6.3 DC Side Connection

For Omniksol-10k-TL3 and Omniksol-13k-TL3, there are two MPP Trackers, and the DC
characteristics of them are illustrated as the following table.
Inverter Type
Omniksol-10k-TL3
Omniksol-13k-TL3
In order to reduce the line loss of DC side (no more than 1% of Pin), Omnik suggest that
the length of DC cable for each cable section should not exceed the limit below.
Omniksol-10k-TL3
Omniksol-13k-TL3
24
DANGER
DANGER to life due to potential fire or electricity shock.
NEVER connect or disconnect the connectors under load.
DANGER
NEVER connect the ground lead of PV module to
the inverter.
MPP Tracker
2
NOTICE
While installing Omniksol-13k-TL3, Separate the PV
modules evenly and connect them into 3 pairs of DC
connectors.
While installing Omniksol-10k-TL3, DO NOT CONNECT TO
THE SECOND PAIR OF DC CONNECTOR. Separate the PV
modules evenly and connect them into the first and third DC
connectors.
Model
Max.
Max.
DC Power
DC Voltage
10500W
1000V
13500W
Length of cable
2
2.5 mm
100m
90m
Max.
DC Current
10A / 10A
20A / 10A
2
4 mm
160m
144m