Carrier WeatherMaster 48HC07 Series Installation Instructions Manual page 43

Single package rooftop gas heat/electric cooling unit with puron (r-410a) refrigerant
Hide thumbs Also See for WeatherMaster 48HC07 Series:
Table of Contents

Advertisement

MENU
PARAMETER
MAT T CAL
OAS T CAL
OA H CAL
RA T CAL
ADVANCED
SETUP
(CONT)
RA H CAL
DA T CAL
2SP FAN DELAY
DAMPER MINIMUM POSI-
TION
DAMPER OPEN
DAMPER CLOSE
CHECKOUT
CONNECT Y1–O
CONNECT Y2–O
CONNECT AUX1-O
CONNECT EXH1
Alarms display only when they are active. The menu title "ALARMS(#)" includes the number of active alarms in parenthesis ( ). When using SYLK
bus sensors, "SYLK" will appear on the screen, and when using 20k OA temperature sensors, "SENS T" will appear on the screen
MA T SENS ERR
CO2 SENS ERR
OA SYLK T ERR
OA SYLK H ERR
RA SYLK T ERR
RA SYLK H ERR
ALARMS
DA SYLK T ERR
OA SENS T ERR
ACT ERROR
FREEZE ALARM
Table 11 — Menu Structure* (cont)
PARAMETER
PARAMETER
DEFAULT
RANGE AND
VALUE
INCREMENT
0.0°F
±2.5°F
0.0°F
±2.5°F
0% RH
±10% RH
0.0°F
±2.5°F
0% RH
±10% RH
0.0°F
±2.5°F
5 Minutes
0 to 20 minutes in 1
minute increments
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
43
NOTES
SUPPLY AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calibration temperature
sensor.
OUTSIDE AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calibration temperature
sensor.
OUTSIDE AIR HUMIDITY CALIBRATION
Allows for operator to adjust for an out of calibration humidity sensor.
RETURN AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calibration temperature
sensor.
RETURN AIR HUMIDITY CALIBRATION
Allows for operator to adjust for an out of calibration humidity sensor.
DISCHARGE AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calibration temperature
sensor.
TIME DELAY ON SECOND STAGE ECONOMIZING
When in economizing mode this is the delay for the high speed fan to try
to satisfy the call for second stage cooling before the first stage mechan-
ical cooling is enabled.
The checkout for the damper minimum position is based on the system.
See table
Position damper to the full open position.
Exhaust fan contacts enable during the DAMPER OPEN test. Make
sure you pause in the mode to allow exhaust
contacts to energize due to the delay in the system.
Positions damper to the fully closed position
Closes the Y1-O relay (Y1-O)
Closes the Y2-O relay (Y2-O)
Energizes the AUX output. If Aux setting is:
• NONE — not action taken
• ERV — 24 Vac out. Turns on or signals an ERV that the conditions are
not good for economizing but are for ERV operation.
• SYS — 24 Vac out. Issues a system alarm
Closes the power exhaust fan 2 relay (EXH1)
SUPPLY AIR TEMPERATURE SENSOR ERROR
Mixed air sensor has failed or become disconnected - check wiring then
replace sensor if the alarm continues.
CO
SENSOR ERROR
2
CO
sensor has failed, gone out of range or become disconnected -
2
check wiring then replace sensor if the alarm continues.
OUTSIDE AIR S-BUS SENSOR ERROR
Outdoor air enthalpy sensor has failed or become disconnected - check
wiring then replace sensor if the alarm continues.
RETURN AIR S-BUS SENSOR ERROR
Return air enthalpy sensor has failed or become disconnected - check
wiring then replace sensor if the alarm continues.
DISCHARGE AIR S-BUS SENSOR ERROR
Discharge air sensor has failed or become disconnected - check wiring
then replace sensor if the alarm continues.
OUTSIDE AIR TEMPERATURE SENSOR ERROR
Outdoor air temperature sensor has failed or become disconnected -
check wiring then replace if the alarm continues.
ACTUATOR ERROR
Actuator has failed or become disconnected - check for stall, over volt-
age, under voltage and actuator count. Replace actuator if damper is
movable and supply voltage is between 21.6 V and 26.4 V. Check actu-
ator count on STATUS menu.
Check if outdoor temperature is below the LOW Temp Lockout on set-
point menu. Check if Mixed air temperature on STATUS menu is below
the Lo Setpoint on Advanced menu. When conditions are back in normal
range then the alarm will go away.