Download Print this page
TA STAD Series Manual

TA STAD Series Manual

Balancing valves

Advertisement

Quick Links

General
Draining optional
Valves with draining for 3/4" NPS hose connection.
Valves without draining have a sleeve. This sleeve can
temporarily be removed and a draining kit be fitted, which is
available as an accessory.
Technical description
Application:
Heating- and cooling systems.
Tap water systems.
Functions:
Balancing
Pre-setting
Measuring
Shut-off
Draining (optional)
Pressure class:
PN 20
Temperature:
Max. working temperature: 250°F
Min. working temperature: -4°F
STAD (NPT threads), STAS (soldering)
Balancing valves
Measuring points
The measuring points are self-sealed. Remove the cap and
insert the probe through the seal.
Material:
The valves are made of AMETAL
Seat seal: EPDM O-ring
Spindle seal: EPDM O-ring
Handwheel: Polyamide
®
AMETAL
is the dezincification resistant alloy of TA.
Marking:
Body: PN 20/150, DN and inch size.
Handwheel: Valve type and size.
5-5-12
2002.04
Certification of Registration
Number 2125 and 2125 M
Certified by SP
®
.

Advertisement

loading

Summary of Contents for TA STAD Series

  • Page 1 Seat seal: EPDM O-ring Spindle seal: EPDM O-ring Functions: Handwheel: Polyamide Balancing ® Pre-setting AMETAL is the dezincification resistant alloy of TA. Measuring Shut-off Marking: Draining (optional) Body: PN 20/150, DN and inch size. Handwheel: Valve type and size. Pressure class:...
  • Page 2 STAD: NPT threads With draining Weight TA No Size d=3/4” NPS 52 151-814 1/2” N 1/2 NPT 3.50 4.00 2.92 52 151-820 3/4” 3/4 NPT 3.81 4.00 6.61 52 151-825 1” 1 NPT 4.31 4.50 10.1 52 151-832 1 1/4”...
  • Page 3 This causes a flow deviation that increases with small valves, low settings and low differential pressures. Correction for this deviation can be made with the software TA Select or direct in TA-CBI.
  • Page 4 Support material Software TA Select: Makes it easy to choose the right balancing valves by taking into account the desired flow, pressure drop and flow rate. Measuring instruments Use the TA-CBI electronic instrument. It is programmed with valve characteristics for TA valves, enabling measured differential pressure to be read off directly as a flow rate.
  • Page 5 Diagram 1/2” - 2” Wanted: Presetting for a 1” valve at a desired flow rate of 6.7 GPM and a pressure drop of 3 ft. Solution: Draw a straight line joining 6.7 GPM and 3 ft. This gives Cv=5.9. Now draw a horizontal line from Cv=5.9. This intersects the bar for a 1”...
  • Page 6 Accessories Measuring point Max 250°F TA No 52 179-014 1 3/4 Measuring point, extension 2 3/8 IN (60 mm) Can be installed without draining of the system. TA No 52 179-006 Handwheel, complete TA No 52 186-003 Draining kit Can be installed during operation...

This manual is also suitable for: