 Instruction Manual...
Page 159
Extended Floating Point Small Packed Binary-Coded Decimal Medium Packed Binary-Coded Decimal Large Packed Binary-Coded Decimal No object 13,14,23 Table C.3: SEL-2100 Data Map Object Type Index Description 01,02 Processor Word, where index is divided by 8 to get the row, –...
Page 161
The binary input points (objects 1and 2) may be remapped via the DNP command. The map is composed of a list of indices that correspond to those given by the SEL-2100’s DNP data map. The order they occur in the list determines the index that the corresponding value is reported as to the DNP master.
Page 162
35 1 56 57 58 59 60 61 62 63 64 65 66 67 100 101 102 \<Enter> 103<Enter> Save Changes (Y/N)? Y <ENTER> ==> If a single blank line is entered as the first line, remapping is disabled (i.e. the SEL-2100 uses the default map). ==>DNP BI <ENTER> Enter the new DNP Binary Input map <Enter>...
Page 163
PUNSOL = DNP Address of Report (0–65534) REPADR = Number of Events to Transmit On (1–200) NUMEVE = Seconds Until Oldest Event to Tx On (0.0–60.0 seconds) AGEEVE = Date Code 20010529 Distributed Network Protocol 3.00 C-13 SEL-2100 Instruction Manual...
The SEL-2100 provides compressed ASCII versions of some of the ASCII commands. The compressed ASCII commands allow an external device to obtain data from the SEL-2100 in a format which directly imports into spreadsheet or database programs, and which can be validated with a checksum.
Page 166
If a compressed ASCII request is made for data that are not available, (e.g., invalid event request), the SEL-2100 responds with the following message: <STX>"No Data Available","0668"<CR><ETX> CASCII C —SEL-2100 OMMAND Display the SEL-2100 compressed ASCII configuration message by sending: CAS <CR> <STX> "CAS",1,"01A4"<CR> "CST",1,"01B7"<CR> "1H","FID","022C"<CR>...
ASCII names of SER settings Processing The SEL-2100 receives and transmits Fast Meter messages interleaved with ASCII messages. Upon power up and settings change, the SEL-2100 sets the Settings Change bit in the Fast Meter Status byte. Date Code 20010529...
Page 170
A5C0 Fast Meter Definition Message In response to the A5C0 request, the SEL-2100 sends the definition block as described below. A5C0 Command Length Support four protocols Support one Fast Meter message Support one status flag command A5C1 Fast Meter configuration command...
Page 171
Checksum calculated by addition of all the above bytes. 82 bytes Total message length. A5B9 Fast Meter Status Acknowledge Message In response to the A5B9 request, the SEL-2100 clears the Fast Meter Status byte. The status byte includes: Usage Not used...
Page 172
Operate code, set remote bit RB21 Operate code, pulse remote bit RB21 Operate code, clear remote bit RB22 Operate code, set remote bit RB22 Operate code, pulse remote bit RB22 Operate code, clear remote bit RB23 Fast Meter Protocol Date Code 20010529 SEL-2100 Instruction Manual...
Page 173
00–1F clear remote bit RB1–RB32 20–3F set remote bit RB1–RB32 40–5F pulse remote bit for RB1–RB32 for one processing interval 1-byte Operate validation: 4 • Operate code + 1 checksum 1-byte checksum of preceding bytes Date Code 20010529 Fast Meter Protocol SEL-2100 Instruction Manual...
Page 174
Remote bit set and clear operations are latched by the relay. Remote bit pulse operations assert the remote bit for one processing interval. BNA Message In response to the BNA command, the SEL-2100 sends the names of the status bits as described below. <STX>"*","*","*","STSET","*","*","*","*","yyyy"<CR>...
Page 176
If there are more than eight settings in SER, the SNS message will have several rows. Each row will have eight strings, followed by the checksum and carriage return. The last row may have less than eight strings. SNS message for the SEL-2100 is : <STX>"xxxx","xxxx","xxxx","xxxx","xxxx","xxxx","xxxx","xxxx","yyyy"<CR><LF> "xxxx","xxxx","xxxx","xxxx","xxxx","xxxx","xxxx","xxxx","yyyy"<CR><LF>...
6. Enter the sequence CTRL-X QUIT <CR> before entering the prefix character if all relays in the multidrop network do not have the same prefix setting. Note: You can use the front-panel SET pushbutton to change the port settings to return to SEL protocol. Date Code 20010529 SEL Distributed Port Switch Protocol SEL-2100 Instruction Manual...
Burden: < 25 W Jumper Selectable +5 Vdc out on Pin 1, Ports 1–16: up to 0.5 A total. Operating Temperature Range: -40° to +85°C (-40° to +185°F) 7 lb, 12 oz (3.50 kg) Relay Weight: Date Code 20010529 Specifications SEL-2100 Instruction Manual...
Page 180
A/m for 1 minute. IEC 61000-4-9 First Edition–1993 [EN 61000-4-9 First Edition– 1993] Electromagnetic compatibility (EMC), Part 4: Testing and measurement techniques, Section 9: Pulse magnetic field immunity test. Severity Level: 1000 A/m. Specifications Date Code 20010529 SEL-2100 Instruction Manual...
Page 181
1995] Electrical relays, Part 21: Vibration, shock, bump, and seismic tests on measuring relays and protective equipment, Section 3: Method A seismic tests (not tested below 5 Hz). Severity Level: Class 2 (Quake Response). Date Code 20010529 Specifications SEL-2100 Instruction Manual...
Page 182
Pin 6 Chassis ground reference Connectors: All 16 rear DB-9 port connectors Outputs are generated from IRIG-B input (when present) Certifications: ISO: Protection Logic Processor is designed and manufactured to an ISO 9001 certified quality program. Specifications Date Code 20010529 SEL-2100 Instruction Manual...
Page 183
SV15PU = SV15 Dropout Time (0–32000 ms in 1-ms steps) SV15DO = SV16 Pickup Time (0–32000 ms in 1-ms steps) SV16PU = SV16 Dropout Time (0–32000 ms in 1-ms steps) SV16DO = Date Code 20010529 Setting Sheets SEL-2100 Instruction Manual...
SV31PU = SV31 Dropout Time (0–32000 ms in 1-ms steps) SV31DO = SV32 Pickup Time (0–32000 ms in 1-ms steps) SV32PU = SV32 Dropout Time (0–32000 ms in 1-ms steps) SV32DO = Settings Sheets Date Code 20010529 SEL-2100 Instruction Manual...
Page 185
SET15 = Reset Latch Bit LT15 RST15 = Set Latch Bit LT16 SET16 = Reset Latch Bit LT16 RST16 = Set Latch Bit LT17 SET17 = Reset Latch Bit LT17 RST17 = Date Code 20010529 Settings Sheets SEL-2100 Instruction Manual...
Page 188
Transmit Bit 2 Port 1 T2P1 = Transmit Bit 3 Port 1 T3P1 = Transmit Bit 4 Port 1 T4P1 = Transmit Bit 5 Port 1 T5P1 = Transmit Bit 6 Port 1 T6P1 = Settings Sheets Date Code 20010529 SEL-2100 Instruction Manual...
Page 189
Transmit Bit 1 Port 6 T1P6 = Transmit Bit 2 Port 6 T2P6 = Transmit Bit 3 Port 6 T3P6 = Transmit Bit 4 Port 6 T4P6 = Transmit Bit 5 Port 6 T5P6 = Date Code 20010529 Settings Sheets SEL-2100 Instruction Manual...
Page 190
Transmit Bit 8 Port 10 T8P10 = Transmit Bit 1 Port 11 T1P11 = Transmit Bit 2 Port 11 T2P11 = Transmit Bit 3 Port 11 T3P11 = Transmit Bit 4 Port 11 T4P11 = Settings Sheets Date Code 20010529 SEL-2100 Instruction Manual...
Page 191
Transmit Bit 4 Port 15 T4P15 = Transmit Bit 5 Port 15 T5P15 = Transmit Bit 6 Port 15 T6P15 = Transmit Bit 7 Port 15 T7P15 = Transmit Bit 8 Port 15 T8P15 = Date Code 20010529 Settings Sheets SEL-2100 Instruction Manual...
Page 192
Input IN114 debounce time (AC, 0–15 ms in 1 ms steps) IN114D = Input IN115 debounce time (AC, 0–15 ms in 1 ms steps) IN115D = Input IN116 debounce time (AC, 0–15 ms in 1 ms steps) IN116D = H-10 Settings Sheets Date Code 20010529 SEL-2100 Instruction Manual...
Page 193
SER1 = SER Trigger List 2 SER2 = SER Trigger List 3 SER3 = SER Trigger List 4 SER4 = SER Trigger List 5 SER5 = SER Trigger List 6 SER6 = Date Code 20010529 Settings Sheets H-11 SEL-2100 Instruction Manual...
Page 194
Send Auto Messages to Port (Y, N) AUTO = Enable Hardware Handshaking (Y, N) RTSCTS = Fast Operate Enable (Y, N) FASTOP = * Port F baud rate (300, 1200, 2400, 4800, 9600) H-12 Settings Sheets Date Code 20010529 SEL-2100 Instruction Manual...
Page 195
Enable Unsolicited Reporting at Power-up (Y, N) PUNSOL = DNP Address to Report (0–65534) REPADR = Number of Events to Transmit On (1–200) NUMEVE = Seconds Until Oldest Event to Tx On (0.0–60.0) AGEEVE = Date Code 20010529 Settings Sheets H-13 SEL-2100 Instruction Manual...
Transfer” message to enable the SEL-2100 to transmit unsolicited binary SER messages. 2. When SER records are triggered in the SEL-2100, it responds with an unsolicited binary SER message. If this message has a valid checksum, it must be acknowledged by sending an acknowledge message with the same response number as contained in the original message.
Page 198
SEL-2100 transmits an acknowledge message with the same response number received in the enable message. The “nn” field is used to set the maximum number of SER records per message. The SEL-2100 checks for SER records approximately every 500 ms. If there are new records available, the SEL-2100 immediately creates a new unsolicited SER message and transmits it.
Page 199
The function 18 is used for the transmission of unsolicited Sequential Events Recorder (SER) data from the SEL-2100. This function code is also passed as data in the “Enable Unsolicited Data Transfer” and the “Disable Unsolicited Data Transfer” messages to indicate which type of unsolicited data should be enabled or disabled.
Page 200
Packed four-byte element status for up to 32 elements (LSB for the 1st element) cccc Two-byte CRC-16 checkcode for message If the SEL-2100 determines that SER records have been lost, it sends a message with the following format: Data Description...
Page 201
A5 46 10 00 00 00 00 00 01 02 C0 XX 18 00 cc cc (XX = 0, 1, 2, 3) 4. Successful acknowledge from the SEL-2100 for the “Disable Unsolicited Data Transfer” message: A5 46 0E 00 00 00 00 00 00 82 00 XX cc cc (XX is as same as the response number in the “Disable Unsolicited Data Transfer”...
Page 202
When the SEL-2100 sends an SER message packet, it will put a sequential number (0, 1, 2, 3, 0, 1, . . .) into the response number. If the SEL-2100 does not receive an acknowledge from the master before approximately 500 ms, the SEL-2100 will resend the same message packet with the same response number until it receives an acknowledge message with that response number.
After installation, the Quick Tour will show how to create a circuit breaker (CB) simulator. The CB simulator is useful for testing and evaluation. Note: Like all SEL relay products, the SEL-2100 can also be set and operated by a simple ASCII terminal.
Page 204
You can start the following ways: ERATOR 1. Double-click the icon if you have a desktop shortcut. ERATOR 2. Choose “Programs | SEL Applications” and select the icon to start the ERATOR program. SEL-5030 Date Code 20011017 ERATOR SEL-2100 Instruction Manual...
Need help?