Initializing DeviceNet (CompoBus/D) Memory Switches

5-3

Initializing DeviceNet (CompoBus/D) Memory Switches

Reference 1. Memory initialization cannot be performed when screen memory is write-
In addition to the standard OMRON memory initialization functions, the system
menu for the DeviceNet Interface Unit has a function that initializes Compo-
Bus/D setting switches.
Refer to the PT's User's Manual for details on the other memory initialization op-
erations.
protected with the system installer mode's system settings.
2. Either PT memory switches or CompoBus/D setting switches can be se-
lected from the memory switch initialization menu. Select PT memory
switches to initialize settings other than those for the DeviceNet Interface
Unit.
3. When the CompoBus/D setting switches have been initialized, the Device-
Net Interface Unit will use 32 input words and 32 output words. The number
of words used by all of the Slaves (including the DeviceNet Interface Unit)
must not exceed the maximum number of words available in the Master. In
particular when the Master is a C200HS, a DeviceNet Interface Unit set to its
default settings will use all of the Master's available words.
If the number of words used by all of the Slaves exceeds the maximum num-
ber of words available in the Master, either reduce the number of Slaves or
reduce the number of words used by the DeviceNet Interface Unit by chang-
ing the settings of the CompoBus/D setting switches.
The memory switches for the DeviceNet Interface Unit that have been set in the
PT will all be returned to their factory-default settings by the CompoBus/D set-
ting switch initialization function.
Use the following operation in the system menu to initialize all of the memory
switch settings.
Ver 2.10
Press Maintenance Mode.
Press Memory Init..
Section
5-3
57