ASHRAE Standard 135 is the responsibility of BACnet International (BI). Shipments BTL is a registered trademark of BI. Models GTC116 and GTE116 Models GTC116 and GTM116 Part Number: 930-0000 EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com...
Page 2
Visit EBTRON.com to view and/or download the most recent versions of this and other documents. All rights reserved. EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com...
Connectivity is not available while the Data Logger is connected. Data Logger - Model GT Airflow, temperature and timestamp are recorded on the attached USB thumb-drive. EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com...
GTx116 TRANSMITTER INSTALLATION The GTx116 transmitter is designed for use in an environment between -20° F to 120° F (-28.8° C to 48.8° C) where it will not be exposed to rain or snow. The transmitter should be mounted upright in a field accessible location. The enclosure (Figure 4) is designed to accept 1/2 in.
Figure 5. GTx116 Power Connections Multiple GTx116 transmitters wired to a single transformer must be wired “in-phase” (L1 to L1, L2 to L2). EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com...
After mounting the sensor probes and transmitter, connect one or more sensor probe cable plugs to the circular recep- tacles located at the bottom of the GTx116 transmitter enclosure. Probes are “Plug and Play” and do not have to be con- nected to a specific receptacle on the transmitter (unless traverse data is desired - see note below).
Figure 8). In addition, when the Analog Output is concurrently used with the RS-485 Output, the Common connection for both Analog and RS-485 Outputs must be at the same potential. EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com...
Changing the System of Units - IP units or SI Units The GTx116 transmitter is provided with the system of units set to I-P. To change to S.I., simultaneously press and release the “ENT” and “ESC” buttons during normal operation. “IP/SI UNITS” will be indicated on the LCD display. Refer to Appendix B SYSTEM OF UNITS MENU for details on the System of Units menu.
Factory Default Menu Settings for GP1 Sensor Probes The GTx116 transmitter is “plug and play” and does not require setup unless a network option is selected that requires configuration. Table 4 shows the factory default settings for all compatible sensor probes.
(in FPM) by the free area of the air flow probe installation location. Refer also to Table 6 for a complete listing of conversions for each of the analog outputs of the GTx116. The AO1 full scale analog output (OUT- PUT1 ) value is determined by the AO1 FS setting within the SETUP menu.
Airflow and temperature of individual sensors can be displayed on the local LCD display by entering the Diagnostic Menu. Simultaneously depress the up ↑ and down ↓ arrows to enter the GTx116 SETUP menu, and then navigate to the Diagnostic submenu.
TROUBLE ! (Refer to DIAGNOSTIC menu to obtain a submenu. (Trouble Alarm) brief description of the error and any other alarms). EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com...
OUT1 and OUT2 tests are independently accessed, and the output will maintain the % selected until the “ESC” button is pressed and normal operation resumes. EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com...
Communications options can be reset to factory default values (asterisk) * values using the GTC116 RESET NET menu option as shown in Appendix B. EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com...
To change this value, navigate to the *GATE=10.0.0... menu item as shown in Appendix B, and set new segment values as previously described. (See note above regarding *DHCP=OFF). EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com...
Tables 8 and 9 list the specific values provided for BACnet and Modbus communication protocols. TCP/IP Table 7. GTM116 TCP/IP Example http://10.0.0.100 GTM Data (or your custom IP address) EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com...
30076-30077 float Sq.Ft. Area 0 to 100 0: high word first; 300202 word Float word order 1: low word first EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com...
The node object is used for overhead activities on the LonWorks bus. This object is of little interest to the end user. The gtx116 function block contains a set of network variables and configuration properties that allow the end user to monitor various parameters related to airflow, pressure, and temperature that are generated by the transmitter.
This configuration property sets the duct area to be used in flow calculations. Note that this variable must be set to a non-zero value to get flow information. EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com...
This configuration property sets the minimum change in pressure that will cause an update for pressure to the network. When this change is met both nvoPrecisePres and nvoFloatPres will be updated on the network. EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com...
Refer to the preceding paragraphs for description and configuration of the Delta values. EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com...
EB-Link card and/or the transmitter. The EB-Link card must be installed on the GTx116 main board in order to access sensor data with your PDA. If the EB- Link card is ordered separately from the transmitter, it should be installed after the transmitter is mounted.
If traverse data is desired, ensure that probes are installed using the mounting convention specified in Figure 10. Proper instal- lation simplifies sensor location decoding during data analysis. EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com...
EBTRON airflow station is installed. The inherent accuracy of field measurement will not be better than ±5% of reading and can often exceed ±10%. Do not adjust the output of the GTx116 if the difference between the transmitter and the field measurement is less than 10%.
CFM then values need to be divided by duct area before entering in transmitter. 13. Press the “ESC” button until you return to the normal operating mode. Field adjustment is complete. EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com...
EBTRON’s TERMS AND CONDITIONS OF SALE. Defective equipment shall be shipped back to EBTRON, freight pre-paid, for analysis. EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com...
24VAC SOURCE, WIRE 24 VAC POWER IN-PHASE TO THE SAME TERMINALS ON ALL TRANSMITTERS (e.g.: L1 to L1, L2 to L2). Figure A-1. Model GTC116 Combination Analog/RS-485 Wiring Diagram EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com...
Set whether or not TROUBLE will display on LCD during a trouble condition. LCD TRBL=ON TO PART 5 'A' TO PART 2 Figure B-2. GTx116 Setup Menu EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com...
Page 39
Sets AO2 alarm/trouble output state when no fault condition is present, expressed as HI (full scale analog output) or LO (minimum scale analog output). NO FAULT = HI TO PART 3 EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com...
Page 40
NETDI=2 Set network device instance number. EB-LINK *EB-LK INTG=300 SET EB-LK INTG? EB-LK INTG=300 EB-Link integration samples. TO PART 4 EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com...
Page 41
BACnet object or Modbus register. Alarm will only clear when alarm is not active. RESET=MANUAL TO PART 5 'B' EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com...
Page 42
Resets network settings to factory default. RESET NET=NO RESET TRBL ARE YOU SURE? RESET TRBL=YES Clears all disabled trouble settings. RESET TRBL=NO TO PART 6 EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com...
Page 43
For sensors =1 to 9, A to G (number of sensors dependant on sensor type). PROBE TYPE TYPE= P Type 'P' for 'P' probes; Type 'B' for Bleed sensors. EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com...