Damper Maintenance - Greenheck FD 150X Installation, Operation And Maintenance Instructions

1 1/2 hour curtain fire dampers vertical or horizontal mount

Advertisement

Item
1
FD150X fire damper with SSC option
2
Steel stud wall (see UL Fire Resistance Directory for specifc
details)
3
Steel stud frame around opening in wall
4
Duct connection (see section 6)
5
Wallboard (see UL Fire Resistance Directory for specific
details)
6
Fasteners (see UL Fire Resistance Directory and Section 5)

Damper maintenance

Dampers shall be maintained, cycled, and tested in intervals as stated in the latest editions of NFPA 90A, 92A, and UL
864 unless local codes require more frequent inspections.
Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use
mild detergents or solvents. If lubrication is desired, do not use oil-based lubricants or any other lubricants that attract
contaminant's such as dust.
Damper trouble Shooting
The following is a cause and correction list for common concerns with the dampers.
Symptom
Damper does not fully open and/or fully close
Link separated
Description
Frame is 'racked' causing blades to bind on jamb
Screws in damper linkage
Contaminant's on damper
Heat
Possible Cause
Corrective Action
Adjust frame such that it is square and plumb
Locate screws and remove
Clean with a non-oil based solvent
(see Damper Maintenance)
Replace link
Copyright © 2008 Greenheck Fan Corporation
453946 FD/DFD 150X series R12 December 2008