ABB ZMT Zirconia Manual page 8

Oxygen analyzer systems
Table of Contents

Advertisement

SUNSTAR传感与控制 http://www.sensor-ic.com/ TEL:0755-83376549 FAX:0755-83376182E-MAIL: szss20@163.com
SPECIFICATION
Temperature Range:
600° to 1000°C (1112° to 1832°F) NiCr/NiAl thermocouple
BS4937 Pt. 4 Type K.
600° to 1250°C (1112° to 2282°F)
Pt/Pt 13% Rh thermocouple BS4937 Pt. 2 Type R
Measuring Range
Response Rate:
Estimated to be 0.1 seconds.
Reference Gas:
Clean oil-free air. Flow rate 500 to
1000ml/min (0.22gal/min).
Protective Sheath:
Aluminous porcelain or Incoloy 800.
Identification Table for ZGP2
Insertion
Code Digits
Length
1,2,3,4 -
6
ZGP2 Zirconia
1
600mm
Oxygen Probe
(24in)
2
1000mm
(39in)
9
Special
Overall Dimensions ZGP2 Probe.
SUNSTAR自动化 http://www.sensor-ic.com/ TEL: 0755-83376489 FAX:0755-83376182 E-MAIL: szss20@163.com
SS ZMT
Thermocouple
7
1
Pt/Pt13% Rh BS4937 Part 2 Type R
2
NiCr/NiAl BS4937 Part 4 Type K
9
Special
AN-84
Mounting:
Vertical or horizontal, 42mm (1.65in) hole size.
Connecting Cables:
2-core copper, overall screened for probe output. 2-core
compensating cable to suit thermocouple fitted (NiCr/NiAl
or Pt/Pt 13% Rh).
Thermocouple:
Pt/Pt 13% Rh – Pt. 2 BS4937 Type R.
NiCr/NiAl – Pt. 4 BS4937 Type K.
Insertion Length:
556mm (21.9in) or 953mm (37.5in).
Weight:
2.5kg (5.5lb) nett. [600mm (24in) probe]
2.8kg (6.16lb) nett. [1000mm (39in) probe].
Sheath
8
1
Aluminous Porcelain
(Standard)
Incoloy 800
2
Special
3
Mounting
Connector Head
9
10
1
Flange 0
Standard
1
Twin Gland
Type C95 Head

Advertisement

Table of Contents
loading

Table of Contents