Specifications; Power Rating; Maximum Ratings; Service Conditions - SAF Opal Pro MS6 Series Installation & Operating Procedures

Solid state reduced voltage starter for 3 phase induction motors
Table of Contents

Advertisement

MS6 REDUCED VOLTAGE STARTER

2 SPECIFICATIONS

2.1 POWER RATING

Power
Control
Rating
Digital Inputs
Digital Outputs Relay contacts rated at 0.2A, 120VAC
By-Pass Output Relay contact rated at 5A, 120VAC
Analog Input
Analog Output 0 – 5Vdc, 5mA max
Protection

2.2 MAXIMUM RATINGS

OPAL PRO
* HP Rating for estimate only. Size by motor FLA

2.3 SERVICE CONDITIONS

Elevation
Ambient Temperature Do not install in areas where the ambient temperature falls below
0°C(32°F) or exceeds 40°C(104°F)
Page 10
3 phase, 200-600 VAC, 50/60Hz
115VAC 50Hz or 120VAC 60Hz
See Section 2.2
All models have 1600V PIV SCR's
120VAC, 2mA
0 – 10Vdc
Short circuit by HRC fuses or circuit breaker (supplied upon request)
MODEL
230VAC
MS6-30
MS6-50
MS6-80
MS6-125
MS6-250
MS6-420
MS6-500
MS6-600
MS6-800
For altitudes in excess of 1000 meters (3300 feet) above sea level, all
assemblies must be de-rated 1% for every 100 meters (330 feet) above
HORSE POWER
460VAC
10
25
20
40
30
60
40
100
100
200
175
350
200
400
200
500
300
600
575VAC
30
50
75
125
250
420
500
600
800

Hide quick links:

Advertisement

Table of Contents
loading

Related Products for SAF Opal Pro MS6 Series

Table of Contents