IMPORTANT: READ THIS FIRST DO NOT EXPOSE THE F29 Mk2 TO VIBRATION. INSTALL ONLY IN PIPEWORK THAT DOES NOT VIBRATE. Vibration will damage the electronics within the F29 and will void your product warranty. This F29 programmable fl ow switch has been fully tested and calibrated. It is set to operate in a basic way with most of its special functions and features switched off.
Page 3
LCD SCREEN BACKLIGHT The LCD backlight can be turned on or off. To turn the light off press and hold down the (˅) button. Press and release the (R) button. Release the (˅) button. Repeat to turn the light on. The light remembers the state it was last left in, if power is turned off.
Page 4
Do not expose the thermoplastic F29-S to static or dynamic pressures greater than 18 Bars, 261 psi. Do not expose the stainless steel F29-SS to static or dynamic pressures greater than 200 Bars, 2900 psi. 5) Do not install the F29 in a section of pipe that is subject to vibration. Vibration will cause premature failure of the electronic components within the F29.
Page 5
The F29 should be installed in a straight section of pipe preferably with 5 diameters of straight pipe either side of the paddle. The F29 can be installed in a suitable pipe socket, tapping saddle or pipe tee. The F29 can be installed in either the suction or discharge pipework of the pump.
Page 6
closing of the external pressure switch’s contacts on a falling pressure. Choose this arrangement if you want to keep pump starts to a minimum and you are prepared to accept the delay in starting associated with the slow pressure fall from the air cell. Discharge Controller Controller installed before the air cell...
If a low fl ow rate is expected through the system the paddle should be cut longer, perhaps until it only clears the bottom of the pipe by 3 to 5mm. If you are unsure as to what length the paddle should be, a paddle trimming calculator is available at: - http://www.kelco.com.au/paddle-trimming-calculator-2...
Page 8
If you know what the expected fl ow rate is the calculator allows you to enter your pipe diameter and paddle dimensions. It will then determine if the selected paddle dimensions are adequate for the application. Spare paddles to suit the F29 Mk2 are available from Kelco or from your distributor.
FITTING THE PADDLE ASSEMBLY To fi t the paddle assembly into the pipework, apply Tefl on tape or thread sealing compound to the thread and use a suitable spanner and the spanner fl ats provided on the paddle assembly (directly above the process connection thread).
that allows the paddle preload to be reduced. As supplied the sensitivity adjustment screw is wound fully in. In this position the paddle is at its least sensitive. In this position it takes a substantial force from the moving water to move the paddle.
Page 11
WARNING: The contactor control circuit must never exceed 240VAC. Never series connect the F29 relay contacts and contactor coil directly across 2 phases. The F29 requires a stable 220V to 240V AC supply when operated from the mains. It can also be operated from an 18 to 24V AC or DC supply by utilising the low voltage active terminal FELV and neutral terminal N (see the included wiring diagrams).
Page 12
To use the HD drive, place a heavy link wire between the HD terminal and the Normally Open terminal of Relay 1. WARNING The HD terminal must be left unused or only ever linked to Relay 1 Normally Open. It must never be used for any other purpose and it must never be connected to any external device.
Crimp the ears of the strain relief ring onto the cable and pull the cable back into the slots in the gland housing. Controller Housing Rubber Plug Backing Washer Rubber Grommet Backing Washer Cable 7mm to 9mm diameter M20 Gland Nut Plug unused cable glands using the rubber plugs (supplied).
Page 14
POWER REQUIRED TO DRIVE THE STANDARD F29 24VDC Supply to FELV & N Maximum 68mA 1.63Watts 24VAC 50Hz Supply to FELV Maximum 108mA 2.34Watts & N 220VAC 50Hz Supply to A & N Maximum 87mA 2.00Watts 240VAC 50Hz Supply to A & N Maximum 94mA 2.54Watts POWER REQUIRED TO DRIVE THE 12VDC F29-12 With Both Relays Closed 68mA Max at 12VDC...
REMOTE INPUT WARNING: The low voltage source available at the FELV terminal is non-isolated and must be regarded as operating at full mains potential whenever the F29 is powered from the mains. FELV means Functional Extra Low Voltage and refers to a non-isolated extra low voltage source.
Page 16
EXAMPLE A water tank is located 2000 metres from the F29. Two separate wires each 0.2mm^2 are run to the remote tank (total wire length is 4000 metres). The resistance as measured across the 2 wires back at the F29 (with the tank level switch closed) is 382 Ohms.
WIRING DIAGRAMS PLUG & PLAY CONNECTIONS PLUG AND LEAD WIRING Optional voltage free external input All electrical wiring associated with this controller must be carried our by a qualified electrician Earth Link CONNECTIONS FOR A SINGLE PHASE PUMP Supply 110 ~ 240VAC 50/60Hz. Active This link wire must be used whenever the controller is directly controlling a single...
DUAL SINGLE PHASE PUMPS & 2 REMOTE INPUTS Supply 110 ~ 240VAC 50/60Hz. This link wire must be used whenever the controller is directly controlling a single Active phase pump motor, as shown. Do NOT use the HD link in 3 phase or single phase control circuit Neutral applications Remote switches with...
Page 19
BASIC 3 PHASE PUMP CONTROL Contactor WARNING Contactor coil rating must not exceed 240VAC 3 Phase Pump Motor DUAL 3 PHASE PUMP CONTROL Contactor 1 3 Phase Pump Motor 1 Contactor 2 WARNING 3 Phase Pump Motor 2 Contactor coil rating must not exceed 240VAC...
Page 20
Three Phase Pump Motor THE 12VDC F29 FLOW SWITCH A low voltage DC version of the F29 Mk2 is available for battery operation and for use in solar pumping systems. Functionally the 12V DC model is the same as the mains voltage model except for the terminal block markings.
Page 21
12VDC F29-12 CONTROLLING A SINGLE PHASE PUMP This link wire must be used whenever the controller is directly controlling a single Alternate Positive phase pump motor, as shown. Do NOT use the 14 ~ 40VDC HD link in 3 phase or single phase control circuit applications Positive Supply 11 - 24VDC...
Page 22
PROGRAMMING THE F29 Mk2 For a description of the functions of the buttons and lights please read pages 2 and 3 of this manual before proceeding. RESTORING FACTORY DEFAULTS (Purging the Settings) Provided the F29 is unlocked, you can restore it to its default factory settings by pressing and holding down the (P) button and pressing and then releasing the (R) button.
Kelco www.kelco.com.au This is the fi rst screen in the menu. Press and release (P) again. F29 Mk2 Controller Version 000000 The version number must match the number on the cover of this book. Press and release (P) again.
Page 24
closing of the remote contacts causes the F29 to reboot. USE ALARM RELAY The F29 houses 2 output relays. Relay 1 is normally used to control a pump. Relay 2 is normally used as an alarm relay. Selecting yes to this question allows you to confi...
Page 25
suffi cient for fl ow to actuate the F29 paddle before the timer times out. The start-up timer is self-terminating and ceases its run as soon as fl ow is detected. If the start-up timer times out without detecting fl ow, the pump will instantly shut down.
Page 26
To use the pre-start delay timer, press (˄) followed by (P). Use the (˄) or (˅) button to enter a suitable delay period. The display increments up in 60 second steps and down in 1 second steps. Press (P) to lock your selection in and move to the next screen.
Page 27
to 99 hours 59 minutes in increments of 1 minute. Its uses include preventing rapid cycling if the system’s air cell becomes water logged or if a fault develops in a system’s external pressure switch. As an example of its use, consider a pressure system fi...
set to and then stop for the time set on its stop timer. If a run time is set to some value and the stop time is left set at zero, the fl ow switch will behave as a one-shot batch controller. On pressing the reset button or switching the pump on, the pump will run for the set period and then shut down.
Page 29
restart the pump automatically if it runs dry can be a very useful function. Consider a submersible pump installed in a low yield bore. The bore can be pumped until dry and the F29 can be set to shut down the pump as soon as loss of fl...
invoked. If, however, the pump was to start 5 times in a row with less than 10 seconds between the starts the anti-cycling system would be invoked and the pump will shut down. In a conventional pressure system, the anti- cycling function can be used to protect the pump from damage in the event of the system’s air cell losing its air charge.
will only operate in systems where the F29 is connected to an external pressure switch as it relies on the opening and closing of the pressure switch contacts to count pump starts. To use the leak detector, open all valves feeding into the pipe system to be tested.
the reset button is pressed or each time power is reset. THE HOUR METER The F29 includes an hour meter that keeps track of the total time a pump runs for. The hour meter displays the total hours run for 2 seconds each time the pump stops.
Page 33
This Warranty and Limitation of Liability (or any more recent version in effect when you purchase a Kelco Product) (“Warranty”) applies to all Kelco Products regardless of where you purchased the Kelco Products.
Page 34
Fitness of Kelco Products in a Customer Application. (3) You will confi rm that Kelco Products are properly wired and installed for their intended use in your overall system. In the case of Kelco pump controllers, the fl exibility of their operating system means it requires an extensive knowledge of pumps and their characteristics and the intended overall goal of the system in order to select the correct functions and settings.
Page 35
Products by the customer. . (2) Sole Remedy: Unless required to do otherwise as a result of statutory guarantees applicable under ACL, Kelco will provide, at its own discretion, either of the following two services as the sole remedy for a malfunctioning Kelco Product:...
Page 36
(4) If you intend to make a claim under this Warranty you must contact Kelco to register your claim by telephone on (02)99056425 and provide the following details to enable Kelco to assess the claim: (i) proof of purchase;...
Page 37
LIABLE FOR ANY DAMAGES WHICH MAY ARISE FROM OR BE RELATED TO KELCO PRODUCTS. 7. Confi dentiality: You accept that if you make a Warranty claim, Kelco and its agents may exchange information in relation to you to enable Kelco to meet its obligations under this Warranty.
Need help?
Do you have a question about the F29 Mk2 and is the answer not in the manual?
Questions and answers