Daikin 4MXL36TVJU Installation Manual page 14

R410a split series
Hide thumbs Also See for 4MXL36TVJU:
Table of Contents

Advertisement

Wiring
[Wiring procedure]
1) Strip the insulation from the wire (3/4 inch (20mm)).
2) Connect the inter-unit wires between the indoor and
outdoor units so that the terminal numbers match.
Tighten the terminal screws securely. It is recommended
that a slot-head screwdriver be used to tighten the screws.
3) Be sure to match the symbols for wiring and piping.
4) Pull the wire lightly to make sure that it does not
disconnect.
5) After completing the work, reattach the shield cover and
right side plate to their original positions.
• Attach so that the shield cover hooks (2 locations) are
securely engaged.
Shape the wires so that there is
no lifting of the shield cover or
other structural parts.
Use the specified wires and
connect them securely.
CAUTION
Precautions to be taken for power supply wiring
• When using stranded wires, make sure to use the round crimp-style
terminal for connection to the power supply terminal block.
Flat washer
Screw
• When connecting the inter-unit wires to the terminal block using a single core wire, be sure to curl the end of the lead.
I mproper work may cause heat and fi re.
Ground
This air conditioner must be grounded. For grounding, follow all local, and state electrical codes.
13
For Room E
For Room C
Ground wires
A
Round
crimp-style
terminal
Good
Wrong
Stripping wire at terminal block
Outdoor unit
Room
Room
Room
E
C
A
Room
Room
D
B
To room E
To room D
To room C
To room B
Recommend using AWG14, stranded and insulated wire for connections
between indoor and outdoor units.
Local code always supersedes recommendation.
Terminal block
For Room D
For Room A
Round crimp-style
terminal
Screw
Round crimp-
style terminal
Flat washer
Good
Arrow view A
Strip wire end
to this point.
Good
Note: Take care to ensure that all wiring
power
between indoor unit and outdoor unit has a
supply
consistent connection. Any splices can cause
communication errors.
: The Room A and Room B terminal
blocks, as well as the Room C and Room D
terminal blocks, are actually integrated.
Follow local codes for wiring and
safety devices between outdoor
unit and power source.
Indoor unit
Room A
For Room B
For power supply
Ground wires
Screw
Flat washer
Round crimp-
style terminal
Wrong
Excessive strip length
may cause electric shock
or current leakage.
Wrong
60Hz
208/230V
Stranded
wire
English