LG Multi V ARNU283M3A4 Svc Manual page 4

Hide thumbs Also See for Multi V ARNU283M3A4:
Table of Contents

Advertisement

Type
Model
Cooling Capacity
Heating Capacity
Nominal
Power Input
Rated
Casing
Dimensions
Body
(WxHxD)
Rows x Columns x FPI
Coil
Face Area
Type
Motor Output x Number
Running Current
Air Flow Rate(H / M / L)
(High Mode-Factory Set)
External static pressure
Fan
Air Flow Rate(H / M / L)
(Standard mode)
External static Pressure
Drive
Motor type
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Safety Device
Liquid Side
Pipe Connections
Gas Side
Drain Pipe(Internal Dia.)
Net Weight
Body
Sound Pressure Levels (H / M / L)
Sound Power Levels (H / M / L)
Power Supply
Refrigerant Control
Transmission Cable (AWG# -C)
Notes:-
1. Capacities are based on the following conditions:
Cooling
• Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB
• Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB
• Interconnecting Piping Length 7.5m(24.6ft)
• Level Difference of Zero
Heating
• Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB
• Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB
• Interconnecting Piping Length 7.5m(24.6ft)
• Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. To be added for more available Models
5. EEV : Electronic Expansion Valve
6. Noise Level is Standard Mode
(for actual High Mode(factory set) condition, Noise Level may exceed the standard level by 1.5dBA)
Unit
ARNU283M2A4
kW
8.2
kcal/h
7 100
Btu/h
28 000
kW
9.2
kcal/h
8 000
Btu/h
31 500
W
123
W
430
Galvanized Steel Plate
mm
1 250 × 270 × 700
inch
49-7/32 x 10-5/8 x 27-9/16
3 x 13 x 18
m
2
(ft
2
)
0.27(2.91)
Sirocco Fan
W
350 x 1
A
2.3
CMM
28.0 / 24.0 / 21.0
CFM
989 /848 / 742
mmAq(Pa)
6(59)
CMM
28.0 / 24.0 / 21.0
CFM
989 /848 / 742
mmAq(Pa)
5(49)
Direct
BLDC
Microprocessor, Thermostat
for cooling and heating
Foamed polystrene
-
Fuse
mm(inch)
Ø9.52(3/8)
mm(inch)
Ø15.88(5/8)
mm(inch)
25(1)
kg(lbs)
39.1(86)
dB(A)
40 / 39 / 37
dB(A)
64 / 61 / 57
Ø, V, Hz
1, 208-230, 60
EEV
AWG 18 x 2C
- 4 -
Ceiling Concealed Duct -Middle Static
ARNU363M2A4
10.6
9 100
36 200
11.9
10 200
40 600
184
430
Galvanized Steel Plate
1 250 × 270 × 700
49-7/32 x 10-5/8 x 27-9/16
3 x 13 x 18
0.27(2.91)
Sirocco Fan
350 x 1
2.3
28.0 / 24.0 / 21.0
989 / 848 / 742
6(59)
28.0 / 24.0 / 21.0
989 / 848 / 742
5(49)
Direct
BLDC
Microprocessor, Thermostat
for cooling and heating
Foamed polystrene
-
Fuse
Ø9.52(3/8)
Ø15.88(5/8)
25(1)
39.1(86)
42 / 40 / 38
65 / 62 / 60
1, 208-230, 60
EEV
AWG 18 x 2C
Copyright © 2018 LG Electronics Inc.
All rights reserved. Only training and service purposes.
ARNU423M2A4
12.3
10 600
42 000
13.8
11 800
47 000
231
430
Galvanized Steel Plate
1 250 × 270 × 700
49-7/32 x 10-5/8 x 27-9/16
3 x 13 x 18
0.27(2.91)
Sirocco Fan
350 x 1
2.3
38.0 / 33.0 / 28.0
1 342 / 1 165 / 989
6(59)
38.0 / 33.0 / 28.0
1 342 / 1 165 / 989
5(49)
Direct
BLDC
Microprocessor, Thermostat
for cooling and heating
Foamed polystrene
-
Fuse
Ø9.52(3/8)
Ø15.88(5/8)
25(1)
39.1(86)
44 / 43 / 40
66 / 65 / 63
1, 208-230, 60
EEV
AWG 18 x 2C
Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
CFM = m
3
/min x 35.3
l/s = CMM x 1 000/60

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents