Download Print this page

Hochiki TCH-B200 Operating Instructions

Esp device programmer

Advertisement

Available languages

Available languages

Quick Links

HOCHIKI TCH-B200 – ESP DEVICE PROGRAMMER
OPERATING INSTRUCTIONS
(Blue)

General Description

The TCH-B200 ESP Programmer is designed for use with the following products:
C
ALK / ALG-ALN
C
AIE-E
C
ATG-E
C
ATJ / ACB-E
/ ACB-EW
C
ACC / ACA-E
3
HCP Range
3
CHQ-POM
C
CHQ-ARI
C = device clips straight onto Programmer, 2 = in conjunction with PL-2 Programming Lead, 3 = in conjunction with PL-3 Programming
Lead
The programmer is used to set the address of the above products for use with Hochiki ESP systems. The unit is
designed to be light, robust and easy to use and operates from a single PP3 size, heavy-duty battery which gives
the capacity for up to 8,000 operations.
Keys
The TCH-B200 has 3 operating keys, a middle blue key and lower left and right grey keys, these keys have the
following functions.
Left (grey key) key - Power On - automatically reads the address of the fitted sensor - subsequent
operations of this key will advance the programmer address in units of 10.
Right (grey key) key - Advances the programmer address display in units of 1. Also used as the Power Off
button.
Centre (Blue key) key - Stores the displayed address to the Sensor and is used to read the Sensor's
analogue levels.
Operation - Address Setting
Locate the Device onto the programmer ensuring the 3 locating pips line up with the grooves in the
programmer.
Press the left (grey) key to switch the programmer on, a battery check message will be displayed followed by
the address of the device fitted (previously un-programmed devices will read 127).
Select the required address by incrementing the programmer display (left grey key, 10's, right grey key,
units). Whilst the display is showing an address different to that stored in the device, 3 dots will also flash.
Once the wanted address is displayed press the centre (blue) key to store the address in the device. Once
the address is correctly stored the 3 dots will cease to flash and the display will show the address set.
To program a CHQ-BS a PL-2 Programming Lead must be used, firstly connect the plug into the remote
www.acornfiresecurity.com
Analogue Photoelectric
Sensors
Analogue Ionisation Sensor
Analogue Heat Sensor
2
Analogue Multi-Heat Sensors
Analogue Multi-Sensors
Analogue Manual Call Points
Powered Output Module
Addressable Remote Indicator
www.acornfiresecurity.com
C
CHQ-WS2
Wall Sounder
C
Wall Sounder Beacons
CHQ-WSB/WSB2
C
YBO-BS
Base Sounder
C
Base Sounder Beacons
YBO-BSB/BSB2
C
CHQ-CB/WB/AB
Addressable Beacons
3
Single Input Module
CHQ-SIM
2-3-0-237/ISS5/SEP15

Advertisement

loading
Need help?

Need help?

Do you have a question about the TCH-B200 and is the answer not in the manual?

Questions and answers

Summary of Contents for Hochiki TCH-B200

  • Page 1: General Description

    PP3 size, heavy-duty battery which gives the capacity for up to 8,000 operations. Keys The TCH-B200 has 3 operating keys, a middle blue key and lower left and right grey keys, these keys have the following functions. ...
  • Page 2 TCH-B200 and then connect the black croc clip to the C terminal, and the red croc clip to the L terminal on the base sounder. The address can now be programmed as described above. ...
  • Page 3 Akku betrieben werden, der eine Kapazität von bis zu 8.000 Betriebsvorgängen bietet. Tasten Die TCH-B200 ist mit drei Betriebstasten versehen: der blaue Taste in der Mitte und den grauen Tasten unten links und rechts. Den Tasten sind folgende Funktionen zugewiesen: Linke Taste (grau) –...
  • Page 4 Zum Programmieren eines CHQ-SIM, CHQ-POM, CHQ-WS oder eines anderen HCP-Handfeuermelders muss das PL-3-Programmierkabel verwendet werden. Stecken Sie den Stecker in die Fernprogrammierbuchse am TCH-B200 ein. Stecken Sie dann den quadratischen Stecker in die Programmierbuchse am Gerät ein. Die Adresse kann nun wie oben beschrieben programmiert werden.