Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 OVERVIEW Introduction ....................................... 7 EN-54 Information and Key Features............................7 Typical System Schematic................................9 Typical System Block Diagram..............................10 Power Requirements..................................11 Battery Requirements..................................12 Identifying Components.................................13...
Page 3
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 COMMISSIONING Introduction ......................................49 The Main Panel Buttons................................... 49 Getting The Main Panel Running..............................53 Getting A Repeater Running................................53 Getting A Standard Sub-panel Running............................. 54 Setting Panel Addresses And Types............................
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 OVERVIEW INTRODUCTION This document covers the installation and commissioning of a JUNO-NET fire alarm system. This document is intended for use by a competent, qualified, fire alarm installation engineer.
Page 8
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 Key Features Fully expandable system - from 1 to 96 loops 125 device addresses per loop 96 VULCAN (addressable) ultra low current base sounders per loop (32 address limit)
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 TYPICAL SYSTEM SCHEMATIC J-NET-CON MAX CURRENT PER LAMP =100mA PF E AUX 1 AUX 2 ZONE BELL 1 BELL 2 EVAC BATT...
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 TYPICAL SYSTEM BLOCK DIAGRAM GRAPHIC SOFTWARE/MODEM CONTROL PANEL 2 X SOUNDER OUTPUTS LEDs 2 X RELAY (FIRE) 1 X RELAY (FAULT) SWITCHES...
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 BATTERY REQUIREMENTS The battery AH required are calculated from the following formula Quiescent current in mA Standby time required of the panel with in hours divided by 1000.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 IDENTIFYING COMPONENTS Panel boxes for Main Panels or Repeaters JUNO-NET Panel Box for 4 to 13 Loops FIRE 550 mm JUNO-NET Panel Box for 1 to 4 Loops...
Page 14
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 IDENTIFYING COMPONENTS (cont...) Inside a 1 to 12 Loop Self-Contained Panel Box J-NET-CON MAX 3A FAST ACTING INT. SUB PANEL CON 6 F I R E FIRE BRIG.
Page 15
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 IDENTIFYING COMPONENTS (cont...) Panel box for Sub-Panels Inside a Sub-Panel Box LOOP 1 LOOP 1 LOOP 2 LOOP 2 LOOP 3 LOOP 3...
Page 16
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 IDENTIFYING COMPONENTS (cont...) J-NET-CON JUNO-NET-CONNECTOR BOARD J-NET-INT- J-NET-LPCON JUNO NET INTERFACE FOR JUNO-NET RS485 COMMUNICATION ANALOGUE LOOP CONNECTOR J-NET- ADV-COMS J-NET-INT-FO JUNO-NET COMMUNICATION...
Page 17
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 IDENTIFYING COMPONENTS (cont...) J-NET-SP JUNO-NET-SUB-PANEL BOARD 1-LC or 3-LC 1 LOOP CARD or 3 LOOP CARD globalfire.pt...
Page 18
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 IDENTIFYING COMPONENTS (cont...) Juno Net - Motherboard (back view) J-NET-QUART QUAD UART QUAD UART SIM CARD CONNECTOR STANDOFFS (4) FOR LOOPCARD LOOPCARD...
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 RECOMMENDED CABLES Analogue Loops, Conventional Sounders and Data Loops The JUNO-NET can be installed as either a self-contained or a distributed system. The self contained system does not require external data loop connections.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 DEFINITIONS Analogue Loop The physical link, usually fireproof 2 conductor shielded wiring cable, forming a ring of interconnection between sensors and the detection panel.
Page 21
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 NVRAM Non-volatile Random Access Memory. Any information stored in this memory will not be cleared when power is removed from the system. The system has an internal battery for the NVRAM.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 INSTALLATION INTRODUCTION This section covers the physical installation of the system. It primarily focuses on the parts that are required and how they should be connected together.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 Integrated Sub-panels A Main Panel may have an Integrated Sub-panel. To enable the Integrated Sub-panel a Loopcard must be fitted to the Main Panel PCB.
Page 24
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 J-NET-CON + - + - + - + - PF E SF AUX 1 AUX 2 ZONE BATT BELL 1 BELL 2...
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 REPEATERS Repeaters are installed in a similar manner to the Main Panel. Mini Rep repeaters are supplied by an external 24Vdc, normally from the control panel.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 STANDARD SUB-PANELS Standard Sub-panels need 28.5V DC to operate. This should be supplied from the Power Supply Unit found inside the box.
Page 27
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 If the system is distributed, the communication between the main panel and the external sub-panels or repeaters is supported by either an RS422/485 fully redundant loop, fibre-optic cable or alternatively by TCP/IP.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 DATA LOOPS Main Panel RS485 NOTE: Make all connections with the power turned off to avoid risk of permanent damage to the circuit boards.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 Data Loop Interface Configuration J-NET-RS485-INT-NEW LINKS - J1 & J2 MAIN PANEL = REPEATER / SUB-PANEL= If these interfaces are to be used at the Main Panel, all links on both the RS485 INTERFACE BOARD (J1 & J2) and FIBRE- OPTIC INTERFACE BOARD (LK1 &...
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 Standard Sub-panel RS485 If more than one Sub-panel is mounted within a single enclosure, only one RS485 INTERFACE BOARD or FIBRE-OPTIC INTERFACE BOARD needs to be used. The Standard Sub-panels will be interconnected via a TTL bus using a cable form in a daisy-chain from CN4 in the first Sub-panel to CN3 in the next and on to CN3 on the RS485 INTERFACE BOARD or CON1 on the FIBRE-OPTIC INTERFACE BOARD.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 RS485 External Connection The 4 wire external RS485 connections should be made as below: Main Panel First Sub-panel or Repeater LOOP OUT...
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 Connection Schematic for Self-Contained Panels J-NET-CON J-NET-SP with LOOP-CARD + - + - + - + - PF E SF AUX 1...
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 Connection Schematic: Main Panel to External Sub-Panel(s) J-NET-CON INT. SUB PANEL F I R E CON 6 F I R E A L A R M S Y S FIRE BRIG.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 Main Panel Fibre Optic Use a single FIBRE OPTIC INTERFACE BOARD instead of the RS485 INTERFACE BOARD. STF2 and STF4 on one side of the PCB can be considered the IN connection.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 Fibre Optic External Connection The dual fibre external fibre optic connections should be made as below: Main Panel First Sub-panel or Repeater...
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 ANALOGUE LOOPS The Analogue Loops provide the connection to all the analogue addressable devices and loop powered sounders. Unless the loop is completed the panel will not be able to monitor its integrity (open and short circuit monitoring).
Page 41
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 Wire each loop as shown. Unused loops DEVICES must have links left in position, otherwise the panel will indicate a fault. J-NET-LPCON...
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 CONVENTIONAL SOUNDERS Conventional Sounders is the term used to describe conventional alarm sounders (or bells) connected directly to a Main Panel, Repeater or Sub-panel.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 AUXILIARY FIRE RELAYS (2) AND FAULT RELAY (1) Two auxiliary fire relay outputs are provided on the J-NET-CON. These outputs are activated when a fire is detected (unless specifically inhibited).
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 FIRE BRIGADE TRANSMISSION Connection is via the extension socket on the J-NET-CON. Only the Main Panel has a Fire Brigade Transmission output even though a connector is present in Repeaters.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 PRINTER (OPTIONAL) The printer (optional) is supplied fitted to the main panel. It is only necessary to remove the elastic band and label from the printer paper.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 MAIN PANEL BATTERIES It is recommended that the batteries are fitted at the end of commissioning the system otherwise it can be difficult to remove the power quickly if there is a problem.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 SUB-PANEL BATTERIES Make sure that those sub-panels that DO NOT have batteries connected DO have the resistor fitted across the battery connection terminals. The resistor prevents the panel reporting a battery fault.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 ODYSSEY - WINDOWS™ BASED PC GRAPHICS SOFTWARE OUTPUT A PC running this Graphics Management Software can be connected to the panel via either an RS232, RS485, Fibre-Optic or TCP/IP data link.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 COMMISSIONING INTRODUCTION Commissioning involves checking that all connections have been made properly and that all hardware is functioning correctly. This means the system must first be installed in accordance with the previous section of this manual.
Page 50
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 INTERNAL BUZZER SILENCE The occurrence of any new fire or fault condition will initiate the operation of the internal buzzer. By pressing this switch, the operation of the buzzer will be stopped until a new fire or fault appears on the system.
Page 51
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 DELAYS ACTIVE Pressing this button will activate any pre-programmed delays. The yellow LED associated with this button and the general disablements led will both be lit. A second press of this button will de-activate the delays and the led.
Page 52
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 USER & INSTALLER ACCESS CODES To enter both codes use the arrow keys Enter/OK and when finished press Enter/OK User Access Code, press...
LCD display as well as the LED indicator status from the main panel will replicate itself on the repeater. Press the SYSTEM RESET switch and you should see on the LCD display the message "JUNO NET" as well as the software version number, followed by the word, "INITIALIZING".
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 GETTING A STANDARD SUB-PANEL RUNNING If the Standard Sub-panel is fitted within the Main Panel or Repeater box and wired up correctly then the green COMMS OK LED should be either illuminated solidly or flashing when power is applied to the Main Panel or Repeater.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 SETTING PANEL ADDRESSES AND TYPES Each Repeater and Sub-panel needs a unique address. Each Repeater and Sub-panel also needs the detector type set.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 Standard Sub-panels The Standard Sub-panel addresses and detector types are set using the DIP switches on the Sub-panel. Each Sub-panel has an 6 way DIP switch. The first 5 switches set the panel number.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 GETTING INTO PROGRAMMING MODE When the Main Panel is powered up it will be necessary to enter the panel programming mode. Familiarize yourself with this section before proceeding to the next section in the manual and powering up the panel.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 Connecting A PS2 PC Keyboard To The Main Panel QUAD UART SIM CARD CONNECTOR STANDOFFS (4) FOR LOOPCARD LOOPCARD HEADER DISPLAY LOOPCARD HEADER...
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 The IR Keypad is typically the most convenient method to program the system. The sensor for the IR Keypad is just below the SOUND ALARMS button on the Main Panel and on a Repeater.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 Logging In To enter programming mode you need to log in. The Main Panel must be powered up and must have initialized itself i.e. NOT be showing the ‘INITIALIZING’ message.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 GETTING THE SYSTEM RUNNING Ensure all Sub-panels and Repeaters have unique addresses. Ensure all connectors are firmly in place. Ensure that all connections are tight, with no stray strands of wire.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 Learning Which Devices Are Fitted Enter programming mode. If site specific data has NOT been pre-programmed then select function 8-3-1 Clear Customer Flash Memory and clear the customer flash.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 Sounder Audibility Check If the building is unoccupied then press SOUND ALARMS. All sounders should operate until the button is pressed again.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 Analogue Loop Monitoring Check that a short circuit or open circuit is detected on every Analogue Loop. Open Circuit Test Disconnect either the + or the - OUT connection for each Analogue Loop in turn. The connections will be found on the ANALOGUE LOOP CONNECTION BOARD in Main Panels and Repeaters or directly on Standard Sub-panels.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 Conventional Sounder Monitoring Main Panels and Repeaters with Integrated Sub-panels have two Conventional Sounder circuits. Standard Sub-panels have two Conventional Sounder circuits.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 Detector Tests If the devices have been assigned to Zones (on a pre-programmed SIM CARD or via the programming menus) then it is possible to test the detectors with limited or no sounder operation.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 WRAPPING UP INSTALLATION AND COMMISSIONING At this stage you may program the more advanced features of the system. The basic minimum usually involves assigning text labels to the device and Zones.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 Battery Fault Message Test This test should be performed for each set of batteries. Test only the actual battery connections. BLACK BATT...
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 Power Failure Test Carry out this test to check that the battery system works correctly when mains power fails. Switch off the mains supply to the panel.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 MASTER RESET A Master Reset is not accessed through the programming menus. It occurs automatically when the Main Panel power is cycled (both primary and secondary supplies removed and reconnected). It also occurs when the PCB mounted push button fitted on the rear of the Main Panel main PCB is pressed.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 ADVANCED FUNCTIONALITY There are a number of programming functions that allow you to configure your system so that it operates exactly as you require.
Page 72
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 6 Device Set-up 6-1 General 6-1-1 Disable Loops 6-1-2 Device Disable 6-1-3 Set Selective Disablement 6-1-4 Set Device Reporting Details 6-1-5 Set Immediate Evacuate for Device...
Page 73
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 8 General 8-1 Time/Date & Timers 8-1-1 Set Date & Time 8-1-2 Define Day & Night 8-1-3 Delays Off at Night 8-1-4 Configure Evacuate Timer...
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 Keys To Use Within Functions Most functions use some or all of the following keys: 0-9 are used to input numbers are used to browse through items...
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 Specific Functions Review Historic Log All the functions associated with reviewing or printing events and settings. Display Historic Log The panel logs all events in an internal event log. It can store a rolling 2000 entries. When it is full the latest entry is added and the oldest entry discarded.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 Text Descriptions & Names All the functions associated with textual labels or names. Enter Device Text First select the device then input the text label for that specific device. If the IR keypad is being used, to enter letters rather than numbers press the SHIFT key momentarily.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 Zones - Disable & Assign All the functions associated with managing Zones. Disable Zones Allows you to disable or enable Zones. All devices in disabled Zones will cease to operate with the exception of the (audible) output from loop sounders.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 Zone Fire Brigade Delay Set-up Allows the Fire Brigade signal delay to be turned on or off for a specific Zone. NOTE: the Fire Brigade Delay Mode (function 8-1-6) must be set to ZONAL for this function to have an effect.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 Sounders - Disable & Assign Sounder Configuration Allows selection of PRESET or PROGRAMMED sounder operation. Selecting PRESET (the default) will result in all sounders being operated; any Sounder Group settings will be ignored.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 Disable Sounders Allows specific sounders to be disabled or Enabled. Disabled sounders will not be operated regardless of Sounder Configuration, Sounder Groups and evacuate requests.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 Sounder Delay Set-up Allows the sounder delay to be set-up: The sounder delay can be set to GLOBAL MODE, ZONAL MODE or DISABLED.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 Input/Output - Disable & Assign Input/Output Analogue Loop device management. Configure I/O Groups Allows an I/O Group to be established. The I/O Group can then be used for fire or fault reporting. 512 I/O Groups can be defined.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 Inhibit I/O for Device Allows a device to be set so that it does not operate certain I/O Groups. The options are:...
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 Device Set-up Allows specific settings to be selected for individual Analogue Loop devices. General Settings common to all types of Analogue Loop devices.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 6-1-5 Set Immediate Evacuate for Device When a detector set to immediate evacuate reports a fire all Sounder Group settings are ignored. All sounders are operated immediately as if the Sounder Configuration was set to PRESET and all delays are ignored.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 6-1-9 Configure Timed Sensitivity Allows the sensitivity to be set for day and night. Settings are : HIGH Detector alarm threshold of 45)
General Guidelines SAM's can only be used in conjunction with: a) Juno Net panel. b) Juno Net Repeater panel with Integrated Sub-panel c) Junior 1-loop panel. d) Sub panel (incorporating SIMM module & socket). NOTE: Verify panel software version by looking at number on the sticker placed on the SIMM card.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 CAUTION Verify that there are no faults or fire conditions in the loop or system. Clear all fault and fire conditions first.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 NOTE: A programmed SAM that has been RESET and re-enters the fire condition will force the panel to activate the sounders without a new address being programmed. The panel will activate the bells/ sounders every time there is a new fire condition, regardless of it being caused by a new address being attributed or not.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 SAM's will respond with the following fixed analogue values, depending on their state: NORMAL FAULT ACTIVATED-FIRE Smoke Heat Call Point UPON COMPLETION OF THE INSTALLATION AND COMMISSIONING STAGES A FIRE...
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 Monitor Device Counts & Test Device Count, Type & Value Use this function to check that all Sub-panels are present and that all devices are present.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 Test Zones Select the Zones you wish to put into test mode. Exit programming mode, but DO NOT press SYSTEM RESET as this clears all test modes.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 8-1-2 Define Day & Night Defines sunrise and sunset for the system. The system considers a day to start at sunrise. So when different detector sensitivities are set for different days (function 6-1-8) the new day will start at the sunrise time defined here.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 NOTE: disabled sounders are never activated by the evacuate timer. 8-1-5 Device Starts Evacuate Timer Allows you to specify specific detectors that will start the Evacuate Timer.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 8-2-2 Call Points to Evacuate Enables or disables a system wide setting that a report of fire from a call-point automatically starts evacuation.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 8-3-2 Clear Non-Volatile RAM Clearing the NVRAM on a panel with an Integrated Sub-panel will also clear the NVRAM for the Integrated Sub-panel.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 Other Features These are programming functions that do not fall into any other category. 8-4-1 Active/Installation Mode An essential function. The system should always be left in ACTIVE mode, unless the system is being installed and debugged.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 The Main Panel Before entering the UPLOAD/DOWNLOAD Function, The RS-485 and Fibre Optics data Loop connections to Sub-panels and Repeaters on the J-NET-CON board should be removed (CON 5). This task should always be carried out with no power applied to the system.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 8-4-4 Set User Access Code Use this function to set the User Access Code. This access code only permits access to the functions defined by 8-4-5 Set User Functions.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 Remote Access and Monitoring Remote access and monitoring can be performed via RS485, RS232 or a modem (RS232). Remote access and monitoring via RS485 and RS232 is performed using the Odyssey PC software whilst the Telemon PC software is used in conjunction with a modem.
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 How The Dial Out Works From dialing the panel allows 60 seconds for connection to the PC Graphics Software or the attempt fails.
JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 TECHNICAL SPECIFICATIONS Please note that these specifications apply to the stand-alone juno Net Analogue Addressable panel, 1 or 3 loops models, equipped with a 2.4 Amp power supply. Weight: Empty: 5.1 Kg...
Manufacturers of Fire Detection Equipment JUNO NET - NETWORKABLE ADRESSABLE PANEL INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013 Power Budget Quiescent Condition: a - 100 mA internal circuits b - 460 mA auxiliary supply outputs c - 825 mA for analogue loop power d - 1 Amp for battery charger.
EN61000-3-2,3 EN54 Pt 2 and Pt 4. We, Global Fire Equipment Lda. hereby declare, for the effects of the requirements laid down with EN-54 Pt4 paragraph 6.1, that the power supply equipment included in our analogue addressable fire alarm panel named JUNO-NET, has been designed in accordance with a quality management system which incorporates a set of rules for the design of all elements of the p.s.e., and that its components have been selected for the intended purpose , and expected to operate within their...