Installation; Selection Of The Best Location - LG ARNU363B8A4 Installation Manual

Hide thumbs Also See for ARNU363B8A4:
Table of Contents

Advertisement

Installation

Installation
Read completely, then follow step by step.

Selection of the best location

Install the air conditioner in the location that satisfies the following conditions.
• The place shall easily bear a load exceeding four times the indoor unit's weight.
• The place shall be able to inspect the unit as the figure.
• The place where the unit shall be leveled.
• The place shall allow easy water drainage.
(Suitable dimension "H" is necessary to get a slope to drain as figure.)
• The place shall easily connect with the outdoor unit.
• The place where the unit is not a ffected by an electrical noise.
• The place where air circulation in the room will be good .
• There should not be any heat source or steam near the unit.
Top view
Inspection hole
(Unit: mm)
(600 x 600)
600
Side view
(unit: mm)
• Suitable dimension "H" is necessary to get a slope
to drain as shown in the figure
Low static Duct type
B(Min)
A(Min)
Service Space
B
8
Indoor Unit
Control box
Air outlet
600
Air outlet
H=20 or more
Ceiling
A
Top view
Inspection hole
[600(23-5/8) x 600(23-5/8)]
Control box
600
(23-5/8)
Front view
CAUTION : In case that the unit is
installed near the sea, the installation
parts may be corroded by salt, The
installation parts (and the unit) should
be taken appropriate anti-corrosion
measures.
Capacity(kBtu/h)
A
L1
800
L2
800
L3
800
600
(23-5/8)
Front
20(25/32) or more
Unit:mm(inch)
Unit:mm(inch)
B
800(31-1/2)
1,000(39-3/8)
1,200(47-1/4)

Advertisement