Time Overcurrent Unit - GE IBCG51M*Y1A Series Instruction Manual

Ground directional overcurrent relays
Hide thumbs Also See for IBCG51M*Y1A Series:
Table of Contents

Advertisement

GEK-49822
MOUNTING
The relay should be mounted on a vertical surface.
The outline and panel drilling
diagram is shown in Figure 26.
CONNECTIONS
The internal connection diagrams for the various relays are shown in Figures 5 to 9.
Typical external wiring diagrams are shown by Figures 10, 11 and 12.
Unless mounted on a
steel
panel
which adequately grounds the relay case,
it
is
recomended
that the case
be grounded
through a mounting stud or
screw with
a
conductor not less than 1/12 B&S gage copper wire or its equivalent.
INSPECTION
At the time of installation, the relay should be inspected for tarnished contacts,
loose
screws,
or
other
imperfections.
If any trouble
is
found,
it
should
be
corrected in the manner described in the section on SERVICING.
CAUTION
Every
circuit
in
the
drawout
case
has
an
auxiliary
brush.
It
is
especially important on current circuits and other circuits with shorting
bars that the auxiliary brush be bent high enough to engage the connecting
plug or
test plug before
the main
brushes do.
This
will
prevent CT
secondary circuits from being opened.
Refer to
Figure 21.
OPERATION
Before the relay is put into service, it should be given a check to determine that
factory adjustments have not been disturbed.
The time dial will be set at 0 before
the relay leaves the factory.
If the setting has not been changed,
it will
be
necessary
to
change
this
setting
in
order
to
open
the
time
overcurrent
unit
contacts.
The following tests are suggested:
TARGET AND SEAL-IN UNIT
1.
Make sure that the tap screw is in the desired tap.
2.
Perform pickup and dropout tests as outlined in the ACCEPTANCE TEST section.
TIME OVERCURRENT UNIT
1.
Set tap screw on desired tap.
Using the test circuit in
Figure 22, apply
approximately twice tap value current until
the contacts just close.
Reduce
the current until
the light in series with the contacts begins to
flicker.
This value of current should be within 5% of tap value.
2.
Check the operating time at some multiple of tap value.
This multiple of tap
value may be 5 times tap rating or the maximum fault current for which the
relay must coordinate.
The value used is left to the discretion of the user.
Use the test circuit shown in Figure 23.
18

Advertisement

Table of Contents
loading

Table of Contents