3 TERMINALS

CONTROL POWER INPUT
Control Power Line 1 (120VAC ± 10%)
1
2
Control Power Neutral
120VAC INPUT LOGIC
3
Start Input – 120VAC
4
Stop Input(three wire control) / DCI or
Soft Stop Enable(two wire control) -
120VAC
5
Jog Input – 120VAC
6
Reverse Input – 120VAC
7
Reset Input – 120VAC
8
Enable Input – 120VAC
9
Input Neutral
MS6 REDUCED VOLTAGE STARTER
Power for the control card and also for
the cooling fans on units below 500A
Momentary normally open switch for 3
wire control. Maintained normally open
switch for 2 wire control
Momentary normally closed switch for 3
wire control. Maintained normally open
switch used to enable or disable a
selected stop mode in 2 wire control.
Maintained normally open switch used
to activate jog function
Maintained normally open switch used
to activate reverse function (if installed).
If activated along with JOG the unit will
run in reverse jog mode
Momentary normally open switch use to
reset a fault
Maintained normally open switch used
to enable unit operation. Unit will not
run if this input is not active. If opened
while running the unit will coast to a
stop no matter what stopping method is
choosen. If this input is active and all 3
incoming phases are valid a green
indicator will be illuminated on the
keypad.
Neutral for 120VAC control signals