Advertisement

Quick Links

KES Plus
KNX Energy Meter
ZIO-KESP
Application Program Version: [1.2]
User Manual Version: [1.2]_a
www.zennio.com

Advertisement

Table of Contents
loading

Summary of Contents for Zennio KES Plus

  • Page 1 KES Plus KNX Energy Meter ZIO-KESP Application Program Version: [1.2] User Manual Version: [1.2]_a www.zennio.com...
  • Page 2: Table Of Contents

    1.2 Installation ........................5 1.2.1 Current Transformer ....................6 1.2.2 KES Plus use cases in different types of installations ..........7 1.3 Measured Quantities ...................... 10 1.4 Consumption data Initialization after a download ............13 1.5 Setting the time of day ....................15 1.6 Visual Notification ......................
  • Page 3: Document Updates

    KES Plus DOCUMENT UPDATES Version Changes Page(s) Changes in the application program: • Global consumed and generated power objects are included. • V and A are added to the voltage and current unit selector. • Sending of voltage and current magnitudes.
  • Page 4: Introduction

    1 INTRODUCTION 1.1 KES PLUS The KES Plus (KNX Energy saver) from Zennio is an energy saver of electrical energy for single-phase or three-phase systems. It can measure and notify in KNX system, not only the consumed or produced energy,...
  • Page 5: Installation

    Please refer to section 1.2.2 to get detailed information about the different use cases and connection schemes for each type of installation. Once KES Plus is provided with power from the KNX bus, both the individual address and the associated application program can be downloaded.
  • Page 6: Current Transformer

    To get detailed information about the technical features of the device, as well as on the installation and security procedures, please refer to the corresponding Datasheet, bundled with the original package of the device and also available at www.zennio.com. 1.2.1 CURRENT TRANSFORMER The set-up process of the ZN1AC-CST60 and ZN1AC-CST120 transformers is described below.
  • Page 7: Kes Plus Use Cases In Different Types Of Installations

    KES Plus 1.2.2 KES PLUS USE CASES IN DIFFERENT TYPES OF INSTALLATIONS The following figures show the connection diagram of KES Plus in different types of installations: Case 1: Three-phase installation with accessible neutral wire and three-phase load Three- phase load Parameter setting as three-phase system (see section 0).
  • Page 8 KES Plus Case 3: Single-phase installation with accessible neutral wire or two-phase with ≤230V Línea Parameter setting as single-phase system (see section 2.2.2). For two-phase systems: Phase voltage ≤ 230V Figure 4 Single-phase system with accessible neutral wire or two-phase system.
  • Page 9 Figure 6 Three-phase system without accessible neutral wire and single-phase loads. In this case, since two KES Plus are used, the power measurements per phase can be added together using a logic function (section 2.6) to obtain total (three-phase) power measurements, provided they are set in kW.
  • Page 10: Measured Quantities

    KES Plus 1.3 MEASURED QUANTITIES Next, the quantities measured by the KES Plus that can be sent to the bus for monitoring and energy management are described.  magnitude available for three-phase systems.  magnitude available for single-phase systems. Magnitudes of each conductor or phase: Phase Voltage (T/S): rms value expressed in millivolts [mV] or volts [V].
  • Page 11 KES Plus Generated Active Power (S): Sum of generated active power of each phase. Resolution: 8W Active Power (T/S): arithmetic sum of the active power of each phase. Resolution: 8W. Reactive Power (T/S): power developed in capacitive and inductive circuits.
  • Page 12 KES Plus Phase / Single Three- Magnitude Units Global Phase Phase Voltage mV / V Current mA / A Active Power W / kW Per Phase Active Consumed Energy W·h / kW·h Active Generated Energy W·h / kW·h Power Factor...
  • Page 13: Consumption Data Initialization After Adownload

    KES Plus 1.4 CONSUMPTION DATA INITIALIZATION AFTER A DOWNLOAD It is important to keep in mind that, when reprogramming the device from ETS (either partial or complete downloads), the consumption variables and therefore any data accumulated so far are cleared on both partial and total registers.
  • Page 14 KES Plus Initialization Phase / Global Magnitude Single Phase Three-Phase - By parameter Active Energy Consumed - By object Total Register - By parameter Active Energy Generated - By object Phase - By parameter Active Energy Consumed - Reset register...
  • Page 15: Setting The Time Of Day

    1.5 SETTING THE TIME OF DAY For certain functionalities, such as periodic registers or the starting date of each register, it is necessary to set the time of day of KES Plus through a master clock in the installation. During the start-up, KES Plus will request the time of day to the KNX bus through the objects “Date”...
  • Page 16: Visual Notification

    KES Plus 1.6 VISUAL NOTIFICATION KES Plus includes four LED indicators which provide information of the consumption in each of the phases in single phase systems or the consumption of the three phases in three-phase systems. The LEDs are bicolour. The colour indicates whether there is consumption or generation of energy in the phase: Yellow LED: consumption of energy.
  • Page 17: Configuration

    KES Plus 2 CONFIGURATION 2.1 GENERAL After importing the corresponding database in ETS and adding the device into the topology of the desired project, the configuration process begins by entering the Parameters tab of the device. ETS PARAMETERISATION The configurable parameters on the General screen are the followings: Figure 7: General Initial State Sending Delay [5…255]...
  • Page 18 KES Plus ➢ Number of Phases / 2 / 3]: Number of phases of the installation. Number of Partial Registers / 1 / 2]: Sets the number of partial registers for each consumption register. When selecting more than zero, the following objects appear (apart from the registers itself): ➢...
  • Page 19 The communication objects available by default are  available for single-phase systems.): systems; “Data” y “Time of day” (T/S): Objects for updating date and time of KES Plus. See section 1.5 for details. “[Global / 3-Phase] Request metering” (T/S): When receiving a “1” through this object global magnitudes of power, energy, cost and emissions, as well as voltage and current of each phase are sent to the bus.
  • Page 20 KES Plus Notes: The label [Phn] refers to magnitudes or measures of phase n (where n = 1, 2, The label [Global] refers to magnitudes or measures of the phases altogether in single phase systems. The label [3-Phase] refers to magnitudes or measures of the phases altogether in 3-phase systems.
  • Page 21: Phases

    The options available will slightly differ for each case, although are entirely analogous. 2.2.1 GENERAL CONFIGURATION On this screen, the basic configuration common to all KES Plus phases can be selected. ETS PARAMETERISATION The general Configuration parameters are shown below:...
  • Page 22: Single Phase System

    KES Plus Phase/3-Phase Nominal Power [[100…30000][W][1…30][kW] [100…90000][W][1…90][kW]]: sets the phase nominal power which will be used to calculate the light-on time of the LEDs (see section 1.6 for details). The available range will vary depending on the power unit selected.
  • Page 23 KES Plus Global Description: text box without functionality, simply allows adding a description. Sending Mode for Power [Disabled / Periodic / With Value Change / Periodic and with Value Change]: sets when global power objects should be sent. Depending on this selection, some more parameters will be available.
  • Page 24 KES Plus Sending Mode for Energy [Disabled / Periodic / With Value Change / Periodic and with Value Change]: sets the sending mode of consumption, cost and CO emissions objects. Depending on this selection, some more parameters will be available: Figure 13 Phases: Global - Total Register –...
  • Page 25 KES Plus ETS PARAMETERISATION The parameters to configure any of the partial registers are: Figure 14 Phases: Global - Partial Register Sending Mode for Energy [Disabled / Periodic / With Value Change / Periodic and with Value Change]: analogous to the same parameter of the total register (see section 2.2.2.1.1).
  • Page 26 KES Plus 2.2.2.2 PHASE n On this screen can be configured the options related to phase objects, that is, those that refer to measures of a specific phase. ETS PARAMETERISATION The parameters shown in each phase tab are the following:...
  • Page 27 KES Plus Sending Mode for Voltage [Disabled / Periodic / With Value Change / Periodic and with Value Change]: sets when voltage object of the corresponding phase should be sent. Depending on this selection, some more parameters will be available.
  • Page 28 KES Plus ➢ Minimum Time Between Sendings [10…255]: sets a minimum period of time (seconds) between consecutive sendings. ➢ Minimum Change to Send [[100…1000…130000][mA] / [1…130][A]]: sets the minimum value change required to send the next value. Sending Mode for Power [Disabled /...
  • Page 29 KES Plus Sending Mode for Energy [Disabled / Periodic / With Value Change / Periodic and with Value Change]: analogous to the same parameter of the global registers (see section 2.2.2.1.1). 2.2.2.2.2 Partial register They are equivalent to partial records of global magnitudes (see section 2.2.2.1.2), but in this case, they store single-phase data.
  • Page 30: Three-Phase System

    KES Plus 2.2.3 THREE-PHASE SYSTEM When selecting a single-phase system, there is one more tab apart from the “General Configuration”: “3-Phase”. 2.2.3.1 3-PHASE On this screen can be configured the options related to 3-phase system objects. These are measures of all phases together.
  • Page 31 KES Plus Sending Mode for Voltage [Disabled / Periodic / With Value Change / Periodic and with Value Change]: analogous to the same parameter in the tab “Phase n” (see section 2.2.2.2). Sending Mode for Current [Disabled / Periodic / With Value Change / Periodic and with Value Change]: parameter analogous to the same described in the tab “Phase n”...
  • Page 32 KES Plus ➢ In case of time adjustments, resets may be affected by a delay. ➢ In case of selecting “Same Day of Month”, the specific day of the month will change whenever the register is manually reset through the object.
  • Page 33: Tariffs

    KES Plus 2.3 TARIFFS For every register, it is possible to calculate the monetary cost of the accumulated consumption/generation, together with the consumption corresponding to each tariff, in case of a time-slot based tariff system. Thus, it will be possible to configure up to six tariffs, being also possible to modify them through object.
  • Page 34 KES Plus For each tariff enabled consumption and cost (or income) communication objects are added for each tariff. For example, for tariff 1: ➢ “[Trf1] [TR] Tariff Consumed Active Energy” ➢ “[Trf1] [TR] Tariff Generated Active Energy” ➢ “[Trf1] [TR] Tariff Inductive Reactive Energy”...
  • Page 35: Notifications

    KES Plus 2.4 NOTIFICATIONS Notifications in KES Plus consist in sending a binary object to the KNX bus when the selected variables, stored in either total or partial registers, reach a pre-set value. The variables on which it is possible to configure notifications are consumption, generation, cost and CO emissions, for global magnitudes and 3-phase systems.
  • Page 36: Notification N

    KES Plus 2.4.1 NOTIFICATION n Figure 23 Notifications - Notification y Notification Description: text box without functionality, simply allows adding a description. Phase [Phase 1 / Phase 2 / Phase 3 / Global] [3-Phase]: sets the phase to monitor. The available options depend on the type of installation selected and the number of phases enabled in the General screen (see section 2.1).
  • Page 37: Alarms

    KES Plus 2.5 ALARMS In addition to notifications, KES Plus implements four alarms to monitor the power according to an upper limit (excess power) and a lower limit (low power), which can be enabled and parameterised independently. In the event of being calculated power greater or lower than such limits, the device will send a binary value, respectively through who separated objects.
  • Page 38: Alarm N

    KES Plus 2.5.1 ALARM n Figure 25 Alarms: Alarm n Alarm Description: text box without functionality, simply allows adding a description. Phase [Phase 1 / Phase 2 / Phase 3 / Global] [3-Phase]: sets the phase to monitor. The available variables depend on the type of installation selected and the number of phases enabled in the General screen (see section 2.1).
  • Page 39 KES Plus place when the power reaches a value outside the deadband. The sign must be consistent with the sign of the limit. Low Power [enabled/disabled]: enables or disables the low power alarm. Once enabled, the same parameters as in excess power alarm and the communication object “Alarm n: low power”...
  • Page 40: Logic Functions

    KNX bus, and to send the results through other communication objects specifically enabled for this purpose. KES Plus can implement up to 10 different and independent functions, each of them entirely customisable and consisting in up to 4 consecutive operations each one.
  • Page 41: Annex I: Comunication Objects

    KES Plus ANNEX I: COMUNICATION OBJECTS “Functional range” shows the values that, with independence of any other values permitted by the bus according to the object size, may be of any use or have a particular meaning because of the specifications or restrictions from both the KNX standard or the application program itself.
  • Page 42 KES Plus 2 Bytes C T R - - DPT_Value_Currency -671088.64 - 0 [Phx] [PRx] Income Currency 2 Bytes C T R - - DPT_Value_Currency -671088.64- 670760.96 [Phx] [PRx] Cost / Income Cost > 0; Income < 0 (Currency) 21, 46, 71...
  • Page 43 KES Plus 4 Bytes C T R - - DPT_ActiveEnergy_kWh 0 - 2147483647 [Global] [TR] Consumed Active Energy kW·h [x-Phase] [TR] Consumed Active 4 Bytes I/O C T R W - DPT_ActiveEnergy 0 - 2147483647 W·h Energy [x-Phase] [TR] Consumed Active...
  • Page 44 KES Plus [Global] [PRx] Inductive Reactive 4 Bytes C T R - - DPT_ReactiveEnergy_kVARh -2147483648 - 2147483647 kVAr·h Energy [x-Phase] [PRx] Inductive Reactive 4 Bytes C T R - - DPT_ReactiveEnergy -2147483648 - 2147483647 VAr·h Energy [x-Phase] [PRx] Inductive Reactive...
  • Page 45 KES Plus Energy (Previous Period) [x-Phase] [PRx] Generated Active 4 Bytes C T R - - DPT_ActiveEnergy 0 - 2147483647 W·h Energy (Previous Period) [x-Phase] [PRx] Generated Active 4 Bytes C T R - - DPT_ActiveEnergy_kWh 0 - 2147483647 kW·h...
  • Page 46 KES Plus [Trfx] [TR] Tariff Generated Active 4 Bytes C T R - - DPT_ActiveEnergy 0 - 2147483647 W·h Energy 126, 170, 214, 258, 302, 346 [Trfx] [TR] Tariff Generated Active 4 Bytes C T R - - DPT_ActiveEnergy_kWh 0 - 2147483647 kW·h...
  • Page 47 KES Plus 140, 142, 146, 148, [Trfx] [Phx] [PRx] Tariff Generated 4 Bytes C T R - - DPT_ActiveEnergy 0 - 2147483647 W·h 152, 154, 184, 186, Active Energy per Phase 190, 192, 196, 198, 228, 230, 234, 236, 240, 242, 272, 274,...
  • Page 48 KES Plus 414, 415, 416, 417, 418, 419, 420, 421, 422, 423, 424, 425, 426, 427, 428, 429, 430, 431, 432, 433, 434, 435, 436, 437, 438, 439, 440, 441 442, 443, 444, 445, 446, 447, 448, 449, 1 Byte...
  • Page 49 Join and send us your inquiries about Zennio devices: http://support.zennio.com Zennio Avance y Tecnología S.L. C/ Río Jarama, 132. Nave P-8.11 45007 Toledo (Spain). Tel. +34 925 232 002. www.zennio.com info@zennio.com...

Table of Contents