Pressure switch

Advertisement

IMPORTANT:
The scale plate is only for reference and for more
precise setting a pressure gauge should be used.
Adjustment:
Low Pressure Switch
Cut out on pressure fall
with automatic reset.
Scale plate directly indicates
the Cut In and the Differential
set points.
Adjustment:
Low Pressure Switch
Cut out on pressure fall
with manual reset.
Scale plate directly indicates the Cut
Out set point. There is no pointer for
the Differential.
The Differential pressure value is
fixed and printed on the scale plate.
Adjustment:
Condenser Fan Cycling
Scale plate directly indicates
the Cut In and the Differential
set points.
Adjustment:
High Pressure Switch
Cut Out on pressure
rise with automatic reset.
Scale plate directly indicates
the Cut Out and the Differential
set points.
Adjustment:
High Pressure Switch
Cut Out on pressure
rise with manual reset.
Scale plate directly indicates
the Cut Out set point.
There is no pointer for the
Differential.
The Differential pressure value is
fixed and printed on the scale plate.
4 | 520H11543 | DKRCC.PI.CD0.F4.22
1. Set Cut In by adjusting range screw.
1
2
2. Then set Differential by adjusting differential screw. Turn the
3. The Cut Out setting equals the Cut In
1. Set Cut Out by adjusting range screw.
1
2. The Cut In setting equals the Cut Out plus
1. Set Cut In by adjusting range screw.
1
2
2. Then set Differential by adjusting differential screw. Turn the
3.The Cut Out setting equals the Cut In less
1. Set Cut Out by adjusting range screw.
1
2
2. Then set Differential by adjusting differential screw. Turn the
3. The Cut In setting equals the Cut Out
1. Set Cut Out by adjusting range screw.
1
2. The Cut In setting equals the Cut Out
IMPORTANT:
After installing and adjusting pressure switch run the
controlled equipment several times (at least three
cycles) at normal operating conditions.
Turn the screw clockwise to lower the set point.
screw clockwise to increase the Differential.
less the Differential: CUT OUT = CUT IN - DIFFERENTIAL
NOTE:
Cut Out set point must be above absolute vacuum!
If the Differential is set too high then the switch
will not stop the compressor.
Turn the screw clockwise to lower the set point.
the Differential: CUT IN = CUT OUT + 10 psi
Turn the screw clockwise to lower the set point.
screw clockwise to increase the Differential.
the Differential: CUT OUT = CUT IN - DIFFERENTIAL
Turn the screw clockwise to lower the set point.
screw clockwise to decrease the Differential.
less the Differential: CUT IN = CUT OUT - DIFFERENTIAL
Turn the screw clockwise to lower the set point.
less the Differential: CUT IN = CUT OUT - 60 psi