Time-Overcurrent - GE IAC51V Instructions Manual

Time overcurrent relay
Table of Contents

Advertisement

TIME-OVERCURRENT

Type
Circuits
IAC51A(-)A
IAC51B(-) A
IAC51R(-) A
IAC52A(-) A
IAC52B(-) A
The Type lAC relays comprise a group of relays
that are employed to protect against overcurrent on
single-phase and polyphase circuits.
relays in this lAC group are identified by model
numbers, and the relays differ in the number of
circuits they close, the length of time delay and
features that are determined by the characteristics
of the protected circuit.
These relays consist of an induction unit or an
induction unit with an instantaneous unit which
INTRODUCTION
The induction unit is the basic unit in all lAC
relays.
Fig.
shows the induction unit mounted in
1
the cradle.
These units are of the induction-disk
construction type. The disk is actuated by a current
operating coil on a laminated U-magnet. The disk
shaft carries the moving contact which completes
the alarm or trip circuit when it touches the station­
ary contact or contacts. The disk shaft is restrained
by a spiral spring to give the proper contact-closing
current and its motion is retarded by a permanent
magnet acting on the disk to give the correct time
delay.
There is a seal-in unit mounted on the front
to the left of the shaft.
series and its contacts in parallel with the main
contacts such that when the main contacts close the
seal-in unit picks up and seals in.
seal-in unit picks up, it raises a target into view
by
which latches up and remains exposed until released
pressing a button beneath the lower left corner
of the cover.
These
every possible
instructions do not p urport to cover all details or variations in equipment nor to provide for
t
contingency to be met in connection with installation, operation or maintenance.
the p
r
h
s
furt!JGr informa
ion be desired or should particular problems arise which are not covered sufficiently for
u
c
a
e
'
s
r
purposes, the matter should be referred to the General Electric Company.
To the extent
but
sue:!:
ss
r
n
required
no
a
u
a
e
c
TYPE lAC
INTRODUCTION
Contact
Instantaneous
Unit
One
Na
One
Yes
One
Yes
Two
No
Two
Yes
The various
INDUCTION
This unit has its coil in
When the
is
with
e
p
to local codes and ordinances
the prod ucts described herein meet applicable ANSI, IEF:E and NEMA standards;
ect
given
r
s
RELAYS
AC Trip
Induction
Unit
Unit
One
No
One
No
One
Yes
One
No
One
No
permits instantaneous tripping for extremely high
currents, or an induction unit with an a-c tripping
unit for use where d-e power is unavailable or a-c
tripping is preferred.
relays are composed of various combinations of the
above - that is, the induction unit, the instantaneous
unit and the a-c tripping unit - they are for con­
venience, described separately in the following text.
The above table indicates the units comprising each
type and also lists the internal connections and out­
line and panel drilling diagrams.
UNIT
APPLICATION
The induction unit is the main unit in all lAC
relays, supplying the inverse time delay character­
istics of the relay and sounding an alarm or tripping
the breakers for overload currents which cause it
to close its contacts.
OPERATING
The induction unit may have one or two circuit­
closing contacts which close as the current increases
to the pick-up value as set on the tap block. The
time delay in closing the contacts is determined by
the setting of the time dial (Fig. 1). The time-current
characteristics are shown in Fig.
The induction element is designed to use any
one of three operating coils, each having a different
combination of taps as follows:
and
amperes;
16
1.5, 2.0, 2.5, 3.0, 4.0, 5.0
amperes;
0.5,
0.6, 0.8, 1.0, 1.2, 1.5
peres.
Outline &
Internal
Panel Drilling
Connection
Fig.
Fig.
18
Fig.
Fig.
18
Fig.
Fig.
18
Fig.
Fig. 18
Fig.
Fig.
18
Since practically all lAC
CHARACTERISTICS
2.
RATINGS
4, 5; 6, 8, 10, 12
and
because they vary greatly.
11
12
13
14
15
and
6.0
am­
2.0
Should
3

Advertisement

Table of Contents
loading

Table of Contents