Delayed Egress Switch Connections ........................... 20 Multiple Panel Fire Alarm Connections ..........................21 Connecting Multiple SMT Advantage 500DE Exit Panels to the Fire Alarm Control Panel........22 Sounder Connections ................................22 4 & 8 Channel Nurse Station Connections ......................... 23 LED Nurse Station Annunciator ............................
Page 3
Panel Initialization ................................24 Changing Access Code ............................... 24 Arm or Disarm Panel ................................24 PM Mode Enable/Disable ..............................24 Delayed Egress Settings ............................... 25 Delayed Egress Activation Time ............................25 No Code/ Irreversible Delayed Egress ..........................25 PM Programming Options ..............................26 Same arm and disarm times seven days a week: .........................
Page 4
SECTION 14 GENERAL PRODUCT WARRANTY ............35 1. Notices....................................35 2. Limited Warranty ................................37 3. Limitations of Liability ............................... 38 4. Governing Law and Arbitration ............................38 5. Severability ..................................39 6. Waiver ....................................39 APPENDIX A CALIFORNIA FIRE MARSHALL LISTINGS ..........40 APPENDIX B CARD ACCESS INPUT MODE ..............
SYSTEM BLOCK DIAGRAM SECTION 2 Typical Installation Wiring Diagram 2 wires from Separate central or wall mount power supply 2 wires from central or wall mount power supplied to lock under 500DE control supply 12v 1.6A 12v 1.6A Power Power Supply Supply A41010901)
SMT Advantage 500DE Exit location if a wall mount power supply is used. The SMT Advantage 500DE Exit Panel can be powered from an optional wall mount local power supply or aa central power supply may be used to power several SMT ADV 500 DE Exit Panels. The use of emergency power circuits is highly recommended.
INSTALLATION AND CONNECTIONS SECTION 3 Power Supply for Exit Panel 12VDC 8AMP POWER SUPPLY BATTERY CONN. INPUT AC VOLTAGE 8 FUSED OUTPUTS 12VDC BATTERY 12VDC BATTERY BATTERIES MUST BE WIRED IN BATTERIES MUST BE WIRED IN PARALLEL PARALLEL REFER TO THE MANUFACTURER'S Risk of shock ...
3. Run all Nurse Station and fire alarm cables. 4. Determine the location of the SMT Advantage 500DE Exit Panel and cut holes in the wallboard as needed. Mount surface mount boxes if required. The SMT Advantage 500DE Exit Panel should be mounted 48 inches from the center of the panel to the floor.
NOTE: The Nurse and Elevator relays are activated when the SMT Advantage 500DE Exit Panel is in an alarm state. The Nurse/Elevator relay will remain active until the SMT Advantage 500DE Exit Panel is reset. Mounting Boxes for Exit Panels: Flush Mount Box SCP Part #A10000210 Surface Mount Box SCP Part #401 Dimensions: 4-1/2"...
SECTION 6 SYSTEM COMPONENTS Flush Mount Box 2 hour fire rated back boxes are available upon request KNOCK OUTS MADISON CLIP VIEW WITH FLAP FOLDED FINGERS BEND FLAP DOWN THEN INSERT THE MADISON CLIP BETWEEN THE BOX AND SHEETROCK SLIDING THE CLIP ALL THE WAY TO THE END IN THIS CASE TO THE LEFT.
PM Mode of Operation The SMT Advantage 500DE Exit Panel can be programmed to unlock or disarm during certain hours of the day, it then will automatically lock and unlock at the specified times. These specific times are programmed into the panel by following the PM programming instructions provided in this Manual.
One or Two Sets of Magnetic Door Contacts Connections Normally Open Push Button (P/N A04150900) Connections NOTE: The use of release devices which provide a maintained closure are not recommended for use with SMT Advantage 500DE System. Normally open Push-Button or any other device that provides a "momentary"...
SECTION 8 INSTALLATION AND CONNECTIONS Use SCP Part #B60000429 wire to connect the Push Button to the SMT Advantage 500DE Exit Panel. When the Push Button is activated the escort delay feature is activated and the door will become disarmed for the programmed exit delay. (See programming section of this Manual (Section 10) for setting and/or changing the escort delay time.)
Connecting a single electromagnetic lock to the SMT Advantage 500DE Exit Panel Refer to the manufacturer’s instructions provided with the lock for proper mounting of the lock. Refer to Fig. 9-6 below for connection to the SMT Advantage 500DE Exit Panel. Use the SCP part #B60000440 22AWG, six-conductor wire for connections.
Refer to the manufacturer’s instructions provided with the lock for proper mounting of the lock. Refer to Fig. 9-8 for connections to the SMT Advantage 500DE Exit Panel. Use the SCP part #B60000440 22AWG, six-conductor wire for connections. All applicable electrical and life safety codes must be strictly adhered to when installing the systems. Refer to manufacturer’s instructions for details of proper delayed egress operation.
Use SCP Part #B60000438 16Awg wire for connection of the SMT Advantage 500DE Exit Panel to the fire alarm panel. Up to eight SMT Advantage 500DE Exit Panels can be connected in parallel to a normally open, dry relay contact in the fire alarm control panel.
Multiple Panel and Fire Alarm Control Panel Connections Use SCP Part # B60000438 16Awg wire for connection of the SMT Advantage 500DE Exit Panel to the fire alarm control panel. Up to eight SMT Advantage 500DE Exit Panels can be connected in parallel to a normally open, dry relay contact in the fire alarm control panel.
401 for surface mounted applications. The A20240901 Nurse Station Annunciator requires a mounting box 449 for flush mounted applications and mounting box 448 for surface mounted applications. Secure Care Products Made with Pride in the U.S.A. Figure 8-11 Nurse Station Front View Doc No.: A05160691 REV Q ECO 12425 Date: 03/27/17...
SECTION 9 Basic Panel Operation The factory default settings for the SMT Advantage 500DE Exit Panel are as follows: armed 24 hours per day, with a reset code of *234 and an authorized entry/exit escort time of 30 seconds. If connected only to a set of door contacts, it is an access control perimeter alarm. (Section 9 of this Manual has more information on perimeter access control.) If the (4101SC) electromagnetic lock is connected to the SMT Advantage 500DE...
To disable Nuisance Silent enter *567*9876543213 holding the 3 for 5 beeps Each SMT Advantage 500DE Exit Panel controlling an electromagnetic lock has a required time period for pressure applied to a door to activate the delayed egress release feature as required by NFPA 101. Refer to the NFPA 101 Life Safety Code or your local Fire Marshall/Safety Inspector for guidance on local requirements.
SECTION 9 PROGRAMMING INSTRUCTIONS enabled, will continue with the delayed egress after the activation time is passed. No Code will stop or reset the delayed egress until the door is opened and then closed. At this time you can reset the delayed egress. No Code/ Irreversible Delayed Egress Factory Default Disabled To enable the No Code/ Irreversible delayed egress feature, follow the three listed steps without pausing for...
SECTION 9 PROGRAMMING INSTRUCTIONS Enter the programming by pressing *567 *987654321, holding the 1 until you hear one beep. Enter the current day of the week. 1 = Monday, 2 = Tuesday, 3 = Wednesday … 7 = Sunday You will hear two beeps. Enter the current time of day, in military time.
You can lock all Life Safety 101 features. This will lock the delayed egress and fire alarm settings. This feature is NON REVERSIBLE and cannot be undone by initializing the SMT Advantage 500DE Exit Panel. Make sure the Life Safety 101 features are correct and meet your local authorities requirements before locking the feature .To undo this feature the...
Verify that all wiring connections are complete and wired as shown in the diagrams in Section 7 of this manual. The SMT Advantage 500DE Exit Panel out of the box, with power supplied, should be in the armed mode and the red LED Open the door.
Testing the Escort and Anti-tailgate Features Enter the reset code into the keypad on the SMT Advantage 500DE Exit Panel. The red LED should turn off and the green LED should turn on. Open the door. No alarm condition should be activated. (This is the Escort Feature) Now close the door, the SMT Advantage 500DE Exit Panel should again be in the armed mode with the red LED on.
Testing the Door Status feature Enter the reset code into the keypad on the SMT Advantage 500DE Exit Panel, the red LED should turn off and the green LED should turn on. Open the door. No alarm condition should be activated at this point. Keep the door open for 30 or more seconds.
SECTION 13 COMPLIANCE STATEMENTS FCC Compliance Statement This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment.
Product and promptly return this Product to the place where you obtained it for a full refund. If you have any difficulty obtaining a refund, please contact Secure Care at the telephone number provided in Section 2.B below.
Page 36
Interference (RFI); physical orientation and positioning of the equipment; and sources of Electro Static Discharge (“ESD”). Secure Care cannot be responsible for the effect of these types of factors on operation of its software, parts and products. D. This Product must be installed, set-up, tested, supported, operated, maintained, repaired and used only in accordance with all manuals and instructions (including the user, installation, technical and other manuals) issued by Secure Care (the “Product Manuals”).
Secure Care to an authorized Secure Care distributor, shall conform to the specifications which accompany this product for a period of one (1) year from the date of delivery of this product by Secure Care to a common carrier, f.o.b.
(without interest) paid to Secure Care for this product. B. In no event shall Secure Care be liable to anyone for any loss of data, loss of profits or loss of use of this product or...
Page 39
General Product Warranty Statement shall not constitute or be deemed to be a waiver of such term or condition on any other occasion. No delay or failure of Secure Care to exercise any right or remedy under this General Product Warranty Statement will operate as a waiver thereof;...
This product has been approved by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing No. (Listed below) for allowable values and/or conditions for use concerning material presented in this document. All of the following CSFM Listing Certificates are available by calling Secure Care Products at 1-800-451-7917 CSFM Listing Number...
With the Card Access System connected to the SMT Advantage 500DE you can escort a resident through the locked door by swiping your access card once. If there is an alarm at the SMT Advantage 500DE then you can clear the alarm by swiping once with your access card.
Need help?
Do you have a question about the Advantage 500DE and is the answer not in the manual?
Questions and answers
i have a green flashing light on the panel