SKF CMSS-ONL-2504 Quick Start Manual
SKF CMSS-ONL-2504 Quick Start Manual

SKF CMSS-ONL-2504 Quick Start Manual

Acoustic emission (ae) interface cable assembly for the skf multilog on-line system imx

Advertisement

CMSS-ONL-2504
Acoustic Emission (AE) Interface Cable Assembly for the
SKF Multilog On-line System IMx

Connections

• Blue wire: AE sensor signal / phantom power line
• Green wire: AE sensor 0 V return
• Red wire: ICP signal
• Black Wire: ICP ground
• Screen: Cable shield

Simple installation

• To install the CMSS-ONL-2504:
– Mate the connector with CMSS 786M sensor, using thread lock
(Loctite 243 recommended)
– Connect the blue wire to J1-1 (input +) of CMON 2504
– Connect the green wire to J1-2 (input –) of CMON 2504
– Connect the red wire to IMx channel terminal A [ + ]
– Connect the black wire to IMx channel terminal B [ – ]
– Connect the cable shield to IMx chassis ground bar
• Mount the CMSS 786M sensor per installation instructions
• Connect the CMON 2504 per installation instructions
Terminal A or B refers to IMx-S
Terminal + or – refers to IMx-W
The cable screen is connected to the body of the sensor and is
usually grounded by the sensor. Note that where the sensor is glued
into position, there may not be an electrical connection and the cable
screen may need to be connected to the earth strip below the DIN
rail.

Configuration

In order to configure IMx-S, IMx-T or IMx-M and SKF @ptitude
Analyst / SKF @ptitude Observer, it is necessary to position DIP
switches in the used channels as shown in figs. 1 and 2. Only change
DIP settings when the IMx unit is powered off.

DIP Settings

Terminal
position: 123456
+
A
100100
B
Fig. 1. DIP switch positions for IMx-S, IMx-T and IMx-M channels 1-8.
Terminal
DIP A Settings
N.C.
P
100100
+
A
B
Shield
S
Fig. 2. DIP switch positions for IMx-M channels 9-16.

Specifications

• Temperature range: –40 to +120 °C (–40 to +248 °F)
• Ingress protection:
– Cable to sensor IP 65
– Cable to gland IP 65
• Humidity: 10 to 90% relative
• Power supply: 11 to 30 V DC; 30 mA
• AE sensitivity: 100 to 500 kHz
• Nominal: 100 mV / aeE
• Accelerometer sensitivity: ±10% of
100 mV/g at 25 °C (77 °F)
Quick Start Guide
DIP B Settings
0010

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CMSS-ONL-2504 and is the answer not in the manual?

Questions and answers

Summary of Contents for SKF CMSS-ONL-2504

  • Page 1: Specifications

    SKF Multilog On-line System IMx Connections Configuration In order to configure IMx-S, IMx-T or IMx-M and SKF @ptitude • Blue wire: AE sensor signal / phantom power line Analyst / SKF @ptitude Observer, it is necessary to position DIP • Green wire: AE sensor 0 V return switches in the used channels as shown in figs.
  • Page 2 Every care has been taken to ensure the accuracy of the information contained in this publication but no liability can be ac- cepted for any loss or damage whether direct, indirect or consequential arising out of the use of the information contained herein. SKF re- serves the right to alter any part of this publication without prior notice.

Table of Contents