Replace Battery In Panelview Component Terminals - Allen-Bradley 2711P-RY2032 Installation Instructions Manual

Battery replacement
Table of Contents

Advertisement

5. Locate the battery on the
circuit board.
6. Remove the battery by lifting
the side of the battery.
7. Insert the new battery with
the positive polarity (+)
facing up.
IMPORTANT
The battery can be removed for up to 15 seconds without losing the clock and calendar data.
8. Reattach the logic module by aligning the logic module connector with the connector
on the display module.
Logic Module
9. Push down on the logic module until it is firmly seated.
10. Tighten the captive screws that secure the logic module to the display module and torque
to 0.58...0.79 N•m (5...7 lb•in).
11. Reattach the communication module, if necessary, and tighten the screws to a torque of
0.58...0.79 N•m (5...7 lb•in).

Replace Battery in PanelView Component Terminals

The PanelView Component C400, C600, and C1000 terminals, catalog numbers 2711C-T4T,
2711C-T6x, and 2711C-T10C, contain a lithium battery on the back of the terminal. No
special tools are required to remove the battery cover and replace the battery.
Follow these steps to replace the battery in the PanelView Component terminals.
1. Disconnect power from the terminal.
2. Remove or unlatch the battery cover on the back of the terminal.
Rockwell Automation Publication 2711P-IN009J-EN-P - December 2017
Battery Replacement
Captive Screw
5