Page 10
WINTER OUTDOOR CONDITIONS Indoor 12ºC D 7ºC D 4ºC D 0ºC D -4ºC D -7ºC D 11ºC W 6ºC W 3ºC W -1ºC W -6ºC W -8ºC W Conditions Capacity kW 8.30 7.38 6.53 4.22 3.53 3.40 15ºC Input kW. 2.94 2.63 2.35...
Page 13
WINTER OUTDOOR CONDITIONS 12ºC D 7ºC D 4ºC D 0ºC D -4ºC D -7ºC D Indoor Conditions 11ºC W 6ºC W 3ºC W -1ºC W -6ºC W -8ºC W Capacity kW 10.46 9.44 8.49 5.91 5.14 5.01 15ºC Input kW. 3.47 3.11 2.80...
Page 16
6.2 Wiring diagram 6.2.1 Cooling only MSE-21CR, MSE-24CR, MSE-28CR W I R I N G D I A G R A M TR A N S 1 ( I N D O O R U N I T) C N 1 X S 2 X P 2 C N 8 U N I T1...
Page 17
6.2.2 Heating/cooling MSE-21CR, MSE-24CR, MSE-28CR W I R I N G D I A G R A M TR A N S 1 ( I N D O O R U N I T) C N 1 X S 2 X P 2 C N 8 U N I T1 FU S E 3.
7.troubleshooting The following tables will help to find where error happened (LED on indoor unit): For models adopting electrical function (part I) (cooling only models): Operation Timer Failure phenomenon lamp lamp Indoor fan speed has been out of control for ☆...
Page 19
☆ ☆ EEROM error ☆ Indoor unit communication err ☆ Flash at 5Hz r Extinguish Cur r ent protectio n (LED indi cates) Chec k t he indoor air filt er. Check the out door condenser. Che ck t he positio n If wro ng, t he unit w ill and wiring of tem p result in current...
Page 20
T he unit does not o per ate Ye s Does the power LED C heck t he elec t rical Per f orm Do th e LED lamps light af ter turning so urce. the related indicat es ERR? the switch on? inst ruct io ns.
Page 21
PROBLEM CAUSE REMEDY Power failure Check the power cord. Wiring failure Check the wiring. Replace the terminates or wires if failure. Not operating Check the input and the output on transformer. Replace if Transformer failure failure. Indoor PCB failure Replace after checked failure. Replace the fan if cracked, out of balance, or partially Cross flow fan failure missing...
Page 22
PROBLEM CAUSE REMEDY Check leakage. Recycle the refrigerant. Correct and Lack of refrigerant recharge if there is any leakage in the refrigerant system. Check the module and the capacitor connected to the Compressor Soft starter module failure module. Replace if failure. protection Overcurrent protector Check the resistance of compressor overcurrent protector.
Page 23
PROBLEM CAUSE REMEDY LED failure Replace the display if checked failure. No display on Remote control shut the indoor unit. Push the button to turn the display on. display No power Check the voltage. Call an electrician if not within the limit. Wiring Check the terminals.
8. Electronic Control Principle of Large Cooling Capacity Split Model A/C Fan only mode Fan speed is high/mid/low/ Auto Cooling mode The 4-way valve is closed at cooling mode. The action of the compressor and the outdoor fan: T: Room temp. Ts: Setting temp.
Page 25
8.4.1 Generally, the 4-way valve is open in heating mode, but it is closed in defrosting mode. 8.4.2 Generally, the outdoor fan is turned off with the on-off action of compressor in heating mode, except for the defrosting mode or the end of defrost. 8.4.3 Action conditions of compressor at heating mode: compressor must run for 4 minutes after starting and then judge temperature.
Page 26
the compressor still running. Add up to 90 minutes 8.5.2 Conditions of defrost ending: Defrosting ends when either of the following : The time gets to 10 minutes; T3>20°c 8.5.3 Time sequence of the whole defrosting procedure is as follows: Defrost 10or 6minutes Compressor 4-way Valve...
Page 27
8.8.1.3 During the start-up and operation, all of the following protecting functions work: 3minutes start-up delay protection, overload protection, outdoor protection, evaporator Protection against low temperature. If any of the protection functions, the comparative protecting action is executed. The forced cooling mode is closed by one touch on the button, meanwhile the operation light is off, the buzzer buzzes lasts for 1 seconds, then A/C turns to be closedown status.