Product Information Information produit Informazioni sul prodotto Información sobre producto CP 343–1 Deutsch / English / Français / Italiano / Español E SIEMENS AG 1998 Änderungen vorbehalten Subject to alteration Sous réserve de modifications Con riserva di modifiche Sujeto a cambios C79000–Z8964–C038–05...
Copyright E Siemens AG 1998..1999 All rights reserved The reproduction, transmission or use of this document or its contents is not permitted without express written authority.
The CP 343-1 Communications Processor Application The CP 343-1 communications processor is designed for operation in an S7-300 programmable logic controller. It allows the S7-300 to be attached to Industrial Ethernet. Figure 1 CP 343-1 Design The module has been designed to match the components of the S7-300 programmable logic controller and has the following features: S Double-width module for simple installation in the S7-300 rack.
The full functionality including the extended functions as listed in Section 1.1 can be used. Information about the required service pack (SP2) is available on the Internet at: http://www.ad.siemens.de/csi/net Characteristics Services The CP 343-1 supports the following communication services: S S5-compatible communication with –...
Page 7
Note If there is a diagnostic connection to the CP via the CPU, configuration data cannot be downloaded automatically to the CP by the CPU at the same time! Extended Functions Compared with Version 5 S Reading and writing data in the FETCH/WRITE mode The services FETCH and WRITE are supported for direct access to sy- stem memory areas on the SIMATIC S7 PLC via ISO transport and and ISO-on-TCP connections.
Page 8
english Table 2 CPU 614 6ES7 614–1AH03–0AB3 CPU 614–Z 6ES7 614–1AH03–0AB3–Z The table lists the CPUs approved at the time of printing this product informa- tion bulletin. S7–300 CPUs approved later and not listed in the table also support the range of functions described here. All versions of the SINUMERIK CPUs 840D and 810D are supported.
Performance Data 1.2.1 Characteristics of S7 Communication The functions and characteristics of S7 communication are described in /8/ and /11/. 1.2.2 Characteristics of ISO Transport Connections The following information is important for operating ISO transport connections (SEND/RECEIVE interface): Table 4 Characteristic Total number of connections on Industrial Ethernet...
english Table 5 Component Run time in the CPU 314-1 Displays and Mode Selector LED Displays The LED panel on the front of the CP 343-1 has three display elements: STOP Figure 2 LED Displays CP Operating Mode The LEDs indicate the current operating mode of the CP 343-1 as follows: STOP–LED RUN–LED (yellow)
Page 11
STOP–LED RUN–LED (yellow) (green) Legend: Note Read the explanations of the operating modes in the NCM S7 for Industrial Ethernet manual /8/. Controlling the Operating Mode There are three ways in which you can control the mode of the CP 343-1, as follows: S Mode selector S From a PG/PC.
english Note Read the sections about downloading configuration data to the CP in the NCM S7 for Industrial Ethernet manual /8/. Further Information on Operation Downloading Firmware The CP 343-1 supports firmware updates using the Firmware Loader. An update of the firmware can be downloaded from the PC/programming de- vice at any time.
Status on the FC call interface; special situation with FC versions With the FCs AG_SEND (FC 5) and AG_RECV (FC 6), you receive the follo- wing return values after a connection is aborted: S AG_SEND: DONE=1; ERROR=0; Status=0000 S AG_RECV: DONE=0; ERROR=1; Status=8183 The new FCs for longer data fields (FC AG_LSEND and AG_LRECV) react in exactly the same way to a connection abort, in other words with the return values...
english Procedure Steps in Installation Installing the CP 343-1 involves the following steps. S Plug in the CP 343-1 and secure it with the screws (make sure that the bus connector between the CPU/IM and CP 343-1 is present). S Attach the CP 343-1 to Industrial Ethernet as illustrated in Section 2.3. S Connect a 24 V power supply.
Attaching the CP 343-1 to Industrial Ethernet The CP 343-1 can be attached to Industrial Ethernet using a S Transceiver with an AUI interface CP 343–1 STOP STOP Transceiver Figure 3 Attaching the CP 343-1 to Industrial Ethernet with AUI/Transceiver The CP 343-1 generates and supplies the 13 V power required by the transceiver.
Page 16
english CP 343–1 e.g Optical Switch Modul STOP (OSM) STOP Figure 4 Attaching the CP343-1 to Industrial Ethernet with TP/Optical Switch Module (OSM) or Hub S Optical Industrial Ethernet using an AUI attachment Connection of the CP 343-1 TCP to Industrial Ethernet is also possible using an optical transceiver with an AUI interface.
Technical Data General Technical Data Dimensions and Weight Dimensions, module in casing H x W x D (mm) Weight Voltage, Current, Operating Conditions Power supply Current consumption: – from the S7-300 backplane bus: – from the external 24 V supply: Permitted ambient temperature Specifications according to /7/ must be adhered to when operating an S7-300 tier...
english Pinout Connector for Industrial Ethernet On the front panel of the CP 343-1, there is a 15-pin sub D female connector with a sliding locking mechanism for connecting a transceiver cable. The signals of an ITP interface can also be applied to this connector (switchover by relay).
89/336/EEC ”Electromagnetic Compatibility”. The EU conformity certificates are available for the relevant authorities accor- ding to the EU directives and are kept at the following address: Siemens Aktiengesellschaft, Bereich A&D Industrielle Kommunikation SIMATIC NET (A&D PT 2) Postfach 4848 D–90327 Nürnberg...
SIMATIC NET Manual: ITP Networks for Industrial Ethernet Order Numbers The order numbers for the SIEMENS documentation listed above can be found in the catalogs “SIMATIC NET Industrial Communication, Catalog IK 10” and “SIMATIC Programmable Logic Controllers SIMATIC S7 / M7 / C7”.
Page 21
Type of cabling Network topology Suggestions: ... Note: Your information will be used to improve our products and will of course be handled confidentially. Suggestions for improvement are welcome on e-mail address simatic.net@nbgm.siemens.de. Please include for identification “CP 343-1”. From Name...