TEMPERATURE CONTROLLER FOR IMPULSE SEALING THERMOSALD UPSCR AUTOMATIC CALIBRATION • MANUAL BALANCING at first start up • AUTOMATIC BALANCING at sealing band change • BURN IN of sealing band • AUTOMATIC POWER FREQUENCY SWITCHING • ENERGY CONTROL ON SEALING BAND •...
- When the machine is running under normal conditions, make sure the heat sink of the controller does not exceed 60°C . If this happens, increase heat sink ventilation or contact our engineering department. THERMOSALD UPSCR_M_V4 – USE AND MAINTENANCE MANUAL - Rev. 2001 / 05 Page N.
Page 3
89/336 CEE standards and following amendments • The manufacturer states that the temperature controller fully complies with current low voltage electrical codes 73/23 CEE and subsequent amendments. THERMOSALD UPSCR_M_V4 – USE AND MAINTENANCE MANUAL - Rev. 2001 / 05 Page N. - Tot.
Annex D FAULTS AND WARNINGS LIST ( CAUSES - REMEDIES ) Annex E DIMENSIONS Annex F MULTIVOLTAGE TRANSFORMERS TECHNICAL FEATURES Annex G STAR UP CARD THERMOSALD UPSCR_M_V4 – USE AND MAINTENANCE MANUAL - Rev. 2001 / 05 Page N. - Tot.
DIAGNOSTICS: The temperature controller comes with an efficient diagnostics system capable of identifying faults which have occured during the production process, indicating the cause and suggesting the remedies required to restore normal operating conditions. THERMOSALD UPSCR_M_V4 – USE AND MAINTENANCE MANUAL - Rev. 2001 / 05 Page N.
1.2 BLOCK DIAGRAM CONTROL TRANSF. PANEL MAINS CONTROL POWER CIRCUIT MAINS BAND THERMOSALD UPSCR_M_V4 – USE AND MAINTENANCE MANUAL - Rev. 2001 / 05 Page N. - Tot.
Page 8
CN1/5 should be connected to the EARTH ELECTRODE of the machine by using a yellow- green wire whose size should be >= that of the power leads. THERMOSALD UPSCR_M_V4 – USE AND MAINTENANCE MANUAL - Rev. 2001 / 05 Page N.
If You DON’T USE AN ORIGINAL band 3E included in the underlying tables, You must measure the band resistance directly on te contact with a precision instrument. [ Ω Ω Ω Ω ] Resistance: R-BAND= ……………………. THERMOSALD UPSCR_M_V4 – USE AND MAINTENANCE MANUAL - Rev. 2001 / 05 Page N. - Tot.
ACTIVE I SHORT C. (SEZ.) (RATED I) MAXIMUM CURRENT 8 x 0,2 x 2 180 Amp 210 Amp Thermoregulator model: UPSCR_M_V4_100……. [ 30/60/90 Ampere ] THERMOSALD UPSCR_M_V4 – USE AND MAINTENANCE MANUAL - Rev. 2001 / 05 Page N. - Tot.
VOLTAGE will be 0.4 Ohm x 60 Ampere x 1.5 = 36 Volts a.c.. Trasformer: POWER = ……………………. [ VA ] PRIMARY = ……………………. [ V ] SECONDARY = ……………………. [ V ] THERMOSALD UPSCR_M_V4 – USE AND MAINTENANCE MANUAL - Rev. 2001 / 05 Page N. - Tot.
- Primary 230V: Automatic breaker 16A type D (o del-action-fuse) - Primary 400V: Automatic breaker 10A type D (o del-action-fuse) - Secondary: Automatic breaker 100 A type D (o del-action-fuse) THERMOSALD UPSCR_M_V4 – USE AND MAINTENANCE MANUAL - Rev. 2001 / 05 Page N.
Mount the thermoregulator leaving a rigth space around for cooling: 5 cm about for model 30Ampere 8 cm about for model 60 Ampere 10 cm about for model 90 Ampere THERMOSALD UPSCR_M_V4 – USE AND MAINTENANCE MANUAL - Rev. 2001 / 05 Page N. - Tot.
Page 17
SOMETIME IT’S POSSIBLE TO USE TEFLON COATED BANDS; THE CONTROL IS MORE PRECISIOUS BUT MACHINE INCREASE THE STOPS FOR CHANGING BANDS USE AN ELASTIC SYSTEM TO MAINTAIN BANDS TIGHT THERMOSALD UPSCR_M_V4 – USE AND MAINTENANCE MANUAL - Rev. 2001 / 05 Page N. - Tot.
Page 18
• CONNECTIONS TO THERMOREGULATOR THERMOSALD UPSCR_M_V4 – USE AND MAINTENANCE MANUAL - Rev. 2001 / 05 Page N. - Tot.
58 - 65 66 - 75 76 - 82 83 - 92 93 - 97 97 - 100 ( TO LIGHT RED LED) THERMOSALD UPSCR_M_V4 – USE AND MAINTENANCE MANUAL - Rev. 2001 / 05 Page N. - Tot.
Page 23
In applications where a great precision of temperature is necessary, it is possible change this parameter and set it with the actual gripper jaws temperature, simply pressing keys DOWN / UP. 9 - Wait THERMOSALD UPSCR_M_V4 – USE AND MAINTENANCE MANUAL - Rev. 2001 / 05 Page N.
Page 24
(As previous software release, it’s possible to change this parameter entering in the SETTING DATA or HOT CALIBRATION DATA, pressing key UP+RESET 6 seconds, see ANNEX C) THERMOSALD UPSCR_M_V4 – USE AND MAINTENANCE MANUAL - Rev. 2001 / 05 Page N.
NOTE – Each time the pre-heating and sealing temperature or some machine data are changed, an automatic data acquisition needs to be performed. 4.5 - SPECIAL FUNCTION 485 SERIAL INTERFACE AND FIELD BUS (IN PROGRESS) THERMOSALD UPSCR_M_V4 – USE AND MAINTENANCE MANUAL - Rev. 2001 / 05 Page N. - Tot.
WOULD YOU LIKE TO UPDATE OLD MACHINES WITH NEW SOFTWARE RELEASE? For this procedure do not exitate to contact our technical office. From Thermosald Hardware M it is possible update machine without loose any performance; for older units needs pay attention to. This operation is easy enough, but must be done only by skilled workers with experience.
(used only in the course of first start up, after a master reset) or pressing the up/down keys to do an automating balancing (used only after a change of the sealing band) THERMOSALD UPSCR_M_V4 – USE AND MAINTENANCE MANUAL - Rev. 2001 / 05 Page N.
200 and 100 degrees are in progress. At the end the termoregulator will be ready to work. Burn in cycle can be stopped before end pressing key reset. THE MACHINE IS READY TO WORK. THERMOSALD UPSCR_M_V4 – USE AND MAINTENANCE MANUAL - Rev. 2001 / 05 Page N. - Tot.
1 – Verify that the reference and power terminals are screw tight 2 – Verify that the connections of the bands are good without oxidation. 3 – Verify the teflon and the isolation of gripper jaws THERMOSALD UPSCR_M_V4 – USE AND MAINTENANCE MANUAL - Rev. 2001 / 05 Page N.
LEVEL OF BOARD PROTECTION IP00 LEVEL OF DISPLAY CONSOLE PROTECTION IP65 POWER ASSEMBLY WEIGHT 2.5 Kg PANEL WEIGHT 0.3 Kg PANEL-POWER ASSEMBLY EXTENSION WEIGHT 0.2 Kg THERMOSALD UPSCR_M_V4 – USE AND MAINTENANCE MANUAL - Rev. 2001 / 05 Page N. - Tot.
7 – DETAILS FOR ORDER FORM 7.1 DETAILS FOR ORDER FORMS MODEL - Description CODE THERMOSALD UPSCR - Impulse Thermoregulator 100V 30A UPSCR_M_V4_10030 THERMOSALD UPSCR - Impulse Thermoregulator 100V 60A UPSCR_M_V4_10060 THERMOSALD UPSCR - Impulse Thermoregulator 100V 90A UPSCR_M_V4_10090 PANEL 3ESD0039 - Digital panel data input...
Page 32
For other informations don’t exitate to contact our technical office. PRE-HEATING SIGNAL (IN THERMOSALD) SEALING SIGNAL (IN THERMOSALD) closed FILM GRIPPER JAWS open closed BAND SEALERS open COOLING FILM FEED THERMOSALD UPSCR_M_V4 – USE AND MAINTENANCE MANUAL - Rev. 2001 / 05 Page N. - Tot.
Page 33
This parameter is used to set an istantaneous current threshold, above which a partial short-circuit occurs and the thermoregulator sends fault signal F097. The standard istantaneous current is acquired during the balancing or burn-in procedures. THERMOSALD UPSCR_M_V4 – USE AND MAINTENANCE MANUAL - Rev. 2001 / 05 Page N.
Page 34
Internal parameter. Set 0 to disable alarm 63 and phase control PHLL. • BARRA CODICE 4 - MAXIMUM ERROR 1/10000 PERIOD MAINS SUPPLY FREQUENCY Internal parameter. THERMOSALD UPSCR_M_V4 – USE AND MAINTENANCE MANUAL - Rev. 2001 / 05 Page N. - Tot.
Page 35
10 seconds es. .008 (Note the point at the left of number) • A.XXX - VOFFSET Internal parameter. • B.XXX - MAXIMUM SEALING TEMPERATURE Internal parameter. • C.XXX - ANALOG INPUT Internal parameter. THERMOSALD UPSCR_M_V4 – USE AND MAINTENANCE MANUAL - Rev. 2001 / 05 Page N. - Tot.
Page 36
Verify bands characteristic, leave the machine cooling, repeat operation, if the problem persists do not exitate to contact our technichal office. MAINS SUPPLY FREQUENCY OUT OF RANGE THERMOSALD UPSCR_M_V4 – USE AND MAINTENANCE MANUAL - Rev. 2001 / 05 Page N.
Page 37
SHORT CIRCUIT BETWEEN THE BANDS OR BETWEEN A BAND AND GROUND IN THE CASE OF HIGH CURRENT Verify bands, Verify power connectios between thermoregulator and bands. FAULT I 2 T F091 Verify currents. THERMOSALD UPSCR_M_V4 – USE AND MAINTENANCE MANUAL - Rev. 2001 / 05 Page N. - Tot.
Page 38
Verify power on the transformer, Verify Voltage on CN1/1-CN1/2 connector, Verify breaking of power cables, Verify breaking of bands. F099 FAULT EEPROM Do not exitate to contact our technichal office. THERMOSALD UPSCR_M_V4 – USE AND MAINTENANCE MANUAL - Rev. 2001 / 05 Page N. - Tot.
Page 39
ANNEX E – DIMENSIONS THERMOREGULATOR DIMENSIONS SIDE VIEW FRONT VIEW 170 180 THERMOSALD UPSCR_M_V4 – USE AND MAINTENANCE MANUAL - Rev. 2001 / 05 Page N. - Tot.
Page 40
PANEL DIMENSION FRONT VIEW 90 mm 60 mm HOLE PLAIN 73 mm 55 mm 85 mm N. 2 HOLES 3,5 mm THERMOSALD UPSCR_M_V4 – USE AND MAINTENANCE MANUAL - Rev. 2001 / 05 Page N. - Tot.
Page 41
OUTPUTS TERMINALS: (IP20) INSULANCE TREATMENT: Impregnating by insulance paint auto-extinguishing type BC359/D green Class “F” DRYING: oven-drying of the insulance paints , after treatment THERMOSALD UPSCR_M_V4 – USE AND MAINTENANCE MANUAL - Rev. 2001 / 05 Page N. - Tot.
Page 42
OUTPUTS TERMINALS: (IP20) INSULANCE TREATMENT: Impregnating by insulance paint auto-extinguishing type BC359/D green Class “F” DRYING: oven-drying of the insulance paints , after treatment THERMOSALD UPSCR_M_V4 – USE AND MAINTENANCE MANUAL - Rev. 2001 / 05 Page N. - Tot.
Page 43
Type of connections (Parallel/Serial) = _______________________ [P/S] TECNICHAL NOTE RESISTANCE OF THE SEALING = _______________________ [Ω] RATED CURRENT OF THE THERMOSALD = _______________________ [30/60/90 A] SECONDARY VOLTAGE OF THE TRANSFORMER = ______________________ [V] MODEL OF THE THERMOSALD = _______________________ [UPSCR_M_V4_……]...
Page 44
Mains supply frequency 9. [ xxx ] Voffset A. [ 400] Max sealing temperature B. [ 250 ] Analog input C. [ xxx ] THERMOSALD UPSCR_M_V4 – USE AND MAINTENANCE MANUAL - Rev. 2001 / 05 Page N. - Tot.