INSTALLATION INSTRUCTIONS
TC846A1005 Pinnacle™
Intelligent Laser Smoke Sensor
Installation in XLS Fire Alarm Systems
SPECIFICATIONS
Electrical Ratings:
Operating Voltage:
Standby Current (maximum average):
GENERAL
The TC846A1005 Pinnacle™ Laser Smoke Detector can be used with the Hon-
eywell XLS1000 fire alarm control panel. The TC846A1005 is configured in
the SDU data file from the TC846 tab in the 3-AADC configuration screen.
The TC846A1005 is connected to the 3-AADC Analog Addressable Device Con-
troller using a Honeywell B210LP standard base, B224RB relay base, B224BI
isolator base, B501BH Horn Base, or B501BHT Temporal Tone Sounder Base.
PREINSTALLATION
Configure and install the XLS1000 fire alarm control panel with a 3-AADC An-
alog Addressable Device Controller as described in form no. 95-7545, XLS1000
Installation and Service Manual. When configuring the database using the
SDU, use the TC846 smoke detector parameters.
NOTE: For use with the DeltaNet FS90 Fire & Security System, refer to form no.
95-7421, DeltaNet FS90 Fire & Security System Installation Instructions.
WIRING
The TC846A1005 Pinnacle™ Laser Smoke Detector is wired to the 3-AADC
loop by using a separate Honeywell Plug-in Detector Base. Terminal 1 is wired
to the negative polarity (–) side of the loop, and terminal 2 is wired to positive
polarity (+) side of the loop. See Fig. 5.
CHECKOUT
Standard checkout procedures are used for commissioning the TC846A1005
Pinnacle™ Laser Smoke Detector when used with the XLS1000 and 3-AADC.
Please refer to insert for the Limitations of Fire Alarm Systems
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must
accept any interference received, including interference that may cause undesired operation.
NOTE: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses and can radiate radio frequency
energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential
area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
15 VDC to 32 VDC peak
220µA 24 VDC (without communication), 330µA at 24 VDC
(one communication every five seconds with LED enabled)
FCC STATEMENT
FIGURE 5. TYPICAL WIRING FROM TC846A1005 TO XLS1000.
WITH B201LP BASE
+
1
B
B
S
A
A
N/C
B
B
N/C
+
+
+
H
LOOP1
LOOP1
LOOP1
CIRCUIT 1
3-AADC
4
1985 Douglas Drive North
Golden Valley, MN 55422 USA
customer.honeywell.com
Honeywell Control Systems Ltd
Honeywell House, Arlington Business Park
Bracknell, Berkshire RG12 1EB UK
TC846A1005
REQUIRED FOR
CLASS A ONLY
IF SHIELD USED, MUST BE CONTINUOUS
1
AND FREE FROM EARTH GROUND.
NOTE: ALL WIRING SUPERVISED
AND POWER LIMITED.
0832
DOP# 0832-CPD-0193
16
I56-0060-007