5.7.1.2. Switching output ................38 5.7.1.3. Block ....................38 5.8. Humidity PI control ....................39 Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany Sensor KNX AQS/TH-UP Touch • from ETS programme version 1.0 Status: 23.10.2018 • Technical changes and errors excepted.
Page 4
5.18.1. Pushbutton for temperature control ............59 5.18.2. Pushbutton interface .................. 59 Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany Sensor KNX AQS/TH-UP Touch • from ETS programme version 1.0 Status: 23.10.2018 • Technical changes and errors excepted.
Page 5
Clarification of signs Installation, inspection, commissioning and troubleshooting of the device must only be carried out by a competent electrician. This manual is amended periodically and will be brought into line with new software releases. The change status (software version and date) can be found in the contents footer. If you have a device with a later software version, please check www.elsner-elektronik.de in the menu area "Service"...
• 2 actuating variable comparators for output of minimum, maximum or average values. Each with 5 inputs (for values received via communication objects) Sensor KNX AQS/TH-UP Touch as of software 0.1.0 • Version: 23.10.2018 • Technical changes and errors excepted.
Accuracy of the measurement) Temperature measurement 0…+50°C range Temperature resolution 0.1°C Temperature accuracy ± 0,5°C at 0…+50°C (Mind the notes on Accuracy of the measurement) Sensor KNX AQS/TH-UP Touch as of software 0.1.0 • Version: 23.10.2018 • Technical changes and errors excepted.
After unpacking the device, check it immediately for possible mechanical damage. If it has been damaged in transport, inform the supplier immediately. Sensor KNX AQS/TH-UP Touch as of software 0.1.0 • Version: 23.10.2018 • Technical changes and errors excepted.
ETS in order to ensure the specified accuracy of the sensor (offset). To ensure a correct CO measurement, the device must be installed in a windproof socket. Sensor KNX AQS/TH-UP Touch as of software 0.1.0 • Version: 23.10.2018 • Technical changes and errors excepted.
After the bus voltage has been applied, the device will enter an initialisation phase lasting a few seconds. During this phase no information can be received or sent via the bus. Sensor KNX AQS/TH-UP Touch as of software 0.1.0 • Version: 23.10.2018 • Technical changes and errors excepted.
Mode display with scale display and range. Shows the possible adjustment range (as set in the ETS). The control position in the image reads "Base target value reduced". Sensor KNX AQS/TH-UP Touch as of software 0.1.0 • Version: 23.10.2018 • Technical changes and errors excepted.
ETS or be suppressed for Priority 1 operating modes. The individual operating modes can also be locked for manual selection in the ETS. Sensor KNX AQS/TH-UP Touch as of software 0.1.0 • Version: 23.10.2018 • Technical changes and errors excepted.
Page 13
2 secs. evening). The period is defined in the ETS (up to 10 hours). The time remaining in Comfort mode is displayed. Sensor KNX AQS/TH-UP Touch as of software 0.1.0 • Version: 23.10.2018 • Technical changes and errors excepted.
Ext. Reading proportion of the total reading 5% • 10% • ... • 50% • ... • 100% All of the following settings are referred to the total value. Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
For units which have already been taken into service, the last communicated threshold value can be used. Basically, Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
• on change to 1 and periodically • on change to 0 and periodically Cycle 5 s • 10 s • 30 s… • 2 h (only if sending periodically is selected) Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
Please note that the setting "After power supply restoration and pro- gramming" should not be used for the initial start-up, as the factory settings are always used until the 1st communication (setting via objects is ignored). Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
Page 29
Behaviour of the blocking object with value • 1 = Block | 0 = release • 0 = block | 1 = release Blocking object value 0 • 1 before 1st communication Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
Preserve modified set points after mode No • Yes change Setting the nominal values • separate with switching object • separate without switching object • with comfort set point as a basis Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
Minimum base setpoint (in 0.1°C) -300…800; 160 Maximum base setpoint (in 0.1°C) -300…800; 280 Reduction by up to (in 0.1°C) 0…100; 50 Increase by up to (in 0.1°C) 0…100; 50 Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
Starting cooling setpoint (in 0.1 °C) -300…800; 280 valid until 1st communication Min. object value heating/cooling -300…800; 160 (in 0.1 °C) -300…800; 280 Max. object value heating/cooling (in 0.1 °C) Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
When using the control variable for a 4/6 way valve, the following applies: 0%...100% heating = 66%...100% control variable OFF = 50% control variable 0%...100% cooling = 33%...0% control variable Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
On release, the control variable follows the rule again. When blocked, the control variable shall • not be sent • send a specific value Value (in %) 0...100 (if a value is sent) Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
Page 35
1 bit object (on/off) or an 8 bit object (on with percentage/off). Control variable is a • 1 bit object • 8 bit object Value (in %) 0...100 (for 8 bit object) Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
You should set the time appropriate to the cooling system at this point (observe manufacturer's instructions). Maximum control variable is reached 1...5 at setpoint/actual difference of (in °C) Reset time (in min.) 1...255; 30 Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
Page 37
1 bit object (on/off) or an 8 bit object (on with percentage/off). Control variable is a • 1 bit object • 8 bit object Value (in %) 0...100 (for 8 bit object) Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
Humidity threshold values Activate the required air humidity threshold values. The menus for setting the thresh- old values are displayed. Use threshold value 1/2 Yes • No Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
Use humidity control No • Yes General control Sensor KNX AQS/TH-UP Touch can be used to control one- or two-level dehumidi- fication or combined humidification/dehumidification. Type of control • One-level dehumidification • Two-level dehumidification •...
Start setpoint in % 0 … 100; 50 valid until first communication 0…100; 40 (not upon saving the setpoint value after programming) Object value limit (min.) in % 0…100; 60 Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
On release, the control variable follows the rule again. When blocked, the control variable shall • not be sent • send a specific value Value in % 0...100 (if a value is sent) Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
During initial commissioning, an offset must be defined which is valid until the first communication of a new offset. For units which have already been taken into service, the last communicated offset can be used. Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
(is only sent if periodically is selected) Blocking The switching output can be blocked using an object. Define specifications here for the behaviour of the output when blocked. Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
= 0 send 0 Switching output sends on change to 0 and periodically 5.10. Absolute humidity The absolute air humidity value is detected by the KNX AQS/TH-UP Touch and can be output to the bus. Use absolute humidity No • Yes Sending pattern •...
Parameter setting 5.11. Comfort field The Sensor KNX AQS/TH-UP Touch can send a message to the bus if the limits of the comfort field are exceeded. In this way, it is for example possible to monitor com- pliance with DIN 1946 (standard values) or even to define your own comfort field.
Threshold value setting using a communication object: Define, how the threshold value will be received from the bus. Basically, a new value can be received, or simply a command to increase or decrease. Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
None • 1 s • 2 s • 5 s • 10 s • … • 2 h (If delay can be set via objects: valid until first communication) Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
If you activate air quality control, you can use the following settings to define control type, setpoint values, and ventilation. Use control Yes • No General control The Sensor KNX AQS/TH-UP Touch can be used to control one or two-stage venti- lation. Type of control • One-stage ventilation • Two-stage ventilation Configure a block for the ventilation control using the blocking object.
Send cycle 5 s • 10 s • 30 s • ... • 5 min • … • 2 h (is only sent if "periodically" is selected) Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
Each logic output may transmit one 1 bit or two 8 bit objects. Determine what the out put should send if logic = 1 and = 0. Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
Page 55
• on change of logic+object receipt • on change of logic+object receipt and periodically Send cycle 5 s • 10 s • ... • 2 h (if sent periodically) Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
(with optional thermostat display) • Permanent thermostat Temperature controller display when using No • Yes pushbutton only possible if the pushbuttons are also set to "For temperature control") Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
Page 59
Content line 3 (small font size) • display nothing • relative humidity internal • other selection options The following table contains a list of other selection options. Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
• send 0 • send 1 • do not send message Command when releasing the pushbutton • send 0 • send 1 • do not send message Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
Page 62
Stop released after time 1 +2 no more stop Time 1 (in 0,1 s) 0 ... 50; 4 Time 2 (in 0,1 s) 0 ... 50; 20 Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.