Jaguar Model J-390
JAGUAR J-390 NON - DIRECT VENT, UTILIZING AN EXISTING
All joints must be liquid and pressure tight. Use 4" dia. PVC/CPVC schedule 40 pipe or U/L listed single wall 4" dia.
Figure 9. Jaguar J-390 - non-direct vent, utilizing an existing chimney as a chase.
* AL 29-4C IS A REGISTERED TRADEMARK OF ALLEGHENY LUDLUM CORP.
CHIMNEY AS A CHASE
AL29-4C S.S.*. venting materials (See page 7).
*
ALTERNATE VERTICAL TERMINATION
45°ELBOW
*
RAIN CAP TERMINATION MAY BE USED
SLOPE UP 1/4 IN.
PER FOOT MIN.
90°ELBOW
AIR INTAKE
(DO NOT BLOCK)
90°TERMINATION
ELBOW WITH SCREEN
10 FT. MIN
CHIMNEY
TOP PLATE
VENT TERMINATION
TEE WITH SCREEN
1 FT. MIN
4 INCH DIA. PVC/CPVC
PIPE OR STAINLESS STEEL
VENTING MATERIAL FOR
VENT
SEAL CHIMNEY OPENING
WITH MORTAR OR COVER PLATE
4 INCH DIA. PVC/CPVC
PIPE OR STAINLESS STEEL
VENTING MATERIAL FOR
VENT