Page 3
This causes a flow deviation that increases with small valves, low settings and low differential pressures. Correction for this deviation can be made with the software TA Select or direct in TA-CBI.
Page 4
Support material Software TA Select: Makes it easy to choose the right balancing valves by taking into account the desired flow, pressure drop and flow rate. Measuring instruments Use the TA-CBI electronic instrument. It is programmed with valve characteristics for TA valves, enabling measured differential pressure to be read off directly as a flow rate.
Page 5
Diagram 1/2” - 2” Wanted: Presetting for a 1” valve at a desired flow rate of 6.7 GPM and a pressure drop of 3 ft. Solution: Draw a straight line joining 6.7 GPM and 3 ft. This gives Cv=5.9. Now draw a horizontal line from Cv=5.9. This intersects the bar for a 1”...
Page 6
Accessories Measuring point Max 250°F TA No 52 179-014 1 3/4 Measuring point, extension 2 3/8 IN (60 mm) Can be installed without draining of the system. TA No 52 179-006 Handwheel, complete TA No 52 186-003 Draining kit Can be installed during operation...