Materials Required; Before Installation - Prime PHC42W06 Installation & Operating Instructions Manual

Water pipe freeze protection
Table of Contents

Advertisement

Available languages

Available languages

Materials Required

Storage
• These Pipe Freeze Protection Cables should be stored in a clean, dry area when not in use. The storage temperature range is 0°F to
140°F (-18°C to 60°C).

Before Installation

If installing on a new construction, the piping, insulation, electrical and instrument groups need to be coordinated before the installation
of any electric heat tracing system. Installation should begin only after the majority of mechanical construction is complete. Make sure
all mechanical testing (i.e. hydrostatic testing/purging) is complete and the system has been cleared.
If the heating cable is stiff (due to ambient temperatures being below 40°F/4°C), first uncoil the cable completely and power it with a
120V outlet until it is warm and pliable, then unplug the cable and begin installation.
!
Warning:
• Improper installation, use and/or maintenance of heating cable can cause fire, electric shock and/or freezing of pipe.
• Pipe heating cables must be installed in compliance with the National Electrical Code and Canadian Electrical Code. Ground fault
protection (GFCI) is required. If an outlet does not exist close enough to the pipe to plug in the cable, have a licensed electrician
install one for you.
• Do not use with an extension cord.
• Do not connect power to the heating cable while it is coiled.
• Do not install damaged heating cable.
• Minimum pipe length is 6 ft/1.82 m.
• Never alter this heating cable in any way. If made shorter, it will overheat. Once cut, the heating cable cannot be repaired.
• Do not install the same cable on more than one pipe.
• Never allow the heating cable to touch, cross or overlap itself at any point.
• Disconnect the pipe heating cable from its power source during installation.
• While energizing the heating system circuit, regardless of normal operation, installation period or maintenance, always keep the
heating section of the heating cable system away from combustible surfaces at least 1in/ 2.5cm.
Fiberglass tape or application tape
with a temperature rating higher than
175°F/80°C. (not included)
1/2-inch fiberglass or equivalent
non-flammable pipe insulation.
(not included)
3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Phc84w12Phc126w18Phc210w30Phc168w24

Table of Contents