Alarm Settings; Spare Parts - Jerguson MTII4200 Series Installation, Operation & Maintenance Instructions Manual

Level transmitter

Advertisement

17.) Press the arrow UP key (far left) so the screen will now display "Set Span?".
18.) Move the float to the span location.
19.) Press Enter.
20.) The screen will display "Span (corresponding number)".
21.) Press Enter to reset the (corresponding number) to span and hold for approximately 1-3 seconds.
22.) The screen will display "ACCEPT?".
23.) Press Ener (You have now set the span point).
24.) The screen will display "Cal Lev 1?".
25.) Press and hold all three button simultaneously for 2-3 seconds to reset the unit.
26.) The zero (4mA) and span (20mA) set points are now configured.
To calibrate or change the working range of the transmitter, press any button to enter Function Mode. Hit the enter button
when the "CAL LEV 1?" prompt apprears. "Calibrate Zero" should now be on the display, if not press the Up or Down
button until it is. Press the enter button to set the low level of the range. At this time, position the float magnet at the
desired low level point and keep it there while pressing the Enter button and holding it down for approximately two
seconds. Once done, "ACCEPT" should be on the display, press the Enter button. This is now your new low level for the
range.
Setting a new low level for the range does not change the high level position. To change the high level position, press
Enter when "CAL LEVEL 1?" appears on the display. Press Enter again when "Calibrate Span" is displayed, using the Up
and Down buttons if needed. Repeat the above steps beiginning with "position the float magnet" to change the high level
of the range. When done, press all three buttons to exit Function Mode.

8. ALARM SETTINGS

When a fault condition is detected by the internal microprocessor, the 4 to 20 mA current will go to the current selected.
In the 4 mA alarm mode, when a fault is detected the output will be continuous at 3.8  0.1 mA. In the 20 mA alarm mode,
when a fault is detected the output will be continuous ar 21.5  0.2 mA.

9. SPARE PARTS

MTII4200 Transmitter (Puck) P/N: V19962HP
MTII4200 I/O PCB