Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 C-PRO 3 CLIMA sistema+ Climatic modules for the air conditioning and heating of buildings ENGLISH INSTALLER MANUAL ver. 1.1 CODICE 144CP3CSE114 page 1 of 74...
Page 2
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 Important Important Read this document thoroughly before installation and before use of the device and follow all recommendations; keep this document with the device for future consultation.
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 Index GENERALITIES ............................6 Description............................. 6 APPLICATIONS ............................7 INSTALLATION ............................8 Dimensions ............................ 8 3.1.1 Thermal power plant (MCCT), zone modules (MCZN) and solar panels (MCPS) dimensional drawing..8 3.1.2...
Page 4
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 User menu ........................... 30 Maintenance menu ........................30 Installer menu ..........................30 Manufactor menu .......................... 30 Main OFF page..........................31 5.10 Main ON page ..........................31 5.11 State pages ..........................
Page 5
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 Configuration parameters ......................53 7.6.1 List of MAINTENANCE menu configuration parameters ..............53 30 ................................55 7.6.2 List of INSTALLER menu configuration parameters ................ 56 Unit status ........................... 57 Regulations ............................
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 GENERALITIES Description The climatic modules of the c-pro 3 CLIMA sistema series are devices studied for the air conditioning and the heating of buildings. They make use of the programmable controllers belonging to the c-pro 3 series and of the user interfaces belonging to the same series.
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 APPLICATIONS Example of maximum configuration - n. 1 thermal power plant module c-pro 3 mega MCCT or c-pro 3 hecto - n. 8 zone modules c-pro 3 hecto MCZN - n.
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 INSTALLATION Below we will show the dimensions, assembly and electric connections of the c-pro 3 CLIMA sistema, made up from thermal power plant modules (MCCT), Zones (MCZN), solar panels (MCPS) and graphical displays (Vroom).
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 3.2 Assembly 3.2.1 Assembly of thermal power plant modules (MCCT), Zone (MCZN) and solar panels (MCPS) To install the thermal power plant, zone and solar panels module, operate as indicated in the diagrams (points 1 and To remove thermal power plant, zone and solar panels module, use a screwdriver and operate as indicated in the diagrams (points 3 and 4).
3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 3.2.2 Display Assembly (Vroom) There are three possibilities for assembly of the Vroom graphical display: 3.2.2.1 Wall recessed in 506E box 3.2.2.2 Wall-installation, on Evco CPVW00 support 3.2.2.3 Panel installation page 10 of 74...
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 3.3.3 Return temperature control The return temperature is monitored so as to avoid, for example in summer mode, that if cooling is required and the water that arrives at Vmix is hot heads are activated by heating the environment rather than cool it. A check is done...
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 3.4 Regulators network configuration The c-pro 3 CLIMA sistema is based on the CANbus communication between the various control modules present in the network, with the following maximum configuration: •...
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 3.4.1 MCCT thermal power plant controller network configuration The controller of thermal power plant (the logical center of the controlled), you must first set the number of zone controllers MCZN will be present in the system, using the following procedure: 1.
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 3.5.1 Public terminal If the viewer is configured as a terminal Vgraph public (universal), will be able to view all zone controllers MCZN in the system and all areas managed by the controllers MCZN to 6 zones.
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 3.5.2 Module private terminal If the viewer is configured as a private terminal of separate zones, each viewer will be able to display only the regulator MCZN chosen area, managing the areas controlled by the controller MCZN.
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 3.5.3 Zone private terminal If the viewer Vroom is configured as a private terminal areas separated, every Vroom display will be able to only show the preselected MCZN zone regulator, and only the zone selected managed by the MCZN controller.
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 MCZN zone controllers settings: Below find the settings to make on the MCZN regulators to make Vroom a private zone terminal: From the Installer Other parameters menu, enable the presence of the private zone Vroom display by setting...
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 4.2 Navigation through the applications making up the system The c-pro 3 hecto+ MCCT controller represents the heart of the c-pro 3 CLIMA sistema, also from a user interface point of view.
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 c-pro 3 hecto+ MCCT regulator Through the module, you can manage the circulation pumps, boiler and chiller-heat pump. It is able to manage up to two discharge lines (expandable to four by using the expansion I / O c-pro 3 hecto + EXP), eight modules and a module area of solar thermal panels.
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 5.2.2 Status page P1: Pump discharge line on AL : Pump lock FL: Flow alarm Fs: Reached maximum number flow alarms LT: Low temperature alarm sent HT: High temperature alarm sent...
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 5.2.3 Menu page 5.2.4 Network *: Zone not configured A: Zone in alarm !: Zone disabled ?: Zone offline =: Zone OK +: Zone request with C / F...
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 5.3 Alarms/log menu This menu contains the functionality linked to the controller alarms and the alarms log of the system. 5.3.1 Alarms log To view the system alarms log (MCCT regulator and MCZN regulators), press ENTER on “hystorical alarms”.
Page 28
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 Disable supply on AL07 Supply Temperature probe L6 T. regulation Disable return on AL08 Return Temperature probe T. control Closed mixing AL09 Return temperature alarm PAR retard...
Page 29
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 AL23 Flow switch alarm L2 Line Lock PAR retard AL24 Flow switch alarm L3 Line Lock PAR retard AL25 Flow switch alarm L4 Line Lock PAR retard...
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 5.4 Clock menu From this menu you can set/change the value of the date and time that the module c-pro 3 MCCT extends to the whole c-pro 3 CLIMA sistema.
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 5.9 Main OFF page The main OFF page changes depending on the reason for which the unit is off. The unit in OFF alarm can be switched off completely using the key, digital input or supervisor.
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 5.12 Configuration parameters The following task map lists all the configuration parameters contained in the user menu, maintainer, installer and manufacturer. For each parameter is also provided a brief description, the range of permissible values, the unit of measure and the default value proposed.
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 The machine On/Off key is the ESC key, pressed for about 2 seconds. The remote On/Off input (when present) can be configured via the parameters: PH02: Enables the function PH34 : Sets the NC, NO logic for the digital contact 5.13.1 OFF state due to alarm...
Page 38
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 As well as selection of the operational mode, a digital output is linked to the summer/winter functioning mode, which functions as follows: Functioning mode State of the digital input...
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 c-pro 3 hecto MCZN regulator Via the form you can manage the collectors of heating/cooling and dehumidification of those, for its management is necessary to use a remote user interface.
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 6.2.3 Screenshot setpoint area Configuration Screen 1 6.2.4 Screen time zones The time slots are available for each day 5 and for each of them can be configured setpoint "night", "economy", "comfort"...
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 6.2.5 Screenshot holiday You can set the start date and end and enabling the vacation mode. 6.3 Main menu accessible by MCCT Under Network Module MCCT you can access the setup pages of all the operating parameters of the controller are organized in the following sub-menus: 6.3.1 Alarm menu...
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 6.3.4 Manufactor menu The menu manufactor is level 4, that is used to enter the password level builder to be able to view/edit the parameters in this branch.
Page 43
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 1: Summer 2: Winter 3: Summer/Winter Kind of booster 0: OFF PZ05 1: Summer 2: Winter 3: Summer + Winter PZ16 Delivery line associated (CT) Temperature probe...
Page 44
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 3: Summer/Winter Kind of booster 0: OFF PZ09 1: Summer 2: Winter 3: Summer + Winter PZ18 Delivery line associated (CT) Temperature probe 0: --- 1: Vroom...
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 c-pro 3 hecto MCPS regulator 7.1 List of pages This paragraph presents the main pages and menus found in the MCPS application. As shown previously, the main menu is divided into 2 levels: maintenance technician and installer are also present along with "States”...
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 7.2 Main page The main page is displayed during the ON state: By pressing the DOWN key it is possible to select whether to access the State, pages, the Main Menu or the System Network, described below.
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 7.4 Main menu By accessing the pages of the main menu from the “Main Page” of the MCPS regulator, access the setting pages of all regulator functioning parameters organised in the following sub-menu: 7.4.1 Alarms/log menu...
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 Entering the GENERAL PARAMETERS menu, it is possible to enable/disable and set the parameters relative to the execution of the Antigrip and Antilegionella cycles, as well as the calibration of the signals coming from the temperature probes.
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 7.5 System Network page From page network system controller MCPS you have the option to return to the application of thermal power plant MCCT, as follows: By pressing ESC key, the controller will go back all the same to the main display of the MCCT thermal power plant controller.
Page 54
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 General parameters Water temperature set-point during the antilegionella Antilegionella cycle 70.0 150.0 Setpoint (expressed in °C) General parameters Duration of the antilegionella cycle Antilegionella (expressed in minutes)
Page 55
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 - DHW = heat exchange with DHW tank - SOL = heat exchange with solar panel Aux1 Maintenance Auxiliary 1 circuit water temperature set-point 60.0 35.0 80.0 Setpoint (expressed in °C)
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 7.6.2 List of INSTALLER menu configuration parameters Label Parameter description Default I/O CONFIGURATION I/O configuration Type of analogue input configured for AIn2: AIn 1 read only parameter...
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 the value of the differential for that zone, the MCZN regulator will activate the corresponding zone heating/cooling manifold. The activation of the manifold automatically generates an activation request for the delivery circulation pump in the MCCT controller that serves the requesting zone which, after a delay time that can be set from the parameter, activates the circulation of water in the system and the management of the mixing valve.
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 If it is NOT configured an electric battery or hot water with the function of post-heating the request of temperature or humidity will take precedence in accordance with the priorities defined by parameter. If it IS configured a battery electric or hot water function with re-heating it will be activated to prevent excessive cooling environment.
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 8.1.4.2 Variation of the zone work set-point for "manual compensation" (MCZN module) By activating the work set-point variation function for “manual compensation” by installing a remote set-point variator it is possible (e.g.
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 8.1.6 "Heating/cooling integration" function (MCZN modules) You can activate the "auxiliary heating/cooling" (also referred to by the term "booster"). This function allows the use of the battery housed in the dehumidifier for adjustment of temperature, through an air system in support of that regularly checked by the system.
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 • Management of the water heater (boiler): correct operation of the boiler is controlled by a digital input block heater that, if activated, will immediately block the user •...
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 In the installation phase it is necessary to set a proportional regulation band and, if necessary, an integration constant for a PI control, on the basis of system features.
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 8.2.8 Control of the high and low delivery temperature (MCCT module) Whenever the temperature of the delivery water exceeds or drops below the minimum and maximum temperature...
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 8.3.4 Management of digital on/off dehumidifier The zone controller c-pro 3 hecto MCZN has two digital inputs (one for each zone) on/off dehumidifiers. If the digital input is at logic level "disabled", the corresponding additional dehumidifier will be considered in the OFF state and all of its settings are disabled.
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 8.4.2.1 DHW circuit circulation pump management (MCPS module) with setpoint panel mode. The controller for solar panels MCPS is able to manage a DHW tank with circulation pump.
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 As well as the request by the AUX 1 circuit, the solar panels circuit circulation pump will be activated for the following special cycles: auxiliary circuit low temperature protection...
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 8.5 Management and configuration of the heating solar panel circuits (MCPS module) 8.5.1 With DHW setpoint Whenever the c-pro 3 hecto MCPS module for solar panels is present and enabled in the system, one or two heating solar panel circuits management can be enabled, with the function of heating the DHW in the DHW tank.
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 8.5.3 Management of the solar panels circuits circulation (MCPS module) The controller for the MCPS solar panels can manage up to 2 thermal solar panel circuits, each with relative circulation pump.
Page 70
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 As well as the cover opening relay, the circulation pump of the corresponding solar panels circuit is activated at the same. Cover2: the stagnation emergency will be managed by the opening/closing of a motorised cover (servomotor with separate opening and closing controls) which will cover the surface of the solar panels from solar exposure.
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 8.6 Other regulations 8.6.1 Management and setting of the periodic anti-grip cycle (MCCT, MCPS modules) The function has the purpose of preventing the blocking of the pumps and valves present in the c-pro 3 CLIMA sistema during system standstill due to any deposits present in the system or due to the formation of crystalline aggregates (lime scale or other) on the mechanical seals of the pumps and valves.
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 8.6.3 Manual functioning mode (MCCT, MCZN, MCPS modules) The c-pro 3 CLIMA sistema allows to set manual functioning for the various uses. In this state the devices are not governed by the automatic functions, but are however sensitive to any alarms.
Page 73
This document is exclusive property of EVCO. Reproduction and disclosure are prohibited without express authorisation from EVCO. EVCO is not liable for any features, technical data and possible errors stated in this document or deriving from use of the same.
Page 74
Evco S.p.A. c-pro 3 CLIMA sistema | Installer manual ver.1.1 | Code 144CP3CSE114 EVCO S.p.A. Via Feltre 81, 32036 Sedico Belluno ITALIA Tel. 0437 / 84.22 Fax 0437 / 83.648 info@evco.it www.evco.it page 74 of 74...
Need help?
Do you have a question about the C-PRO 3 CLIMA sistema+ and is the answer not in the manual?
Questions and answers