Page 1
F-PM100 Multifunctional Power Meter User Manual Product Version Page F-PM100 Multifunctional Power V1.0 Meter User Manual Product Name:F-PM100 Total: F-PM100 Multifunctional Power Meter For Power Distribution System User Manual Version 1.0...
F-PM100 Multifunctional Power Meter User Manual Product Introduction Multi-function power meter, a multi-function intelligent power meter with full power acquisition, programmable measurement, display, RS485 digital communication and switch input, relay output, it can complete three-phase electrical measurement (includes three-phase voltage, three-phase current, active power, reactive power, apparent power, power factor, frequency, harmonics, multi-rates, demand, SOE event records, etc.), four quadrant energy metering, data display,...
F-PM100 Multifunctional Power Meter User Manual Parameter Accuracy Measuring range 0 999,999V Voltage 0 49,999A Current Power Factor -1.0<|CosΦ|<+1.0 Single-Phase:0 100MW Active Power Total:0 300MW Single-Phase:0 100Mvar Reactive Power Total:0 300Mvar Single-Phase:0 100MVA Apparent power Total:0 ...
Page 4
F-PM100 Multifunctional Power Meter User Manual Relay 1 Output Relay 1 Output Relay 2 Output Relay 2 Output AC power supply 220V Zero Line AC power supply 220V live wire Remark: Indicates that the terminal function is related to the order type.
Page 5
F-PM100 Multifunctional Power Meter User Manual 4. Power Meter Parameter Setting 4.1 Key Functions in Setup Mode: When the cursor is flashing, select and confirm the function (Enter key); : When the cursor is flashing, modify the configuration; When the cursor is flashing, switch the parameter page (up key);...
Page 6
F-PM100 Multifunctional Power Meter User Manual Page Content Description Press "SET" key to enter into setting mode; Press " " key, the digital cursor will flash, prompt for the password entering , the factory default value is 0000;...
Page 7
F-PM100 Multifunctional Power Meter User Manual The communication address range is 1 ~ 254, the factory default communication address is 1; Press the " " key to move the cursor to the communication address modification area; Press "...
Page 8
F-PM100 Multifunctional Power Meter User Manual The Power Meter should set the correct CT variable ratio parameters. Value range of the setting is 0 ~ 5000, the factory default of the Power Meter is 1. For example, CT: 500/5 requires a CT value of 100.
Page 9
F-PM100 Multifunctional Power Meter User Manual You can manually enter the base of active power . When no cursor is flashing, press " " to switch to the setting page; Press " " to start the setting; 8. Preset the ...
Page 10
F-PM100 Multifunctional Power Meter User Manual Power Meter enters into the presentation mode When no cursor is flashing, press " " to switch to the 11. Settings setting page; of the Press " " to start the setting;...
Page 11
F-PM100 Multifunctional Power Meter User Manual The password of the manual controlling relay output is 4131. When no cursor is flashing, press " " to switch to the page; Press " " to start the setting; Press the "...
Page 12
F-PM100 Multifunctional Power Meter User Manual Press " " key to move the cursor, press " " key to change the cursor value to set the rate period and rate time; Press " " key to save the setting;...
Page 13
F-PM100 Multifunctional Power Meter User Manual (3) Overcurrent value and overcurrent time ; (4) Zero sequence overcurrent value and zero sequence overcurrent time; (5) 5 Phase loss threshold and phase delay time; (6) Low PF value and low PF setting time;...
Page 14
F-PM100 Multifunctional Power Meter User Manual Press " " key to start each phase setting; Press " " key to move the cursor, press " " key to change the cursor value to set the alarm value; Press "...