MAINTENANCE

Before performing any maintenance, stop
the machine and disconnect it from the
power supply and from the compressed
air distribution network.

MAINTENANCE SCHEDULE

These maintenance intervals are recommended for work
environments that are not dusty and are well ventilated.
For particularly dusty environments, double the frequency
of these operations.
Each Week
Condensate drain: Clean the filter of the auto drain.
Each Month
Condenser: Clean the condenser fins to remove
accumulated dust.
3

CLEANING THE CONDENSER

The condenser must be cleaned every month (see Figure 13).
1.
Switch off the machine by turning the STOP button to
position "0 OFF" (3).
2.
Turn off the supply by opening the circuit breaker or
fused disconnect switch (4).
3.
Remove the panels (5).
10
CLEANING AUTOMATIC CONDENSATE
DRAIN FILTER
(see Figure 13)
10. Close the panels (5).
4
2
FIGURE 13 — MAINTENANCE
Back to TOC
1.
Isolate the dryer from the air system (1).
2.
Release the pressure in the dryer by pressing the
condensate drain "TEST" pushbutton located on the
auto drain (2).
3.
Switch off the machine by turning the STOP button to
position "0 OFF" (3).
4.
Turn off the supply by opening the circuit or fused
disconnect switch (4).
5.
Remove the panels (5).
6.
Remove the stopper (6).
7.
Remove the filter (7).
8.
Clean the filter (7) with a jet of air, working from
inside to outside.
9.
Install the filter and affix the plug (7 - 6).
6
7
5
4.
Clean the condenser fins with compressed air. DO
NOT USE WATER OR SOLVENTS.
5.
Close the panels (5).
1