Electromagnetic Compatibility; Outputs; Fuses; Electrical Safety - Cooper Security EXP-PSU Installation Manual

Smart power supply
Table of Contents

Advertisement

To meet Security Grade 2 the control unit
can be fitted with a plug-on communicator,
for example the i-sd02.
The table below shows the current
consumption of the EXP-PSU itself and each
device that can be fitted to it.
EXP-PSU power
requirement:
Keypad power
requirement:
Wired Expander
requirement
Radio Expander
requirement
Battery charging
requirement:
Plug-by
Communicator pins
require:
10 FSL zones
5 CCL zones
12V Bus output
voltage range :
Aux 1 & 2 12V
output voltage
range:
Max p-to-p ripple
voltage:
Standby Battery:
„Low battery‟ fault
at:
Aux power output
fault at:
Deep discharge
protection at:
Standby time:
Electromagnetic
Compatibility
Immunity
Conforms to EN50130-4.
Emissions
Conforms to EN61000-6-3.
Page 12
50mA quiescent.
100mA max
30mA (backlight off)
45mA (backlight on)
65mA (backlight on)
60mA in alarm
20mA max quiescent.
300mA in alarm if
sounder connected.
40mA max quiescent
320mA in alarm if
sounder connected.
750mA per battery
(recharge within 24
hrs)
5mA each when
active.
5mA
7mA
10±0.5V to 13.8V
10±0.5V to 13.8V
0.5V
12V, 17Ah sealed
lead acid, 2 off (not
supplied).
< 12V
< 9V
10±0.5V
See "Power
Availabillity" on page
3.

Outputs

O/P 1 - 4
Open collector transistor,
+12VDC when inactive, 0V
when active. 500mA max.
Plug-by O/P
Open collector transistor
1-16
+12VDC when inactive, 0V
when active, 50mA max.
LS
Min impedance 16 Ohm per
(loudspeaker)
output, current
consumption = 280mA in
alarm.

Fuses

The EXP-PSU has a replaceable T500mA
mains fuse.
The Aux 1 and Aux 2 outputs are protected
by separate F-1A 20mm fuse.

Electrical Safety

Conforms to EN60950-1.

Compliance Statements

The EXP-PSU is a type B ACE (as defined in
EN50131-3 clause 8.7).
The EXP-PSU is compliant with EN50130-5
environmental class II.
The EXP-PSU is suitable for use in systems
designed to comply with PD 6662: 2004 at
grade 3.
When installed correctly the EXP-PSU is
capable of compliance with EN50131 at
Grade 3.
If the installer selects a non-compliant
configuration then they must remove or
adjust compliance labelling

Compatible Equipment

i-on160EX
160 zone expandable
control panel
i-on30EX
(available end of 2011)
30 zone expandable
control panel
i-rc01
Relay Card
KEY-ENG
Engineering keypad.
xcelw
Wired PIR
xcelwpt
Pet tolerant wired PIR
EXP-PSU

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents