EMERGENCY ASSIST ALARM Models covered: Single Zone Plastic Control Unit Single Zone Stainless Steel Control Unit Plastic Reset Unit Stainless Steel Reset Unit Plastic Over-Door Unit Stainless Steel Over-Door Unit Pull Cord Unit Four Zone Plastic Control Unit Four Zone Stainless Steel Control Unit Single Zone Plastic System Kit Single Zone Stainless Steel System Kit...
1. Models Covered Components Single Zone Plastic Control Unit EACP1 (with battery back up EACP1PR) Single Zone Stainless Steel Control Unit EASSCP1 (with battery back up EASSCP1PR) Plastic Reset Unit EARB1 Stainless Steel Reset Unit EASSRB1 Plastic Over-Door Unit EADF1...
Page 3
Typical Single Zone System (Available as EASZK) Fused Spur (not supplied) 2-wire Single Zone Control Unit 2-wire Pull Cord Unit Over Door Unit 2-wire Reset Unit...
Page 4
Typical Four Zone System There are no four zone kits, but two to four zones can be accommodated by using any of the four zone Control Units in combination with the appropriate number of Reset Units, Over-Door Units and Pull Cord Units. There are no adverse effects if any of the four zone control units input connections are left open.
2. Introduction The basic system consists of a Control Unit (which is powered by AC mains supply) connected by an extra low voltage 2- wire link to a Pull Cord Unit which is in turn connected to an Over-Door Unit by another extra low voltage 2-wire link. The Over-Door Unit is then connected to a Reset Unit by a further extra low voltage 2-wire link.
Page 6
MUST be switched off at all times while installation is in progress • The installation shall be carried out in accordance with all applicable installation rules. • None of the units in the system should be subject to dripping or splashing liquids. •...
3.1. Control Unit This should be sited (following the recommendations of BS8300) where it can best attract the attention of an appropriate person/member of staff. An example of this is near a reception desk in view of a receptionist. Having located the site, install a flush or surface mount double gang wall box at least 25mm deep.
Page 8
Extra Low Voltage Wiring Important: Ensure that low voltage wiring are kept well away from mains wiring. The low voltage wiring must be tied to each other using the tie wrap provided to overcome clearances and creepage distances if any wire becomes detached. Bring the extra low voltage two core cable into the wall box and connect to the terminals marked output (see diagram).
Page 9
3.2. Pull Cord Unit BS8300 (code of practice for the design of buildings and their approaches to meet the needs of disabled people) recommends that this should be sited on the ceiling such that for a toilet it can be operated from the W.C. and an adjacent floor area. The lower handle should be set 100mm above the floor (knot and trim off any excess cord) and the upper handle should be set between 800 and 1000mm above the floor (knot the cord at...
3.3. Over-Door Unit This should be sited to attract appropriate personnel to the area where assistance is required. An example of this is above the toilet cubicle door. Having located the site, install a flush or surface mount single gang wall box at least 25mm deep. Bring the extra low voltage two core cable from the Pull Cord Unit into the wall box and connect to the terminals marked input (see diagram).
Page 11
4. Battery A battery is provided with the following control units and kits - EACP1PR, EASSCP1PR, EACP4PR or EASSCP4PR and cannot be fitted to other types. To fit the battery remove it from the holder and turn it round and offer it up to the connector and after correct polarity is ensured press the battery into the connector.
Page 12
Remove all power source including battery when wiring any part of the system. The following possible faults and solutions are for guidelines only. If in doubt contact the Timeguard Helpline on 020 8450 0515...
Page 13
Symptoms Possible fault Possible Solution Green LED on Mains supply not Check Mains wiring Control Unit is OFF connected Mains switch is off Switch on mains supply Yellow LED on Some units in the Checks the 2 wire Control Unit is ON system are not link in all units are properly connected...
7. Specifications Control Unit Supply voltage: 230V (+10%, -15%) 50Hz Operating temperature: +5 to 40°C Reserve battery: Metal Hydride (rechargeable) PP3, 9Volt Alarm Output: DC voltage through 470 ohm resistor. (Do not connect to mains voltage source) Maximum pull force on pull cord: 200N Reset button marking:...
Page 15
Installation Wiring and Fixing Holes Battery Holder Connector for Reset Mains rating (Back-up PR incoming mains Selection information versions only) supply External Alarm Buzzer WARNING Do not connect to mains supply! Fixing Holes Output Control Unit (Rear) Transformer Fixing Holes Pull Cord Hole Cover Fixing Holes Pull Cord Unit (Backplate)
Page 16
HELPLINE 020-8450-0515 For a product brochure please contact: Timeguard Ltd. Victory Park, 400 Edgware Road, London NW2 6ND 020-8452-1112 or email csc@timeguard.com 67.058.192 Iss 1...