LG LS091HSV3 Engineering Manual page 61

Single zone high efficiency, standard and extended pipe wall mount
Hide thumbs Also See for LS091HSV3:
Table of Contents

Advertisement

Outdoor Unit Clearance
Proper clearance through the outdoor unit coil is critical for proper unit operation. When installing the outdoor unit, consider service, inlet and
outlet and minimum allowable space requirements as illustrated in the diagrams below.
Specific clearance requirements in the diagram below are for the single zone wall mount systems. Figure 27 shows the overall minimum
Outdoor Unit Clearance
clearances that must be observed for safe operation and adequate airflow around the outdoor unit.
Figure 27: Outdoor Unit Clearances
11-3/16
27-19/32
When placing the outdoor unit under an overhang, awning, sunroof or other "roof-like structure, observe the clearance requirements (as
shown in Figure 27) for height in relation to the unit. This clearance ensures that heat radiation from the condenser is not restricted around
the unit.
Adhere to all clearance requirements if installing the unit on a roof. Be sure to level the unit and ensure that the unit is adequately anchored.
Consult local codes for rooftop mounting requirements.
Do not place the unit where animals and/or plants will be in the path of the warm air, or where the warm air and/or noise will disturb neighbors.
PLACEMENT CONSIDERATIONS
23-19/32
11-3/16
23-19/32
Unit : inch
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG " is a registered trademark of LG Corp.
Outdoor Unit Installation
Figure 28: Outdoor Unit Sunroof/Awning Clearances
More than
11-13/16
F e n
c e
o b
o r
s t a
c l e
s
More than
11-13/16
More than
23-19/32
More than
Unit : inch
27-19/32
APPLICATION GUIDELINES | 61