EL160, EL360 & EL500 Eco
– A new generation of electric boilers with touchscreen and
a new design
Installation and Operating Instructions
The Professional's Choice Since 1935
MADE IN
SWEDEN
EN
04/06/2018

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EL 360 Eco and is the answer not in the manual?

Questions and answers

Summary of Contents for Osby Parca EL 360 Eco

  • Page 1 The Professional’s Choice Since 1935 Installation and Operating Instructions IMPORTANT READ CAREFULLY BEFORE USE 04/06/2018 SAVE FOR FUTURE REFERENCE Osby Parca Tel. no.: +46 (0)479 177 00 | sales@osbyparca.se | www.osbyparca.se | Box 93, 283 22 Osby, SWEDEN...
  • Page 3: Table Of Contents

    9.17 Current limitation ___________________________ 45 4.2.3 Dimensions & Connections EL 360 & 500 Eco S 19 9.18 Current sensors ____________________________ 45 4.2.4 Power steps EL 360 Eco ___________________ 20 9.19 Alarm messages ___________________________ 46 4.2.5 Power steps EL 500 Eco ___________________ 22 9.20 External power _____________________________ 46...
  • Page 4 EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 5 Congratulations on your new electric boiler You have just purchased an Osby Parca electric boiler which we hope you will be completely satisfied with. On the following pages, you can read about how to take care of your electric boiler.
  • Page 6: Important To Keep In Mind

    It is of great importance that the product's refrigerant, compressor oil Enertech's obligation and electrical/electronic equipment are properly disposed of. pertaining to the applicable warranty terms and conditions is not binding. Subject to any errors in writing and subject to change. EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 7: Installation

    Note: In the std boiler, the pressure switch connection is plugged. Nothing must be mounted there. Safety equipment must be mounted externally. The electric boiler is CE-approved as a unit and must not be altered. EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 8: Overheating Protection & Emergency Operation

    When emergency operation is required, the emergency operation thermostat can be set to the desired primary flow temperature. Also refer to the boiler's “EMERGENCY OPERATION THERMOSTAT” wiring diagram. The emergency operation function is only available with the 69-498 kW versions. EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 9 EL160 Eco S electric boiler with built-in safety system. The circuit breaker will be at the yellow mark during an interruption. To reset: Down to OFF Up to ON + Reset on the touchscreen. EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 10: Servicing

    For safe operation and functionality, a function test should be carried out at least once per year. Turn the plastic cap (pressure relief valve) until the valve opens. The seal wire is usually of the correct length and does not need to be cut. EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 11 AF38 = 2.5 Nm 2. 8 Nm AF26 = 2.5 Nm AF12 = 1.5 Nm AF09 = 1.5 Nm 7. 2,8 Nm 6. 2,8 Nm 3. 13.5 Nm 4. 4.4 Nm 5. 2.7 Nm EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 12 3. 7 Nm (4x3) 1. Press fuse 2. Remove cover 8. Fuses = 4 Nm 6-7. Contactores: 4-5. Contactor AF52 = 4 Nm AF26 (400V) = 2,5 Nm AF38 (230V) = 2,5 Nm EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 13 Instructions for re-tightening Osby Parca EL 500 Eco Photo re-tightening EL 500 Eco EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 14: Technical Data

    4.0 bar Testing pressure 5.7 bar Design temperature 110 °C Maximum operating temperature 100 °C Boiler water volume 110 litres Protection class IP21 4.1.2 Pressure drop / Water resistance EL 160 Eco EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 15: Dimensions & Connections El 160 Eco S

    Pipe connections do not have the same loca- rear top cover. The distance between the boiler top and the tion as previous Parca EL 350/500. ceiling should not be less than 900 mm. EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 16: Power Steps El 160 Eco

    400 V 3-phase 7700130-01/31 CURRENT Step 100% El 160 Eco 93 kW 400 V 3-phase 7700130-02/32 CURRENT Step 100% El 160 Eco 114 kW 400 V 3-phase 7700130-03/33 CURRENT Step 100% EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 17 El 160 Eco 135 kW 400 V 3-phase 7700130-04/34 CURRENT Step 100% El 160 Eco 156 kW 400 V 3-phase 7700130-05/35 CURRENT Step 100% EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 18: Technical Data El 360 & El 500 Eco

    8,6 bar Design temperature 110 °C Maximum operating temperature 100 °C Boiler water volume 372 litres Protection class IP21 4.2.2 Pressure drop/Water resistance EL360 & 500 Eco Pressure drop kPa Flow EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 19: Dimensions & Connections El 360 & 500 Eco S

    Separate power supply 230 V 1 ~ required ceiling should not be less than 900 mm. for operating voltage. Pipe connections do not have the same loca- tion as previous Parca EL 350/500. EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 20: Power Steps El 360 Eco

    4.2.4 Power steps EL 360 Eco El 360 Eco 198 kW 400 V 3-phase 7700140-01/31 CURRENT Step 100% El 360 Eco 240 kW 400 V 3-phase 7700140-02/32 CURRENT K4+K5 K6+K7 Step 100% EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 21 Step 100% El 360 Eco 315 kW 400 V 3-phase 7700140-04/34 CURRENT K5+K6 K7+K8 Step 100% El 360 Eco 357 kW 400 V 3-phase 7700140-05/35 CURRENT K4+K5 K6+K7 K8+K9 Step 100% EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 22: Power Steps El 500 Eco

    El 500 Eco 420 kW 400 V 3-phase 7700150-01/31 CURRENT K3+K4 K5+K6 K7+K8 K9+K10 Step 100% El 500 Eco 498 kW 400 V 3-phase 7700150-02/32 CURRENT K3+K4 K5+K6 K7+K8 K9+K10 K11+K12 Step 100% EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 23: Example Of Power Limitation

    4.2.6 Example of power limitation EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 24: Built-In Safety System

    Min. pressure switch DN 15 Max. thermostat 315 - 498 kW Safety valve ¹ DN 25/32 6 bar Max. pressure switch ² DN 15 Min. pressure switch DN 15 Max. thermostat EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 25: Design

    Manually reset TZ+ by pressing in the centre button behind the protective cover. TZ+ reset must be carried out in order to reset the power breaker and to reset the alarm in the Alarm menu. EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 26: Accessories

    3 current sensors for secondary measurement, Max. 5A. Excl. current transformer 3364-3065 Cable flange FL21 1x16-300 mm² 3364-3066 Cable flange FL 21 2x16-300 mm² 6000-0502 Pipe system EL360 accessory 700 kW 6000-0501 Pipe system EL500 accessory 1 MW EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 27: Control System

    Home screen and main menu Factory-set values Step Time 30 sec Max. temp 100 °C Min. temp 20 °C Set point 80 °C Delta T 4 °C Lang. EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 28: Menu Overview

    8. Menu overview Home screen Alarm menu Alarm Missing Missing Missing Operating time, energy calculator and highest boiler temperature menu Advanced settings menu EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 29 Advanced settings menu Time, date and language menu Settings menu Define system menu Quick start menu EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 30 Setting type menu BMS communication menu EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 31 Service menu EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 32 Alarm menu Alarm Missing Missing Missing Alarm description menu Operating history menu Graph and chart menu EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 33 Define system menu EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 34: Detailed Menu Descriptions

    The heating system's structure can be set/ Here, the remaining time for delays can be changed here. viewed, and the function can be overridden. Home Press the Home button to return to the home screen. EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 35: Main Menu

    The alarm can be reset If the fault cannot be reset, you will be advised to contact Support. This may happen if e.g. the relay board has broken. The alarm cannot be reset EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 36: Operational Information

    Define System is used to define how the boiler is to be controlled, to specify limit values and communication. Service is used for troubleshooting, diagnostics, history, program updates and to enter the reset PIN code. EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 37: Settings

    Language is selected by pressing the lags. To set the time, press OK and then use + and - to go up or down. The date is set in the same way. EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 38: Deine System

    Reset max. temperature (PIN code) • Reset operating time calculator (PIN code) • Reset energy calculator (PIN code) • History (PIN code) • Service timer (PIN code) Also see chapter 3, Servicing. EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 39: Write Log To Usb

    Phase current L1 • Phase current L2 • Phase current L3 • Internal raw voltage • System temp sensor • Temp sensor heat exchanger out • Temp sensor heat exchanger in EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 40: Update Sw From Usb

    PIN code required to access the menu. 9.10.7 Service timer Shows time remaining until the next service. The interval length between services is set here. This function can be deactivated after the warranty has expired. EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 41: Bms Building Management Automation

    System temp sensor 0.1° Optional Temp sensor from heat exchanger 0.1° Optional Temp sensor to heat exchanger 0.1° Optional Active BMS alarms low value Bit encoded Active BMS alarms high value Bit encoded EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 42: Outdoor Compensation - Utk

    Once an existing sensor has been defined, the outdoor temperature will be displayed in the main menu. The heating curve defines the starting value for the boiler temperature. The outdoor temperature generates regulation of the boiler temperature. EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 43: Heating Curve Ascension/Inclination

    This setting defines the number of degrees by which the boiler temperature is reduced in the heating system when Input Ep06-07 (terminal block X2:35-36) is closed. Adjustment values are -15 °C… +15°C. EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 44: Stage Regulator

    The temperature is within the deadband The stage regulator does nothing. The temperature is lower than the deadband The output stage is connected during the step depending on the temperature's tendency. EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 45: Current Overload

    For connection to the boiler, please refer to the actual model's wiring diagram. Current sensors are available from Osby Parca as boiler accessories. System-specific current transformer These current sensors can be ordered from Osby Parca. Art. no. 1118404-01 EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 46: Alarm Messages

    (terminal block line X1:15-16), the boiler quickly downshifts and enters OFF mode. When the circuit is closed again, the boiler first enters STANDBY mode and then, once the step duration permits, ON mode. EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 47: Sensor Resistors

    1746 2010 2320 2690 3130 3650 4280 5045 5960 7080 8450 10130 12200 1115 14770 1443 18000 1883 22000 2478 27100 3289 33540 41800 52400 66200 84750 108000 139000 181000 238000 EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 48: Spare Parts Eco Series

    Max. thermostat (Safety thermostat, TZ+) 70-495 kW 1211754-01 Max. high pressure switch (PZ+) 70-495 kW 3352-0350 Min. high pressure switch (PZ-) Also refer to the associated “SPARE PARTS LIST” wiring diagram for the actual boiler. EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 49: Ce Certificate

    12. CE certificate EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 50 EN 61000-4-3 EN 61000-4-4 EN 61000-4-5 EN 61000-4-6 EN 61000-4-11 Osby 2018-01-05 ……………………………………… …………………………… Ort och datum / Place and date (Namnteckning / Signature) Dennis Eliasson Enertech AB Osby Parca Div. EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 51 EL 160 Eco EL 360 Eco EL 500 Eco...
  • Page 52: Appendices

    • Pressure Switch function description (only for boilers with built-in safety systems) Subject to errors or updates made ater this edition. Enertech AB, Osby Parca div. Tel. no. +46 (0)479 177 00 | sales@osbyparca.se www.osbyparca.se Box 93 | SE-283 22 Osby | SWEDEN...